EV3143
Controller with two independent regulators for refrigerated milk storage units and ice cream batch freezers

EVCO EV3143 Advanced Controller - Cover

  • 230 VAC or 115 VAC power supply (according to the model)
  • 2 analogue inputs (PTC/NTC)
  • door switch/multi-purpose input
  • main relay 16 A res. @ 250 VAC
  • alarm buzzer
  • TTL MODBUS slave port for BMS
  • hot or cold mode regulation.

MEASUREMENTS AND INSTALLATION

Measurements in mm (inches). To be fitted to a panel, snap-in brackets provided.

EVCO EV3143 Advanced Controller - MEASUREMENTS AND INSTALLATION

INSTALLATION PRECAUTIONS

  • the thickness of the panel must be between 0.8 and 2.0 mm (1/32 and 1/16 in)
  • ensure that the working conditions are within the limits stated in the TECHNICAL SPECIFICATIONS section
  • do not install the device close to heat sources, equipment with a strong magnetic field, in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations, or shocks
  • in compliance with safety regulations, the device must be installed properly to ensure adequate protection from contact with electrical parts. All protective parts must be fixed in such a way as to need the aid of a tool to remove them.

ELECTRICAL CONNECTION

N.B.
• use cables of an adequate section for the current running through them
• to reduce any electromagnetic interference, locate the power cables as far away as possible from the signal cables.

EVCO EV3143 Advanced Controller - ELECTRICAL CONNECTION

P10 OPERATION PROBE 1 PROBE 2 LOAD 1 LOAD 2 LOAD 3
0 controller with two independent regulators regulator 1 regulator 2 regulator 1 regulator 2 alarm
1 controller for refrigerated milk storage units tank auxiliary compres- sor auxiliary beater
2 controller for ice cream batch freezers tank plate compres- sor plate heaters beater

PRECAUTIONS FOR ELECTRICAL CONNECTION

  • if using an electrical or pneumatic screwdriver, adjust the tightening torque
  • if the device is moved from a cold to a warm place, humidity may cause condensation to form inside. Wait for about an hour before switching on  the power
  • make sure that the supply voltage, electrical frequency, and power are within the set limits. See the section TECHNICAL SPECIFICATIONS
  • disconnect the power supply before carrying out any type of maintenance
  • do not use the device as a safety device
  • for repairs and for further information, contact the EVCO sales network.

FIRST-TIME USE

  1. Carry out the installation following the instructions given in the section MEASUREMENTS AND INSTALLATION.
  2. Power up the device as set out in the section ELECTRICAL CONNECTION: an internal test will startup.
    The test normally takes a few seconds; when it is finished the display will switch off.
  3. Configure the device as shown in the section Setting configuration parameters.
    PAR. DEF. PARAMETER MIN… MAX.
    SP1 0.0 load 1 setpoint r1… r2
    SP2 0.0 load 2 setpoint r12… r13
    SP3 0.0 beater setpoint r16… r17
    PO 1 type of probe 0 = PTC 1 = NTC
    P2 0 temperature measurement unit 0 = °C 1 = °F
    P10 0 operating logic 0 = controller with two independent regulators
    1 = controller for refrigerated milk storage units
    2 = controller for ice cream batch freezers 1…

    Then check that the remaining settings are appropriate; see the section CONFIGURATION PARAMETERS.

  4. Disconnect the device from the mains.
  5. Make the electrical connection as shown in the section ELECTRICAL CONNECTION, without powering up the device.
  6. When connecting to an RS-485 network, connect the EVIF22TSX interface; see the relevant instruction sheets.
  7. Power up the device again.

