FRIGA-BOHN MOSC Compressor Rack

Overview
This manual provides dimensional characteristics, handling guidance, technical data for MOSC positive/negative compressor rack models, and installation/technical details for oil level and liquid level monitoring components used with compressor systems.
Specifications
| Specification | Details |
|---|---|
| Dimensional characteristics (MOSC models) — H / P / A / L’ / P’ / H’ | Positive: MOSC 64/5P: 1400 / 800 / 655 / 650 / 620 / 1700; MOSC 90/5P: 1400 / 800 / 655 / 650 / 620 / 1950; MOSC 108/6P: 1400 / 1000 / 755 / 650 / 620 / 1950; MOSC 110/5P: 1400 / 1000 / 755 / 650 / 620 / 1950; MOSC 129/5P: 1400 / 1000 / 755 / 650 / 620 / 1750; MOSC 132/6P: 1400 / 1000 / 755 / 650 / 620 / 1750; MOSC 154/6P: 1400 / 1000 / 755 / 650 / 620 / 1750. Negative: 20/5N: 1400 / 800 / 655 / 650 / 620 / 1700; 23/5N: 1400 / 800 / 655 / 650 / 620 / 1700; 28/6N: 1400 / 1000 / 755 / 650 / 620 / 1950; 35/5N: 1400 / 1000 / 755 / 650 / 620 / 1750; 38/5N: 1400 / 1000 / 755 / 650 / 620 / 1750; 42/6N: 1400 / 1000 / 755 / 650 / 620 / 1750; 45/6N: 1400 / 1000 / 755 / 650 / 620 / 1750. |
| Weight — liquid station | Positive: MOSC 64/5P: 140 kg; 90/5P: 190 kg; 108/6P: 190 kg; 110/5P: 190 kg; 129/5P: 230 kg; 132/6P: 230 kg; 154/6P: 230 kg. Negative: 20/5N: 140 kg; 23/5N: 140 kg; 28/6N: 190 kg; 35/5N: 230 kg; 38/5N: 230 kg; 42/6N: 230 kg; 45/6N: 230 kg. |
| Compressor weights (positive/negative) | Positive: 64/5P (5 x ZB56) 820 kg; 30/5P (5 x ZB75) 820 kg; 110/5P (5 x ZB92) 890 kg; 129/5P (5 x ZB11) 930 kg; 108/6P (6 x ZB75) 980 kg; 132/6P (6 x ZB92) 1040 kg; 154/6P (6 x ZB11) 1100 kg. Negative: 20/5N (5 x ZF24) 820 kg; 23/5N (5 x ZF33) 820 kg; 35/5N (5 x ZF40) 890 kg; 38/5N (5 x ZF48) 930 kg; 28/6N (6 x ZF33) 980 kg; 42/6N (6 x ZF40) 1040 kg; 45/6N (6 x ZF48) 1100 kg. |
| Technical data — Positive models (I max / I dem / P max) | 64/5P: 80 A / 163 A / 40 kW; 90/5P: 110 A / 222 A / 61 kW; 110/5P: 125 A / 269 A / 68 kW; 129/5P: 150 A / 307 A / 83 kW; 108/6P: 132 A / 244 A / 73 kW; 132/6P: 150 A / 294 A / 82 kW; 154/6P: 180 A / 337 A / 99 kW. |
| Technical data — Negative models (I max / I dem / P max) | 20/5N: 81 A / 163 A / 43 kW; 23/5N: 112 A / 223 A / 65 kW; 35/5N: 126 A / 259 A / 73 kW; 38/5N: 155 A / 311 A / 85 kW; 28/6N: 97 A / 180 A / 52 kW; 42/6N: 134 A / 246 A / 77 kW; 45/6N: 151 A / 285 A / 87 kW. |
