Firecell-logo

Firecell FC-610-001 Wireless Input Output Unit

Firecell FC-610-001 Wireless Input Output Unit-fig1

 Pre installation

Installation must conform to applicable local installation codes and should only be installed by a fully trained competent person.

  • Ensure that the device is installed as per the site survey.
  • The use of a non-metallic spacer should be considered if mounting the device on to a metal surface.
  • Do NOT Press the Log On button on a pre-programmed device, as this will cause communication with the Control Panel to be lost.
  • Should this happen, delete the device from the system and add it back on.
  • This device contains electronics that may be susceptible to damage from Electrostatic Discharge (ESD). Take appropriate precautions when handling electronic boards.

Components

Firecell FC-610-001 Wireless Input Output Unit-fig2

  1. 4x lid fixing screws
  2. Front lid
  3. Back box

Remove cable entry points

Firecell FC-610-001 Wireless Input Output Unit-fig3

  • Drill the cable entry points as necessary.
  • Cable glands should be used.
  • DO NOT leave excess cable in the device.

Fix to the wall

Firecell FC-610-001 Wireless Input Output Unit-fig4

  • Use all four circled fixing positions to ensure a firm fixing.
  • Use suitable fasteners and fixings.

Input wiring

Firecell FC-610-001 Wireless Input Output Unit-fig5

  • Two resistor monitored inputs are available.
  • Both inputs monitor; closed (alarm), open and short circuit conditions.
  • Each input is factory fitted with an end of line 20 kΩ resistor.
  • To connect inputs to external devices, wire as shown below. I.e. Input 1, using the resistor pack provided.
  • If an input is not being used, leave the 20 kΩ resistor as factory fitted.

Output wiring

Firecell FC-610-001 Wireless Input Output Unit-fig6

  • Two outputs are also available.
  • Both outputs are voltage free and rated 2 A at 24 VDC.
    WARNING. DO NOT CONNECT TO MAINS.

Power device

Firecell FC-610-001 Wireless Input Output Unit-fig7

  • When fitting / replacing batteries; observe correct polarity, using only specified batteries.
  • Connect the power jumper across the PIN header.
  • Once powered, reassemble the device.

Configuration

The device’s loop address is configured within the user interface’s menu structure.

Refer to the programming manual for full programming details.

Firecell FC-610-001 Wireless Input Output Unit-fig8

LED operation

Firecell FC-610-001 Wireless Input Output Unit-fig9

 

The device has six indication LEDs. Pressing the LED enable button enables their illumination for 10 minutes before automatically timing out.

Firecell FC-610-001 Wireless Input Output Unit-fig10

Specification

Firecell FC-610-001 Wireless Input Output Unit-fig11

 

Regulatory Information

Firecell FC-610-001 Wireless Input Output Unit-fig12

 

 

Documents / Resources

Firecell FC-610-001 Wireless Input Output Unit [pdf] Installation Guide
FC-610-001 Wireless Input Output Unit, FC-610-001, Wireless Input Output Unit

References

Leave a comment

Your email address will not be published. Required fields are marked *