USER INTERFACE AND MAIN FUNCTIONS

EVCO EV3143 Advanced Controller - USER INTERFACE AND MAIN FUNCTIONS

Switching the device on/off
  1. If POF = 1 (default), touch the ON/STAND-BY key for 4 s.
    If the device is switched on, the display will show the P5 value (“probe 1 temperature” default); if the display shows an alarm code, see the section ALARMS.
LED ON OFF FLASHING
compressor on compressor off – compressor protection in progress
– setpoint being set
plate heaters on plate heaters off setpoint being set
regulator 1 on regulator 1 off – load 1 protection in progress
– setpoint being set
defrost active
beater on beater off setpoint being set
alarm active and silenced – alarm active and not silenced
temperature displayed
regulator 2 on regulator 2 off – load 2 protection in progress
– setpoint being set
device off device on device being switched on/off

When 30 s have elapsed without the keys being pressed, the display will show the “Loc” label and the keypad will automatically lock.

Unlocking the keypad

Touch a key for 1 s: the display will show the label “UnL”.

Quick setting:
  • of setpoints (if P9 = 1 or 3)
  • beater switch on/off times (if P9 = 2 or 3)

Check that the keypad is not locked.

1. Touch the SET key: the display will show the label “SP1”.
2. Touch the UP or DOWN key within 15 s to set the load 1 setpoint value within the limits r1 and r2 (default “-50… 50”).
3. Touch the SET key: the display will show the label “SP2”.
4. Touch the UP or DOWN key within 15 s to set the load 2 setpoint value within the limits r12 and r13 (default “-50… 50”).
5. Touch the SET key: the display will show the label “SP3”.
6. Touch the UP or DOWN key within 15 s to set the beater setpoint value within the limits r16 and r17 (default “-50… 50”).
7. Touch the SET key: the display will show the label “t0”.
8. Touch the UP or DOWN key within 15 s to set the time the beater is switched off within the limits 0… 240 min.
9. Touch the SET key: the display will show the label “t1”.
10. Touch the UP or DOWN key within 15 s to set the time the beater is switched on within the limits 0… 240 min.
11. Touch the SET key (or take no action for 15 s).

Settings are temporary: when the device is switched back on (and after a power failure), it resets the values SP1, SP2, SP3, t0 and t1.

Starting up/interrupting batch freezing (if P10 = 2)

Check that the keypad is not locked.

  1. Touch the ON/STAND-BY key.
Manually switching on the beater (if P10 = 1)

Check that the keypad is not locked.

  1. Touch the DOWN key for 4 s.

The beater is switched on for time t1.

Activating manual defrost (if r5 and/or r19 = 0, default)

Check that the keypad is not locked.

  1. Touch the UP key for 4 s.
Silencing the buzzer (if Pbu = 2 or 3)

Touch a key.
If u4 = 1, the alarm output is also deactivated.

OPERATION

Controller with two independent regulators (P10 = 0, default)

Cold mode regulation regulator 1 (r5 = 0).

EVCO EV3143 Advanced Controller - OPERATION

Hot mode regulation regulator 1 (r5 = 1).

EVCO EV3143 Advanced Controller - OPERATION 2

Cold mode regulation regulator 2 (r10 = 0).

EVCO EV3143 Advanced Controller - OPERATION 3

Hot mode regulation regulator 2 (r10 = 1).

EVCO EV3143 Advanced Controller - OPERATION 4

Controller for refrigerated milk storage units (P10 = 1)

Compressor operation.

EVCO EV3143 Advanced Controller - Compressor operation

Beater operation set to t0 and t1 (r14 = 0).

EVCO EV3143 Advanced Controller - Controller for ice cream batch freezers (P10 = 2) 2

Beater operation set to r19, t0 and t1 if beater setpoint is not reached (r14 = 1).
Cold mode regulation beater (r19 = 0)

EVCO EV3143 Advanced Controller - Controller for ice cream batch freezers (P10 = 2) 3

Beater operation set to r19, t0 and t1 if beater setpoint is not reached (r14 = 1).
Hot mode regulation (r19 = 1).