| Oil level regulator — INT280 | Supply voltage: AC 24V 50/60Hz ±10%, 15VA; AC 115V 50/60Hz ±10%, 15VA; AC 230V 50/60Hz ±10%, 15VA. Permitted ambient temperature: -30…+60°C. Medium temperature: -30…+100°C. Operating pressure: -1…46 bar. Differential pressure: 1…25 bar (across valve). Relay: AC 240V, 2.5A, C300. Protection class: IP65 (per EN 60529). Connecting cable: 6xAWG18 (0.75 mm²), length 1 m. Housing material: Aluminium and PA66/PA6 (glass-fibre-reinforced). Flange connection: 3- / 4-hole flange. Oil connection: 7/16-20 UNF. Permitted oils: standard mineral and ester oil, without additives. Permitted refrigerants: all non-corrosive standard refrigerants. Weight: approx. 950 g. Mechanical service life: approx. 10^6 switching cycles (stated as approx. 106). Mechanical service life also stated as approx. 106 switching cycles. |
| Liquid level monitoring — INT275 L | Optical, contactless level monitoring. Relay on delay after supply voltage: about 3 s (3s±1s). Relay off (low level) after: 5 s±2 s; relay off (fault) after: 5 s±2 s; relay on (level high again) after: 5 s±2 s; relay on (fault disappears) after: 5 s±2 s. Relay rating: AC250V, 2.5A, C300. Mechanical service life: approx. 106 switching cycles. Protection class: IP54 when mounted (per EN60529). Supply voltages listed: 230V version: INT275 L Level Monitoring, electrical part 52S475S60; 115V version: electrical part 41S475S60. Screw-in part: ambient temperature range -30…+60°C; max. temperature at prism +80°C; test pressure 32 bar; mounting M20x1.5mm (wrench size 24) or NPT1/2 (wrench size 24); weight approx. 75 g. Electrical part: ambient temperature range -30…+60°C; connecting cable 4xAWG18 (0.75mm²), L=1 m, colour-coded; weight approx. 80 g. |
Quick Guide
- Handling: Use a pallet truck or forklift truck and handle the unit from the front (compressor side).
- Oil level regulator INT280: Ensure the flange is properly tightened. Carry out the electrical connection according to the provided wiring diagram.
- Liquid level sensor INT275 L: Ensure seal tightness for the specific application. Clean the inside of the screw-in part and the prism. Fit the electrical part into the screw-in part and tighten the coupling ring (torque approx. 10 Nm). Position the lead so the cable exit is downwards. Complete the electrical wiring according to circuit suggestions. After filling the tank, check the tightness of all joints.
Dimensional characteristics
MOSC Positive
| 0oGHO | + [PP] | 3 [PP] | $ [PP] | / [PP] | 3 [PP] | + [PP] | :HigKt OiTXiG
