THG03 CO2 Temperature and Humidity Transmitter
“
Product Information
Specifications
- Model: THG03, THR23, GS23
- Type: CO2, Temperature & Humidity Transmitter (Indoor)
- Manufacturer: eyc-tech
- Website: www.eyc-tech.com
Product Usage Instructions
Safety Precautions
Before using the product, read the user manual thoroughly and
follow the correct steps.
Avoid using the product in explosion-proof areas or dangerous
situations that may threaten human health and life.
If using the product in special environments like Dust-Free
Rooms or Animal Breed Environments, consult with professional sales
from the company.
Warnings
Ensure the product is not damaged during transportation and
check for any lost attachments.
Always operate the product in the specified environment to
prevent damages.
Perform wiring operations only when the power is off to avoid
electric shock or machinery breakdown.
Disconnect the power supply before any wiring or installation to
prevent equipment damage.
Installation
Installation and wiring should be done by qualified personnel
following safety standards and local codes.
All wiring must comply with indoor wiring and electrical
installation rules.
Use crimp type terminals to prevent personal injury and avoid
touching moving parts during operation.
Disposal
When discarding the product, comply with the relevant rules for
industrial domestic wastes in your country/location.
Connection Diagram
Dimension
Usage Precautions
FAQ
Q: Can this product be used outdoors?
A: No, this product is designed for indoor use only.
Q: What should I do if I encounter a malfunction?
A: Refer to the troubleshooting section of the user manual or
contact customer support for assistance.
“`
Operation-Manual
eyc-tech THG03, THR23, GS23 CO2, Temperature & Humidity Transmitter
(Indoor)
eyc-tech THG03, THR23, GS23
THG03, THR23, GS23 CO2, Temperature and Humidity Transmitter (Indoor)
Contents I. Safety Precautions ……………………………………………………………….. 3 II. Connection Diagram …………………………………………………………. 4 III. Dimension ………………………………………………………………………….. 4 IV. Usage Precautions …………………………………………………………….. 5 V. RS-485 & Modbus……………………………………………………………… 5 VI. Configuration …………………………………………………………………….. 6 VII. Inspection and maintenance …………………………………………13
www.eyc-tech.com
2
THG03, THR23, GS23
CO2, Temperature and Humidity Transmitter (Indoor)
I. Safety Precautions
Before using this product, the user must to read the details of this users manual, then use this product with correct steps.
This users manual is for reference while using / Setting this product, and required to conserve properly.
This product is improperly to use in explosion-proof area, do not use this product in dangerous situation where human health & life may be threaten & affected.
If the user installs this product in special environments as Dust-Free Room, Breed Environment for Animals, etc., please initiate a specialized product consultation to our professional sales of our company.
If the improper & dangerous results which result from improper operator or improper environment, our company will not bear any legal responsibility.
Warning
Please ensure the outlook / outbox do not have any damage which result from improper transportation, or malfunction which results from lost attachments.
In order to prevent the GM from damages. This product must be used in the proper environment which specified in this users manual.
Please implement the wiring operation under power-off status; otherwise, it will cause electric shock, or become the root cause of machinery breakdown.
For prevent equipment damage, disconnect the power supply from the product before performing any wiring and installation.
This product must be operated under ruled power supplying value, and be operated under the ruled normal operation conditions which described in the users manualotherwise, it may cause the disasters as fire accident or be the root cause of machinery breakdown.
This product must be operated under the operating conditions specified in manual to prevent equipment damage.
Installation and wring must be performed by qualified personnel in accordance with all applicable safety standards, according to applicable safety standards all wiring must comply with local codes of indoor wiring and electric installation rules.
All wiring must comply with the rule for indoor wiring and electrical installation rules. The screw must be tight for upper cover & lower base.
In order to prevent the interferences from frequency converter, etc., and avoid error signal to result in the product damage, please use the isolated conducting wire.
Please use crimp type terminal. To prevent personal injury, do not touch the moving part of product in operation. It may cause high humidity atmosphere during the product was breakdown. Please take safety
strategy. While discard this product, the user must to comply with the related rules for industrial domestic
wastes for different country / location.
www.eyc-tech.com
3
II. Connection Diagram
THG03, THR23, GS23 CO2, Temperature and Humidity Transmitter (Indoor)
III. Dimension
www.eyc-tech.com
4
THG03, THR23, GS23 CO2, Temperature and Humidity Transmitter (Indoor)
IV. Usage Precautions
To ensure accurate and stable measurements, please follow the installation guidelines below: · The device must be installed in a vertically upright position. Do not lay the device flat or at an angle, as this may disrupt internal air flow and reduce sensing accuracy. · It is recommended to install the device in a ventilated environment with airflow greater than 0.5 m/s to ensure optimal performance.
V. RS-485 & Modbus
THG03, THR23, GS23 integrate a RS-485 interface for digital communication as an option feature. Based on Modbus protocol makes the general convenience on PLC, HMI and PC connection. For Modbus protocol information please download the file from website. Besides the PLC, HMI application, the user software provide the device setting and data logging function, it also can free download from website. Technical Data (1) Max. network size32 transmitters (2) Communicationwith COM-Port (serial interface) of PC (3) Max. network expansion1200m (3937ft) total length at 9600 baud (4) Transmission rate9600, 19200, 38400, 57600, 115200 Baud (5) ParityNone, Even, Odd (6) Data length8 bit (7) Stop bit1 or 2 bit (8) Factory default Station address 1, Data format 9600, N81
www.eyc-tech.com
5
THG03, THR23, GS23 CO2, Temperature and Humidity Transmitter (Indoor)
VI. Configuration
Download the software from eyc-tech official website, decompress it and execute it. Planning software operating system requirements: Windows XP SP2 or above. 1. Hardware connection: Connect the THG03 / THR23 / GS23 to PC through USB to RS-485 or RS-232 to RS-485 converter 2. Check the COM port number from Device Manager in Computer Management. e.g. COM1 in illustration
3. Open the UI, go to function Interface , click item Config and then setting COM port, BAUD rate, data format and Station ID, pressed Apply for connection
4. Scan RS-485 connection
www.eyc-tech.com
6
THG03, THR23, GS23 CO2, Temperature and Humidity Transmitter (Indoor)
Open the UI, go to function Interface , click item Config and then setting COM port, pressed Scan bottom for scan devices and pressedClose and Export when the interested devices found.