EVCO EV3143 Advanced Controller - Controller for ice cream batch freezers (P10 = 2) 5

Controller for ice cream batch freezers (P10 = 2)

The batch freezing cycle consists of 4 phases:

  • heating
  • cooking
  • cooling
  • conservation.
Heating

The compressor remains off.
Plate heaters operation.
EVCO EV3143 Advanced Controller - HeatingBeater operation.
EVCO EV3143 Advanced Controller - Heating 2End of phase.
EVCO EV3143 Advanced Controller - End of phase

At the end of the phase the buzzer emits 10 beeps 1 s long.
If there is a power failure during the phase, it starts back up again from the beginning.

Cooking

The compressor remains off.
Plate heaters operation.
EVCO EV3143 Advanced Controller - CookingBeater operation.
EVCO EV3143 Advanced Controller - Cooking 2
End of phase.
EVCO EV3143 Advanced Controller - Cooking 3At the end of the phase the buzzer emits 10 beeps 1 s long.
If there is a power failure during the phase, it starts back up again from the beginning.

Cooling

Compressor operation.
EVCO EV3143 Advanced Controller - Cooling The plate heaters remain off.
Beater operation.
EVCO EV3143 Advanced Controller - Cooling 2

End of phase.
EVCO EV3143 Advanced Controller - Cooling 3At the end of the phase the buzzer emits 10 beeps 1 s long.
If there is a power failure during the phase:

  • the phase starts back up again from the beginning if (tank temperature after the powerfailure – tank temperature before the power failure) < PFd
  • the cycle starts back up again from the beginning of the heating phase if (tank temperature after the power failure tank temperature before the power failure) > PFd.
Conservation

Compressor operation.

EVCO EV3143 Advanced Controller - Compressor operation 2

The plate heaters remain off.
Beater operation.
EVCO EV3143 Advanced Controller - Conservation 2End of phase.

EVCO EV3143 Advanced Controller - Conservation 3

If there is a power failure during the phase:

  • the phase starts back up again from the beginning if (tank temperature after the power failure – tank temperature before the power failure) < PFd
  • the cycle starts back up again from the beginning of the heating phase if (tank temperature after the power failure
  • tank temperature before the power failure) > PFd.

ADDITIONAL FUNCTIONS

Viewing the temperatures detected by the probes

Check that the keypad is not locked.

1 Touch the DOWN key for 4 s.
2 Touch the UP or DOWN key within 15 s to select a label.
LAB. DESCRIPTION
Pb1 probe 1 temperature
Pb2 probe 2 temperature
3 Touch the SET key.
4 Touch the ON/STAND-BY key (or take no action for 60 s) to exit the procedure.

SETTINGS

Setting configuration parameters
1 Touch the SET key for 4 s: the display will show the label “PA”.
2 Touch the SET key.
3 Touch the UP or DOWN key within 15 s to set the PAS value (default “-19”).
4 Touch the SET key (or take no action for 15 s): the display will show the label “SP1”.
5 Touch the UP or DOWN key to select a parameter.
6 Touch the SET key.
7 Touch the UP or DOWN key within 15 s to set the value.
8 Touch the SET key (or take no action for 15 s).
9 Touch the SET key for 4 s (or take no action for 60 s) to exit the procedure.
Restoring factory (default) settings and saving customised settings

N.B.

  • check that the factory settings are appropriate; see the section CONFIGURATION PARAMETERS.
  • saving customised settings overwrites the factory settings.
1 Touch the SET key for 4 s: the display will show the label “PA”.
2 Touch the SET key.
3 Touch the UP or DOWN key within 15 s to set the value.
VAL.  MEANING
149 value for restoring the factory information (default)
161 value for saving customised settings
4 Touch the SET key (or take no action for 15 s): the display will show the label “dEF” (for setting the “149” value) or the label “MAP” (for setting the “161” value).
5 Touch the SET key.
6 Touch the UP or DOWN key within 15 s to set the value.
VAL. 1  MEANING
1 controller with two independent regulators
2 controller for refrigerated milk storage units
3 controller for ice cream batch freezers
7 Touch the SET key (or take no action for 15 s): the display will show “- – -” flashing for 4 s, after which the device will exit the procedure.
8 Disconnect the device from the power supply.
9 Touch the SET key for 2 s before action 6 to exit the procedure beforehand.

