FNI MPL-302-105-M
IP 67 Module User Manual

FAS FNI MPL 302 105 M IP 67 Module -

Notes

1.1. Manual structure

This manual is organized by organization, so the chapters are interconnected. Section 2: Basic Safety Information.
Chapter 3: Getting Started Guide
Chapter 4: Technical data
……
1.2. Typography

The following typographic conventions are used in this manual.
Enumerate

The enumeration is displayed as a list with bullets.

  • Entry 1
  • Entry 2

Action

Action descriptions are represented by a front triangle.
The result of the action is represented by an arrow.
Action description 1
Action result
Action description 2
Step programs can also be displayed numerically in parentheses.
(1) Step 1
(2) Step 2

Grammar
Number:
Decimal numbers are displayed without additional indicators (eg 123) Hexadecimal numbers are displayed with an additional indicator hex (eg: 00hex ) or with the prefix “0X” (eg: 0x00) Cross-reference
1.3 symbol
Notes
This symbol indicates a general comment.
Notice!
This symbol indicates the most important safety notice.
————————————————– ———
Cross-references indicate where to find additional information on this topic.
1.4. Acronym

FNI FAS Network Interface
I Standard input port
PN Pofinet
ECT EtherCAT
CIE CC_link IEF Basic
EIP Ethernet/IP
EMC Electromagnetic Compatibility
FE functional ground
O Standard output port
1.5. Viewing deviations

The product views and explanations in this manual may deviate from the actual product. They are only left and right solutions

Safety

2.1. Intended use
This manual describes as decentralized input and Precautions! output modules for connection to an industrial network.
2.2.Installation and Startup

Installation and start-up may only be carried out by trained and specialized personnel. A qualified individual is one who is familiar with the installation and operation of the product and has the necessary qualifications to do so. Any damage caused by unauthorized operation or illegal and improper use is not covered by the manufacturer’s warranty. Equipment operators are responsible for ensuring that appropriate safety and accident prevention regulations are followed.
2.3. General Security Notes

Debug and check
Before debugging, you should read the contents of the user manual carefully.
The system cannot be used in applications where the safety of personnel depends on the functionality of the equipment. intended use
The manufacturer’s warranty coverage and limited liability statement do not cover damage caused by:

  • Unauthorized tampering
  • Improper use
  • Owner/operator’s obligations

This device is an EMC Class A product. This device generates RF noise.
The owner/operator must take proper precautions when using this equipment. Use only a power source compatible with this device and connect only approved cables.
Fault

In the event of a defect or equipment malfunction that cannot be corrected, the equipment must be taken out of operation to avoid possible damage from unauthorized use.
Intended use can only be ensured when the enclosure is fully installed.
2.4. Corrosion resistance Precautions!
FNI modules generally have good chemical and oil resistance characteristics. When used in aggressive media (e.g. high concentrations of chemicals, oils, lubricants and coolants (i.e. low water content)), these media must be checked before the corresponding application material compatibility confirm. If the module fails or is damaged due to this corrosive medium, no claim for defects can be claimed
Dangerous voltage
Disconnect all power sources before using the equipment!

Getting Started Guide

3.1. Module overview

FAS FNI MPL 302 105 M IP 67 Module - fig1

1 Mounting hole
2 Network port 2 Status
indicator
3 Network port 2
4 Power outlet
5 DIP switch
6 Port 1
7 Port 3
8 Port 5
9 Port 7
10 Port 6
11 Port 4
12 Port 2
13 Port Status
14 Port 0
15 Port Identification Board
16 Power input port
17 Module indicator
18 Network port 1
19 Network port 1 status indicator
20 Ground connection

3.2. Mechanical connection

The modules are attached using 2 M6 bolts and 2 washers.
Isolation pads are available as accessories.