station [kg] |
| MOSC 64/SP | 1400 | 800 | 655 | 650 | 620 | 1700 | 140 |
| MOSC 90/SP | 1400 | 800 | 655 | 650 | 620 | 1950 | 190 |
| MOSC 108/6P | 1400 | 1000 | 755 | 650 | 620 | 1950 | 190 |
| MOSC 110/SP | 1400 | 1000 | 755 | 650 | 620 | 1950 | 190 |
| MOSC 129/SP | 1400 | 1000 | 755 | 650 | 620 | 1750 | 230 |
| MOSC 132/6P | 1400 | 1000 | 755 | 650 | 620 | 1750 | 230 |
| MOSC 1S4/6P | 1400 | 1000 | 755 | 650 | 620 | 1750 | 230 |
MOSC Negative
| 0oGHO | + [PP] | 3 [PP] | $ [PP] | / [PP] | 3 [PP] | + [PP] | :HigKt OiTXiG station [kg] |
| 20/SN | 1400 | 800 | 655 | 650 | 620 | 1700 | 140 |
| 23/SN | 1400 | 800 | 655 | 650 | 620 | 1700 | 140 |
| 28/6N | 1400 | 1000 | 755 | 650 | 620 | 1950 | 190 |
| 3S/SN | 1400 | 1000 | 755 | 650 | 620 | 1750 | 230 |
| 38/SN | 1400 | 1000 | 755 | 650 | 620 | 1750 | 230 |
| 42/6N | 1400 | 1000 | 755 | 650 | 620 | 1750 | 230 |
| 4S/6N | 1400 | 1000 | 755 | 650 | 620 | 1750 | 230 |
Weight positive / Weight négative
| Model | Compressor | Weight (Kg) | model | Compresseur | Weight (Kg) |
| 64/SP | 5 x ZB56 | 820 | 20/SN | 5 x ZF24 | 820 |
| 30/SP | 5 x ZB75 | 820 | 23/SN | 5 x ZF33 | 820 |
| 110/SP | 5 x ZB92 | 890 | 3S/SN | 5 x ZF40 | 890 |
| 129/SP | 5 x ZB11 | 930 | 38/SN | 5 x ZF48 | 930 |
| 108/6P | 6 x ZB75 | 980 | 28/6N | 6 x ZF33 | 980 |
| 132/6P | 6 x ZB92 | 1040 | 42/6N | 6 x ZF40 | 1040 |
| 1S4/6P | 6 x ZB11 | 1100 | 4S/6N | 6 x ZF48 | 1100 |
Technical data
Positive / Négative
| MODEL | Compressors | I max
(A] |
I dem
[A] |
P max
[kW] |
MODEL | Compressors | I max
(A] |
I dem
[A] |
P max
[kW] |
| 64/5P | 5 x ZB56 | 80 | 163 | 40 | 20/5N | 5 x ZF24 | 81 | 163 | 43 |
| 90/5P | 5 x ZB75 | 110 | 222 | 61 | 23/5N | 5 x ZF33 | 112 | 223 | 65 |
| 110/5P | 5 x ZB92 | 125 | 269 | 68 | 35/5N | 5 x ZF40 | 126 | 259 | 73 |
| 129/5P | 5 x ZB11 | 150 | 307 | 83 | 38/5N | 5 x ZF48 | 155 | 311 | 85 |
| 108/6P | 6 x ZB75 | 132 | 244 | 73 | 28/6N | 6 x ZF33 | 97 | 180 | 52 |
| 132/6P | 6 x ZB92 | 150 | 294 | 82 | 42/6N | 6 x ZF40 | 134 | 246 | 77 |
| 154/6P | 6 x ZB11 | 180 | 337 | 99 | 45/6N | 6 x ZF48 | 151 | 285 | 87 |
Attention: Idem = maximum start current with timer for cascade start-up of compressors. (The compressors do not all start at the same time).
Handling
When using a pallet truck or forklift tuck, the unit must be handled from the front (compressor side). Please refer to the associated commercial and/or software documentation for further details.