CONFIGURATION PARAMETERS

NO. PAR. DEF. SETPOINT MIN… MAX.
1 SP1 0.0 load 1 setpoint rl… r2
2 SP2 0.0 load 2 setpoint r7… r8
3 SP3 0.0 beater setpoint r16… r17
NO. PAR. DEF. ANALOGUE INPUTS MIN… MAX.
4 CAl 0.0 probe 1 offset -25… 25 °C/°F
5 CA2 0.0 probe 2 offset -25… 25 °C/°F
6 PO 1 type of probe 0 = PTC 1 = NTC
7 P1 0 enable decimal point °C 0 = no 1 = yes
8 P2 0 temperature measurement unit 0 = °C 1 = °F
9 P3 2 probe 1 function
not visible if P10 = 2
0 = disabled
1 = tank probe
2 = regulator 1
3 = condenser probe
10 P4 2 probe 2 function
not visible if PIO = 2
0 = disabled
1 = plate probe
2 = regulator 2
3 = condenser probe
11 P5 0 value displayed 0 = probe 1 temperature
1 = probe 2 temperature
2 = load 1 setpoint
3 = load 2 setpoint
12 P8 5 display refresh time 0… 250 s: 10
13 R 0 enable quick settings block 0 = disabled
1 = setpoint
2 = beater on/off times
3 = beater on/off setpoint + times
14 P10 0 operating logic 0 = controller with two inde-
pendent regulators
1 = controller for refrigerated milk storage units
2 = controller for ice cream batch freezers
NO. PAR. DEF. REGULATION MIN… MAX.
15 r0 2.0 load 1 setpoint differential 1… 15 °C/°F
16 rl -50 load 1 minimum setpoint -99 °C/°F… r2
17 r2 500 load 1 maximum setpoint rl… 150 °C/°F
18 r5 0 hot or cold mode regulation regu- lator 1 0 = cold mode 1 = hot mode
19 r6 2.0 load 2 setpoint differential 1… 15 °C/°F
20 r7 -50 load 2 minimum setpoint -99 °C/°F… r8
21 r8 500 load 2 maximum setpoint r7… 150 °C/°F
22 r9 1 enable regulator 2 0 = no 1 = yes
if P10 = 1
23 r10 0 hot or cold mode regulation regu- lator 2 0 = cold mode 1 = hot mode
24 r14 0 beater mode in normal operation 0 = parameter set to tO and tl
1 = parameter set to r19, tO, ti if the beater setpoint is not reached
25 r15 0.5 beater setpoint differential 1… 15 °C/°F
26 r16 -50 beater minimum setpoint -99 °C/°F… r17
27 r17 50 beater maximum setpoint r16… 150 °C/°F
28 r19 0 hot or cold mode regulation
beater
0 = cold mode 1 = hot mode
29 r20 0 beater mode in beater probe
alarm
0 = off
1 = set to tO and tl
30 r21 0 constraint between beater and
compressor
0 = disabled
1 = on if compressor on and parameter set to r14
2 = on if compressor off and parameter set to r14
3 = on if compressor on
NO. PAR. DEF. BEATER MIN… MAX.
31 tO 3 beater off time 0… 240 min
32 tl 2 beater on time 0… 240 min
33 t2 0 beater off delay from compressor off 0… 240 min
34 t3 10 minimum beater on and off time 0… 240 s
NO. PAR. DEF. LOADS MIN… MAX.
35 CO 3 load 1 on delay from power-on 0… 240 min
36 Cl 5 delay between two load 1 switch- ons 0… 240 min