3.3. Electrical connections
3.3. 1 Power interface(L-code )
Definition of power input port

FAS FNI MPL 302 105 M IP 67 Module - fig2

Definition of power output port

FAS FNI MPL 302 105 M IP 67 Module - fig3

Pin Function Describe
1 Us+ +24V
2 Ua-* 0V
3 Us- 0V
4 Ua+* +24V
FE Functional ground* FE

Notes:

  1.  If possible, supply sensor/module power and actuator power separately.
    Otal current <9A. The total current of all modules is <9A, even when daisy -chaining the actuator powersupply.
  2. The FE connection from the housing to the machine must be low impedance and kept as short as possible.

3.3.2 Network Interface (D-code)

FAS FNI MPL 302 105 M IP 67 Module - fig4

Pin Function
1 Tx+ Send data+
2 Rx+ Receive data+
3 Tx- Send data-
4 Rx- Receive data-

Notes:
Unused I/O port sockets must be covered with end caps to meet IP67 rating.
3.3.3
I/O-Port(A-code)

Pin Function
1 +24V,1A
2 Enter/output
3 0V
4 Enter/output
5 FE

Note:

  1. For digital sensor input, please follow the input guidelines of EN61131-2, Type 2.
  2. The maximum output current of pins 2 and 4 is 2A. The total current of the module is less than 9A.
  3. Unused I/O port sockets must be covered with end caps to meet IP67 degree of protection.

Technical data

4.1. size

FAS FNI MPL 302 105 M IP 67 Module - fig5

4.2 Mechanical data

Shell material Die-cast aluminum case, pearl nickel plated
Housing class according to IEC 60529 IP67 (only in plug-in or plug-in style)
Power interface L-Code (Male and Female)
Input port/output port M12, A-Code (8*female)
Size(W*H*D) 65mm*222mm*25.8mm
Installation type 2-Through Hole Mounting
Ground Bus Accessories M4
Weight About 670g

4.3. Operating conditions

Operating temperature -5°C ~ 70°C
Storage temperature -25°C ~ 70°C

4.4. Electrical data

Voltage 18~30V DC,Symbol EN61131-2
Voltage fluctuation <1%
Input current at supply voltage 24V <130mA

4.5 Network port

Port 2 x 10Base-/100Base-Tx
Port connection M12 ,D-Code
IEEE 802.3 Compliant Cable Types Shielded twisted pair, min. STP CAT 5/STP

CAT 5e

Ddata transfer rate 10/100 M bit/s
Maximum cable length 100m
Flow control Half condition/full condition(IEEE 802.3- PAUSE)

4.6 Function indicator

FAS FNI MPL 302 105 M IP 67 Module - fig6

PT Green EtherNet/IP communication protocol
Yellow ProfiNet communication protocol
Blue EtherCat communication protocol
White CC-Link IEField basic communication protocol

ECT Communication Protocol Module Status

LED State Function
US Green Power is OK
Red Greater than 30V or less than 11V
Flashing red less than 18V
UA Green Power is OK
Red Greater than 30V or less than 11V
Flashing red less than 18V
SF/MS/RU N Closure No error, device initialization
Green light flashing Pre-operational: The device is in a pre-operational state
2.5Hz Safe Operation: The device is in safe operation
Green light flashes 1HZ Running: The device is running
BF/NS/ERR Steady green No errors, device EtherCAT communication is working
Closure Invalid configuration
Red light flashes 2.5HZ local error
Red light flashes 1HZ Application watch timeout

EIP Communication Protocol Module Status

LED Show Function
 

 

 

 

 

SF/MS/RU N

Green light is always on Working status: The device is running normally
Green light flashes 1HZ Standby: Device not configured
Green, red and green flashing alternately Self-test: The device is undergoing a power-on test.
Flashing red 1HZ Recoverable failures:
Steady red light Unrecoverable failure
Closure US no input voltage
 

 

 

 

 

BF/NS/ER R

Green light is always on Connected
Green light flashes 1HZ  

Not connected:

Green and red off flashing alternately Self-test: The device is undergoing a power-on test.
Red light flashes 1HZ  

Connection timed out

Steady red light IP Duplicate:
Closure US No input voltage or no IP address
 

US

Green Input voltage is normal
Flashing red Low input voltage (< 18 V)
 