Appendix 1: Installation log sheet
| Company:
Technician: |
Date | ||||
| Unit | Suction pressure | bar | |||
| Suction temperature | oc | ||||
| Delivery pressure | bar | ||||
| Power supply voltage (u, uv, uw) | V | ||||
| Cut-out value HP pressure switch | bar | ||||
| Cut-out value LP pressure switch | bar | ||||
|
Compressor 1 |
Input amperage (u, v, w) | A | |||
| Delivery temperature | oc | ||||
| Crankcase heater in good working order | YIN | ||||
| Oil level (full ¾ ½ ¼) | |||||
| Compressor 2 | Input amperage (u, v, w) | A | |||
| Delivery temperature | oc | ||||
| Crankcase heater in good working order | YIN | ||||
| Oil level (full ¾ ½ ¼) | |||||
| Compressor 3 | Input amperage (u, v, w) | A | |||
| Delivery temperature | oc | ||||
| Crankcase heater in good working order | YIN | ||||
| Oil level (full ¾ ½ ¼) | |||||
| Compressor
4 |
Input amperage (u, v, w) | A | |||
| Delivery temperature | oc | ||||
| Crankcase heater in good working order | YIN | ||||
| Oil level (full ¾ ½ ¼) | |||||
| Compressor 5 | Input amperage (u, v, w) | A | |||
| Delivery temperature | oC | ||||
| Crankcase heater in good working order | YIN | ||||
| Oil level (full ¾ ½ ¼) | |||||
| Compressor 6 | Input amperage (u, v, w) | A | |||
| Delivery temperature | oC | ||||
| Crankcase heater in good working order | YIN | ||||
| Oil level (full ¾ ½ ¼) | |||||
| Refrigerant Circuit | Presence of humidity | YIN | |||
| Pump down working correctly | YIN | ||||
| Refrigerant safety devices working correctly | YIN | ||||
| Hoses in good state | YIN | ||||
| Circuit sealing | YIN | ||||
| Electrical
Cabinet |
Connections properly tightened | YIN | |||
| Electrical safety devices working correctly | YIN | ||||
Appendix 2: Operating instructions for oil management system series “INT 280 -230V”
INT280 in the two mounting positions
Dimensions in mm
Wiring diagram (suggestion)
Application
The INT280 monitors and controls the oil level in the refrigerant compressors. In particular, the problem of poor oil distribution in multi-compressor packs is solved, thanks to active oil supply from a shared oil reservoir. The oil level regulator keeps the oil level at half the height of the sight glass.
Functional description
If the optical monitoring unit detects that the oil level is low, the integrated oil supply solenoid valve is activated by the electronics. Via the solenoid valve, oil is cyclically injected into the compressor crankcase. The INT280 generates an alarm signal and activates the relay output ifthe oil level is still too low after a defined period of time. During the “oil deficiency” alarm status, the electronics of the INT280 continue to operate the solenoid valve to inject oil into the crankcase. The alarm status is automatically reset if the oil level is at half the height ofthe sight glass.
LED status display
- Level OK: Green is continuously lit
- Filling: Green flashes
- Oil level too low: Red is continuously lit
- Internal error: Red flashes
Installation instructions
The user hæ to ensure that the image is properly tight. The eleariæl connætion to be carried out according to the wiring diagram. The unit must be connæted by traæd elEtrEal. All valid European and national standards for connæting dectri(Zlequipme-t must be observed.
Technical Specifications
| Specification | Details |
|---|---|
| Supply Voltage | AC 24V 50/60Hz ±10%, 15VA |
| Supply Voltage | AC 115V 50/60Hz ±10%, 15VA |
| Supply Voltage | AC 230V 50/60Hz ±10%, 15VA |
| Permitted Ambient Temperature | -30 to +60°C |
| Medium Temperature | -30 to +100°C |
| Operating Pressure | -1 to 46 bar |
| Differential Pressure | 1 to 25 bar (across valve) |
| Relay | AC 240V, 2.5A, C300 |
| Mechanical Service Life | Approx. 10⁶ switching cycles |
| Protection Class According to EN 60529 | IP65 |
| Connecting Cable | 6 × AWG18 (0.75 mm²), Length 1 m |
| Housing Material | Aluminium, PA66/PA6, Glass-Fibre-Reinforced |
| Flange Connection | 3-/4-hole flange |
| Oil Connection | 7/16″-20 UNF |
| Permitted Oils | Standard mineral and ester oil, without additives |
| Permitted Refrigerants | All non-corrosive standard refrigerants |
| Dimensions | Refer to dimensions |
| Weight | Approx. 950 g |
Order Data
| Supply Voltage | Order Number |
|---|---|
| AC 24V | 31 S 381 |
| AC 115V | 41 S 381 |
| AC 230V | 52 S 381 |
Appendix 3 : Operating instructions for level monitoring ” INT27SL ”
INT275 L
Connection diagram
Dimensions in mm
Application
The optical sensor INT275 L is developed for contactless level monitoring of liquids. A screw-in part mounted at the required location and a removable electrical part perform this function. The electrical part can be fitted or removed without opening the liquid tank. When the supply voltage is applied, the relay switches on after about 3s. In the absence of liquid or When a fault occurs, the relay trips after a delay. When liquid is present, or the fault disappears, the relay pulls in after a delay. The potential-free normally open contact can be directly wired in a control circuit without an additional auxiliary relay. An integrated self-monitoring circuit ensures high reliability. A mounting check eliminates wrong installation or manipulation.