37 C2 3 load 1 minimum off time 0… 240 min
38 C3 0 load 1 minimum on time 0… 240 s
39 C4 10 load 1 off time in probe 1 alarm 0… 240 min if C6 = 2
40 C5 15 load 1 on time in probe 1 alarm 0… 240 min if C6 = 2
41 C6 3 load 2 on delay from power-on and load 2 minimum off time 0… 240 min
42 C7 2 load 2 minimum on time 0… 240 s
43 C8 5 delay between two load 2 switch- ons 0… 240 min
44 C10 10 load 2 off time in probe 2 alarm 0… 240 min if C6 = 2
45 C11 15 load 2 on time in probe 2 alarm 0… 240 min if C6 = 2
46 C13 80.0 high condensation signal thresh- old
not visible if P10 = 2
0… 199 °C/°F differential = 2 °C/4 °F
47 C14 90.0 high condensation alarm thresh- old 0… 150 °C/°F
48 C15 60 high condensation alarm delay 0… 240 s
NO. PAR. DEF. DEFROSTING (if r5 = 0) MIN… MAX.
49 dO 8 automatic defrost interval regula- for 1 and regulator 2 0… 99 h
0 = manual only
50 d3 30 defrost duration regulator 1 0… 99 min
51 d4 0 enable defrost at power-on 0 = no 1 = yes
52 d5 0 defrost delay from power-on 0… 99 min
53 d6 2 value displayed when defrosting 0 = value P5 (if P5 = 0 or 1)
1 = value P5 (if P5 = 0 or 1)
at defrost activation
2 = label dEF
54 d10 30 defrost duration regulator 2 0… 99 min
55 d12 0 constraint between defrost regu- lator 1 and defrost regulator 2 0 = disabled
1 = regulator defrost is acti-
vated only if defrost of the other regulator is not in progress. If it is, it waits for this to end.
NO. PAR. DEF. ALARMS MIN… MAX.
56 Al –10.0 low temperature alarm threshold probe 1 -99… 150 °C/°F
57 A2 1 type of low temperature alarm probe 1 0 = disabled
1 = relative to load 1 setpoint
2 = absolute
58 A4 10.0 high temperature alarm threshold probe 1 -99… 150 °C/°F
59 AS 1 type of high temperature alarm probe 1 0 = disabled
1 = relative to load 1 setpoint
2 = absolute
60 A6 12 high temperature alarm delay
probe 1 from power-on
0… 99 minx10
61 A7 15 high/low temperature alarm delay probe 1 0… 240 min
62 AS 15 high temperature alarm delay
probe 1 after defrosting regulator
1
0… 240 min
63 A10 – – – unused
64 All –10.0 low temperature alarm threshold probe 2 -99… 150 °C/°F
65 Al2 1 type of low temperature alarm probe 2 0 = disabled
1 = relative to load 2 setpoint
2 = absolute
66 A14 10.0 high temperature alarm threshold probe 2 -99… 150 °C/°F
67 A15 1 type of high temperature alarm probe 2 0 = disabled
1 = relative to load 2 setpoint
2 = absolute
68 A16 12 high temperature alarm delay
probe 2 from power-on
0… 99 minx10
69 A17 15 high/low temperature alarm delay probe 2 0… 240 min
70 A18 15 high temperature alarm delay