UA

Green The output voltage is normal
Flashing red Low output voltage (< 18 V)
Red always on No output voltage present (< 11 V)

PN Communication Protocol Module Status

LED Show Function
 

 

SF/MS/RU N

Closure Works fine
Red flashing 3s 1HZ Bus start
Red always on System error
 

 

BF/NS/E RR

Closure Works fine
Flashing red 2HZ No data exchange
Red always on No configuration; or slow physical link; or no physical link
 

US

Green Input voltage is normal
Flashing red Low input voltage (< 18 V)
 

UA

Green The output voltage is normal
Flashing red Low output voltage (< 18 V)
Red always on No output voltage present (< 11 V)

CIE Communication Protocol Module Status

LED Show Function
 

 

 

SF/MS/RUN

Green light off Module not connected
Green light flashing 2.5HZ Module not communicating
Green light flashes 1HZ Module is not configured
Steady green Running: The device is running
 

BF/NS/ERR

Closure Module works fine
Steady red light Communication error
 

US

Green Input voltage is normal
Flashing red Low input voltage (< 18 V)
 

UA

Green The output voltage is normal
Flashing red Low output voltage (< 18 V)
Red always on No output voltage present (< 11 V)

FAS FNI MPL 302 105 M IP 67 Module - fig7

I/O port status

LED State Function
1 Closure The status of Pin4 input or output is 0
1 Yellow The status of Pin4 input or output is 1
1 Red Port configured as input: short between Pin1 and 3
1 Flashing red Port configured as output: Pin4 overcurrent
2 Closure Port configured as output: short circuit between Pin1 and 3
2 Yellow The status of Pin2 input or output is 0
2 Red The state of Pin2 input or output is 1
2 Flashing red Port configured as input: short between Pin1 and 3

FAS FNI MPL 302 105 M IP 67 Module - fig8

Network port status

LED State Function
ACT Closure Bus rate: 10Mbit/s
Yellow Bus rate: 100Mbit/s
LK1 IN       (ECT IN) Flashing green Data transmission
LK2 IN       (ECT OUT) Flashing green Data transmission

Module configuration
5.1.1 Factory reset and communication protocol switching

FAS FNI MPL 302 105 M IP 67 Module - fig9

5.1.2 Network segment modification

FAS FNI MPL 302 105 M IP 67 Module - fig10

5.2 Data mapping

EIP PN ECT Communication protocol—process output data
Bytes  

Function

位( Bit)
7 6 5 4 3 2 1 0
0 PIN4 output Port7 Port6 Port5 Port4 Port3 Port2 Port1 Port0
1 PIN2 output Port7 Port6 Port5 Port4 Port3 Port2 Port1 Port0
Da t a de s c r i p t i o n ( b i n a r y ) : 0 = o f f 1 = o n
EIP PN ECT Communication protocol—process input data
Bytes  

Function

位( Bit)
7 6 5 4 3 2 1 0
0 PIN4 Enter Port7 Port6 Port5 Port4 Port3 Port2 Port1 Port0
1 PIN2 Enter Port7 Port6 Port5 Port4 Port3 Port2 Port1 Port0
2 PIN4 short circuit Port7 Port6 Port5 Port4 Port3 Port2 Port1 Port0
3 PIN2 short circuit Port7 Port6 Port5 Port4 Port3 Port2 Port1 Port0
4 Port power short circuit Port7 Port6 Port5 Port4 Port3 Port2 Port1 Port0
5  

Module status

Us

over volt age

Ua

over volt age

 

overhe at

 

Us underv oltage

 

Ua underv oltage

D a t a d e s c r i p t i o n ( b i n a r y ) : 0 = n o s i g n a l 1 = s i g n a l
EIP Communication Protocol—Port Configuration
Bytes  

Function

位( Bit)
7 6 5 4 3 2 1 0
0 PIN4 model Port3 Port2 Port1 Port0
1 PIN4 model Port7 Port6 Port5 Port4
2 PIN2 model Port3 Port2 Port1 Port0
3 PIN2 model Port7 Port6 Port5 Port4
Data description (binary): 00 = normally open input 01 = normally closed input 10 = output 11 = input and output adaptive
EIP Communication Protocol—Port Configuration
4 PIN4