Pick up the device that you want to connect to and then press “Apply” to go.
www.eyc-tech.com
7
THG03, THR23, GS23
CO2, Temperature and Humidity Transmitter (Indoor)
5. Setting on Analog Output In the group of OUT1(OUT2), Output tab. Both output1 and output2 related setting could be found. (1) QuantityTemperature, Relative Humidity, Carbon Dioxide (CO2) (2) Analog typeVoltage or Current (3) Analog Range0 … 20 mA / 4 … 20 mA (if output current) / 0 … 10 V (if output voltage) (4) Range for Upper and Lower (5) Alarm Mode: Check the box if analog output pretends an alarm switch output (6) Alarm Trigger Point: Upper and Lower (7) Alarm Output Level: Upper and Lower
(1)
(1)
(2)
(2)
(3)
(3)
(4)
(4)
(5)
(5)
(6)
(6)
(7)
(7)
www.eyc-tech.com
8
THG03, THR23, GS23 CO2, Temperature and Humidity Transmitter (Indoor)
6. Display Panel In the Monitor tab. There is a large display of available measurements.
www.eyc-tech.com
9
THG03, THR23, GS23
CO2, Temperature and Humidity Transmitter (Indoor)
7. Setting on RS-485, Data Transmission Test and environment parameters There are 3 groups in setting tab. The description of each item as below. Environment Parameters (1) Air Pressure Modbus Protocol (2) station ID (3) Baud Rate (4) Date Frame (5) Modbus Echo Test Enable/Disable (6) Modbus Echo Test Result Reset CO2 Auto Calibration (7) CO2 Auto CalibrationFunction is enabled if the bar color green, otherwise function is disabled. In the general environment, the CO2 concentration usually measured as 400ppm. The environments as From Room/ Office with the condition as midnight period & nobody status, the CO2 concentration usually measured as 400ppm. Thus, eyc-tech use the average statistics values for 7 days to implement Self-Correcting feature. This feature is not adaptive to use in special environment as Factory/ Plant Greenroom where the CO2 concentration may keep on high value & keep for long period. Others (8) Write Setting (9) Read Setting
(1)
(2) (3) (4)
(5)
(6)
(7)
(8)
(9)
www.eyc-tech.com
10
THG03, THR23, GS23
CO2, Temperature and Humidity Transmitter (Indoor)
8. Data display and logging (1) The measurement of OUT1 and OUT2 will be display here (2) Clear plot chart (3) Toggle the selection channel of color function, refer to item (8) (4) Snap the current plot chart (5) Display title of vertical axis (ON or OFF toggle in turn once click) (6) Enable secondary axis (right axis) (7) Change chart line style in turn (8) Select the color of plot channel (9) Export the records in plot buffer (10) Enable horizontal axis (11) Enable the legend of plot channel (12) Enable the log function, the data in cvs format with comma delimiter (13) The scale of horizontal scale (14) Select the scale method of vertical axis (15) Select the range of vertical axis (16) The vertical axis, label of OUT1 (17) The vertical axis, label of OUT2
(1)
(2) (3) (4)
(5)
(7) (8) (9)
(10)
(1)
(6)
(15)
(11)
(12) (13)
(14)
(16)
(17)
www.eyc-tech.com
11
THG03, THR23, GS23
CO2, Temperature and Humidity Transmitter (Indoor)
9. Device Information (1) Serial Number (2) Model Name (3) Firmware Version (4) Firmware Checksum (5) The activation of RS-485 function (6) Programming range of measurements and offset values (7) Analog Output Calibration Data (8) Calibration Date
(1)
(2)
(3)
(4)
(5)
(6)
(7) (8)
www.eyc-tech.com
12
THG03, THR23, GS23 CO2, Temperature and Humidity Transmitter (Indoor)
VII. Inspection and maintenance
1. Maintenance Since this product is inspected and calibrated for high accuracy at the factory before
shipment, no calibration on the installation site is necessary when this product is installed. For inspection and maintenance follow the instructions below (a) Periodic inspection Periodically inspect this product for its sensing accuracy and clean the cover. Set the period between inspections based on atmospheric dust and other contaminants in the installation environment. (b) Sensor maintenance Do not damage sensor surface during maintenance process (c) Troubleshooting If any problem occurs during operation, refer to the table below for appropriate solutions. 2. Troubleshooting
Problem
No output Unstable output
Slow response to
output
Error in output
Cleck items
Disconnected wiring Loose wiring Power supply voltage Sensor damages
Soluations
Re-perform wiring Crew on terminal tightly or
replace wires
Replace the sensor
Moisture / Condensation
on the product
Check installed location Check installed angle Check dust and
contamination on the sensor
Remove the sensor and filter dry
power-off state sensor in clean
air seasoning
Refer to the section Cleaning the filter of THG03 Calibrate Replace the sensor
www.eyc-tech.com
13
THG03, THR23, GS23 CO2, Temperature and Humidity Transmitter (Indoor)