probe 2 after defrosting regulator
2
0… 240 min
71 A19 2.0 high/low temperature alarm reset differential 1… 15 °C/°F
NO. PAR. DEF. DIGITAL INPUTS MIN… MAX.
72 i2 0 door switch/multi-purpose input alarm signal delay 0… 120 min
73 i3 0 maximum compressor and beater off time with door switch/multipurpose input active 0… 120 min
74 i7 0 door switch/multi-purpose input alarm activation delay 0… 120 min
75 i5 0 door switch/multi-purpose input function 0 = disabled
1 = compressor off
2 = beater off
3 = multi-purpose input
alarm
4 = switches device on/off
5 = thermal switch alarm
6 = door open alarm
76 i6 0 activation door switch/multi-pur- pose input 0 = with contact closed
1 = with contact open
NO. PAR. DEF. DIGITAL OUTPUTS MIN… MAX.
77 u1 3 K1 relay configuration 0 = compressor
1 = plate heaters
2 = beater
3 = load 1
4 = load 2
5 = alarm
78 u2 4 K2 relay configuration as ul
79 u3 5 K3 relay configuration as ul
80 u4 1 enable silencing alarm output 0 = no 1 = yes
NO. PAR. DEF. BATCH FREEZER MIN… MAX.
81 Snd -50 threshold for neutral zone regula- tion during cooking 99… 150 °C/°F
82 d2n 1.0 neutral zone value 0… 99.0 °C/°F
83 r23 0.0 minimum plate setpoint during batch freezing heating and cooking 0 °C/°F… r24
84 r24 130 maximum plate setpoint during batch freezing heating and cooking r23… 150 °C/°F
85 r25 0.0 minimum tank setpoint at end of batch freezing heating and batch freezing cooking setpoint 0 0C/0F… r26
86 r26 pO
O
maximum tank setpoint at end of batch freezing heating and bat& freezing cooking setpoint r25… 150 °C/°F
87 r27 0.0 minimum tank setpoint at end of batch freezing cooling and tank setpoint during conservation -2 0C/0F… r28
88 r28 130 maximum tank setpoint at end of batch freezing cooling and tank setpoint during conservation r27… 60 0C/°F
89 SAl 50.0 tank setpoint for beater on or on/off during batch freezing -99… 150 0C/°F differential = 5 0C/10 of
90 PFd 5.0 difference in tank temperature af- ter power failure during batch freezing cooling or conservation due to reactivating heating 1… 25 °C/°F
NO. PAR. DEF. BATCH FREEZING HEATING MIN… MAX.
P 1 OH 2.0 plate differential setpoint during batch freezing heating and plate setpoint during batch freezing cooking 1… 25 °C/°F
92 1Z1freezing n1H 0 hours beater on during batch
heating
0… 23 h
93 nln 2 minutes beater on during batch freezing heating 0… 59 min
94 n1S 0 seconds beater on during batch freezing heating 0… 59 s
95 FIH 0 hours beater off during batch
freezing heating
0… 23 h
96 F1n 2 minutes beater off during batch freezing heating 0… 59 min