Security Mode

Port3 Port2 Port1 Port0
5 PIN4

Security Mode

Port7 Port6 Port5 Port4
6 PIN2

Security Mode

Port3 Port2 Port1 Port0
7 PIN2

Security Mode

Port7 Port6 Port5 Port4
(On network outage) Safe Mode Configuration: 00 = Hold at 0 01 = Hold at 1 10 = Hold at last value
CIE communication protocol—process output data
Bytes  

Function

位( Bit)
7 6 5 4 3 2 1 0
0 PIN4 output Port7 Port6 Port5 Port4 Port3 Port2 Port1 Port0
1 PIN2 output Port7 Port6 Port5 Port4 Port3 Port2 Port1 Port0
Da t a de s c r i p t i o n ( b i n a r y ) : 0 = o f f 1 = o n
CIE communication protocol—process input data
Bytes  

Function

位( Bit)
7 6 5 4 3 2 1 0
0 PIN4 input Port7 Port6 Port5 Port4 Port3 Port2 Port1 Port0
1 PIN2 input Port7 Port6 Port5 Port4 Port3 Port2 Port1 Port0
2 PIN4 short circuit status Port7 Port6 Port5 Port4 Port3 Port2 Port1 Port0
3 PIN2 short circuit status Port7 Port6 Port5 Port4 Port3 Port2 Port1 Port0
4 Port power short circuit Port7 Port6 Port5 Port4 Port3 Port2 Port1 Port0
5  

Module status

Us

over volt age

Ua

over volt age

 

overhe at

 

Us underv oltage

 

Ua underv oltage

D a t a d e s c r i p t i o n ( b i n a r y ) : 0 = n o s i g n a l 1 = s i g n a l
*When the CIE ECT communication protocol is used, the PIN input and output mode does not need to be configured for self-adaptation

5.3 PLC Integration Tutorial
(The module communication protocol should be set before configuring the module, see 5.1.1 for details)
5.3.1 Siemens S7-1200 Portal Integration (PN)