Installation instruction
Mounting
The installer must ensure seal tightness for the application. The maximum tightening torque is approx. 75Nm. Clean the inside of the screw-in part as well as the prism. Fit the electrical part in the screw-in part and tighten the coupling ring (torque approx. I Nm), Pay attention to the position of the lead (cable exit downwards). Complete the electrical wiring in accordance with the attached circuit suggætions. After filling the tank, check the tightness of all joints.
| Specification | Details |
|---|---|
| Ambient Temperature Range | -30 to +60°C |
| Max. Temperature at Prism | +80°C |
| Test Pressure | 32 bar |
| Housing | VA 1.4510 or 1.4305 |
| Mounting | M20 × 1.5 mm, Wrench Size 24 |
| Mounting | NPT 1/2″, Wrench Size 24 |
| Weight | Approx. 75 g |
Technical Data: Electrical Part
| Specification | Details |
|---|---|
| Supply Voltage (52S…) | AC 230V, 50/60Hz ±10% |
| Supply Voltage (41S…) | AC 115V, 50/60Hz ±10% |
| Ambient Temperature Range | -30 to +60°C |
| Relay On After Supply Voltage On | 3s ±1s |
| Relay Off (Low Level) After | 5s ±2s |
| Relay Off (Fault) After | 5s ±2s |
| Relay On (Level High Again) After | 5s ±2s |
| Relay On (Fault Disappears) After | 5s ±2s |
| Relay | AC 250V, 2.5A, C300 |
| Mechanical Service Life | Approx. 10⁵ Switching Cycles |
| Housing | Ultramid A3XZG5 |
| Protection Class According to EN 60529 | IP54 When Mounted |
| Mounting | Coupling Ring on Screw-In Part |
| Connecting Cable | 4 × AWG18 (0.75 mm²), Length 1 m, Colour-Coded |
| Weight | Approx. 80 g |
Ordering Information
| Product / Version | Order Number |
|---|---|
| 230V Version: INT275 L Level Monitoring Electrical Part | 52S475S60 |
| 115V Version: INT275 L Level Monitoring Electrical Part | 41S475S60 |
| Screw-In Part M20 × 1.5 mm | 02K465 |
| Screw-In Part NPT 1/2″ | 02K460S22 |
The unit must be connected by trained electrical personnel. All valid standards for connecting electrical equipment must be observed. Limit values for the supply voltage of the unit may not be exceeded
- LFB France
- 42 rue Roger Salengro – 205
- 69741 GENAS CEDEX – FRANCE
- Tél. : +33 4 72 47 13 00 – Fax : +33 4 72 47 13 96
- www.frigabohn.com

Troubleshooting
- INT280 (oil level regulator) — oil level still too low: The INT280 generates an alarm signal and activates the relay output if the oil level remains too low after a defined period of time. During the oil deficiency alarm status, the electronics continue operating the solenoid valve to inject oil into the crankcase. The alarm status automatically resets when the oil level reaches half the height of the sight glass.
- INT280 LED status: Green continuously lit = Level OK. Green flashes = Filling. Red continuously lit = Oil level too low. Red flashes = Internal error.
- INT275 L (level monitoring) — relay behavior: When there is absence of liquid or a fault occurs, the relay trips after a delay (relay off after 5 s±2 s). When liquid is present, or the fault disappears, the relay pulls in after a delay (relay on after 5 s±2 s). After supply voltage is applied, the relay switches on after about 3 s (3s±1s).