  1. Install the GSD file
    FAS FNI MPL 302 105 M IP 67 Module - fig11
  2. InPLC—DeviceConfiguration—NetworkView—HardwareCatalog,selectthe moduleanddragitin,click” Unassigned”,andselectthePLCtobeconnected;
    FAS FNI MPL 302 105 M IP 67 Module - fig12
  3. Double-clickthemoduletoentertheconfiguration,
    (1)Slotfunctionconfiguration:Selecttherequireddatainthehardware catalog–moduleanddragitinto theslotinthedeviceoverviewwindow;
    (2)Moduleportfunctionconfiguration:clickthemoduleicon,select “General”,andthenclickslot1toconfiguretheportfunction
    FAS FNI MPL 302 105 M IP 67 Module - fig13
    (3) Module function configuration: Click the module icon, select “General”, and then click slot 0 to configure the module function
    FAS FNI MPL 302 105 M IP 67 Module - fig14(4)Aftertheconfigurationiscomplete,intheconfigurationview,clickDownload.
  4. AssignmodulePNname:PLCswitchtoonlinestate,select”ungroupeddevice”—clickonthe modulename—selectonlineanddi agn osis—function—assignPROFINETdevicename—-Select themoduletobeassignedinthelist(shouldbeselectedaccordingtothephysicalMAC)— Click”AssignName”tocompletetheconfiguration!.
    FAS FNI MPL 302 105 M IP 67 Module - fig15
  5. 3.2OMRONNX1P2SysmacStudioIntegrated(EIP)
    1.InstalltheEDSfile:Tools—ETHERNET/IPConnectionSettings—Double-clickPLCinthe window—right-clickontheblankspaceofth etoolboxontherightandselect”ShowEDS
    Library”,click”Install”inthepop-upwindow,andselectEDSfileinstallation
    FAS FNI MPL 302 105 M IP 67 Module - fig162.Createamodule:Click”+”inthetoolboxwindow,fillinthemoduleIPaddress,model name,version,andclick”Add”belowtoco mpletethemodulecreation;
    FAS FNI MPL 302 105 M IP 67 Module - fig17
    3.Configurationmodule:right-clickthemodule-select”Edit”-configurethecorresponding valuesintheparametersaccordingtoa ctualneedsandclickOKaftercompletion
    FAS FNI MPL 302 105 M IP 67 Module - fig184.Reateavariableassociation:
    (1)Programming–Data–Globalvariablescreatetwoarrays,output2bytes,input6bytes,and thecorrespondinginputandoutputsh ouldbeconfiguredinthenetworkdisclosure;
    FAS FNI MPL 302 105 M IP 67 Module - fig19(2)Inthebuilt-inETHERNET/IPportsettingwindow–selectthefirsticon(tab)onthe left–click”RegisterAll”
    FAS FNI MPL 302 105 M IP 67 Module - fig20(3)Inthebuilt-inETHERNET/IPportsettingwindow–selectthesecondiconontheleft (connection)–click”+”,thetargetdeviceselectsthepreviouslyconfiguredmodule,the IOtypeselectsEXCLUSIVEOwner,andthecorrespondinginputOutput,thetargetvariable mustbefilledwith101,100;thenselectthecorrespondingstartingvariable,andgoonline aftercompletion.Select”TransfertoContro ller”andtheconfigurationiscomplete!
    FAS FNI MPL 302 105 M IP 67 Module - fig215.3.3OMRONNX1P2SysmacStudioIntegrated(ECT)
    1.InstalltheESIfile:double-clickEtherCATintheconfigurationandsettings–right-clickthemasterdevice–select”ShowESIlibrary”,a ndselecttheESIfileinthepop-upwindowtoinstall
    FAS FNI MPL 302 105 M IP 67 Module - fig222.ConfigurethemoduletotheEtherCATnetwork:findtheFieldBusModulesinthe toolboxontheright,findthemodulemodeliconanddouble-clicktoaddittothe network
    FAS FNI MPL 302 105 M IP 67 Module - fig233. The PLC goes to online mode, right-click the master device, and write the node address of the slave device
    4. Variable mapping: Select the configured node in the I/O mapping, fill in the name of the variable, and the configuration is complete! .
    FAS FNI MPL 302 105 M IP 67 Module - fig245.3.4MitsubishiFX5UWork2Integrated(CIE)
    1.InstalltheCCSPfile:firstopenGXWORKS3-Tools-Configurationfilemanagement-Login-CSPPfile(theprojectmustbecl osedtoimportthefile)
    FAS FNI MPL 302 105 M IP 67 Module - fig25
    2. Click on the left side Project – Parameters – FX5UCPU – Module Parameters – Ethernet Port, Basic Settings – Self Node Settings. Set the own node IP
    FAS FNI MPL 302 105 M IP 67 Module - fig26
    3.ClickCC-LinkIEFBasicsettings-selectwhethertouseCC-LinkIEFBasic-clicktouse 4.ClickCC-LinkIEFBasicsettings-selectnet
    FAS FNI MPL 302 105 M IP 67 Module - fig27
    workconfigurationsettings-detailed settings;
    FAS FNI MPL 302 105 M IP 67 Module - fig28
    5.Automaticdetectionofconnecteddevices-occupy4stations,theIPaddressissetusing theDIPswitch-reflectthesettingandclose
    FAS FNI MPL 302 105 M IP 67 Module - fig29
    6.Selectthespecifiedsoftelementforrefreshtarget-softelementnameM-assignsoft elementaddress-application,theconfigur ationiscomplete!
    FAS FNI MPL 302 105 M IP 67 Module - fig30

Appendix

6.1.Included materials

FNI MPL contains the following components
·I/O-block
·4blindplugsM12 ·
Groundbus
·ThreadM4x6
·20tags
6.2.Ordercode

FAS FNI MPL 302 105 M IP 67 Module - fig31

6.3OrderingInformation

Productordercode Order code
FNI MPL-302- 105-M 007E11