EVCO S.p.A. | EV3143 | Instruction sheet ver. 1.0 | Code 1043143E103 | Page 3 of 3 | PT 22/19

97 F1S 0 seconds beater off during batch freezing heating 0… 59 s
2 NO. PAR. DEF. BATCH FREEZING COOKING MIN… MAX.
98 SPC 30.0 plate setpoint during batch freez- ing cooking and plate setpoint during batch freezing cooking r23… r24
99 SU2 30.0 tank setpoint at end of batch freezing heating and tank setpoint during batch freezing cooking r25… r26
100 r2H 2.0 tank differential setpoint during batch freezing cooking 1… 25 °C/°F
101 C2H 1 duration in hours of batch freezing cooking 0… 23 h
102 C2n 0 duration in minutes of batch
freezing cooking
0… 59 min
103 C2S 0 duration in seconds of batch
freezing cooking
0… 59 s
104 n2H 0 hours beater on during batch
freezing cooking
0… 23 h
105 n2n 2 minutes beater on during batch freezing cooking 0… 59 min
106 n2S 0 seconds beater on during batch freezing cooking 0… 59 s
107 F2H 0 hours beater off during batch
freezing cooking
0… 23 h
108 F2n 2 minutes beater off during batch freezing cooking 0… 59 min
109 F2S 0 seconds beater off during batch freezing cooking 0… 59 s
3 NO. PAR. DEF. BATCH FREEZING COOLING MIN… MAX.
110 SU3 30.0 tank setpoint at end of batch
freezing cooling and tank setpoint during batch freezing conservation
r27… r28
111 SA3 10.0 tank setpoint for beater on at end of batch freezing cooking 0… 25 °C/°F
112 ZIfreezing
n3H
0 hours beater on during batch
cooling
0… 23 h
113 n3n 2 minutes beater on during batch freezing cooling 0… 59 min
114 n3S 0 seconds beater on during batch freezing cooling 0… 59 s
115 F3H 0 hours beater off during batch
freezing cooling
0… 23 h
116 F3n 2 minutes beater off during batch freezing cooling 0… 59 min
117 F3S 0 seconds beater off during batch freezing cooling 0… 59 s
4 NO. PAR. DEF. BATCH FREEZING CONSERVA-
TION
MIN… MAX.
118 r4H 2.0 tank differential setpoint during batch freezing conservation 1… 25 °C/°F
119 n4H 0 hours beater on during batch
freezing conservation
0… 23 h
120 n4n 2 minutes beater on during batch freezing conservation 0… 59 min
121 n4S 0 seconds beater on during batch freezing conservation 0… 59 s
122 F4H 0 hours beater off during batch
freezing conservation
0… 23 h
123 F4n 2 minutes beater off during batch freezing conservation 0… 59 min
124 F4S 0 seconds beater off during batch freezing conservation 0… 59 s
125 F4C 0 beater mode during batch freezing conservation 0 = independent on the compressor
1 = on if compressor on, according to n4… and F4… if compressor off
NO. PAR. DEF. SECURITY MIN… MAX.
126 H4E 0 timeout for locking the keypad 0… 240 s
127 POF 1 enable ON/STAND-BY key 0 = no 1 = yes
128 PAS -19 password -99… 999
129 PA1 – – – unused
130 PA2 – – – unused
NO. PAR. DEF. UNUSED MIN… MAX.
131 Hr0 – – – unused
NO. PAR. DEF. UNUSED MIN… MAX.
132 rE0 – – – unused
133 rEl – – – unused
NO. PAR. DEF. MODBUS MIN… MAX.
134 LA 247 MODBUS address 1… 247
135 Lb 2 MODBUS baud rate 0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud
136 bLE – – – unused
NO. PAR. DEF. SECURITY MIN… MAX.
137 bul 0 duration of buzzer activation
when setpoint reached
0… 240 s
138 Pbu 2 enable buzzer 0 = disabled
1 = keys only
2 = alarms only
3 = keys and alarms

ALARMS

CODE DESCRIPTION RESET TO CORRECT
Pr1 probe 1 alarm automatic – check PO
– check integrity of the probe
– check electrical connection
Pr2 probe 2 alarm automatic
rtc unused unused unused
All low-temperature alarm
probe 1
automatic check Al and A2
AH1 high-temperature alarm
probe 1
automatic check A4 and AS
AL2 low-temperature alarm
probe 2
automatic check All and Al2
AH2 high-temperature alarm
probe 2
automatic check A14 and A15
id door open alarm automatic check i5 and i6
PF power failure alarm manual – touch a key
– check electrical connection
COH high condensation signal automatic check C13
CSd high condensation alarm manual – switch the device off and on – check C14
iA multi-purpose input alarm automatic check i5 and i6
it thermal switch alarm automatic – switch the device off and on – check i5 and i6

TECHNICAL SPECIFICATIONS

Purpose of the control device: function controller.
Construction of the control device: built-in electronic device.
Housing: black, self-extinguishing.
Category of heat and fire resistance: D.
Measurements:
75.0 x 33.0 x 59.0 mm (2 15/16 x 1 5/16 x
2 5/16 in) with fixed screw terminal blocks
75.0 x 33.0 x 81.5 mm (2 15/16 x 1 5/16 x 3 3/16 in) with plug-in screw terminal blocks
Mounting methods for the control device: to be fitted to a panel, snap-in brackets provided
Degree of protection provided by the casing: IP65 (front).
Connection method:
fixed screw terminal blocks for
wires up to 2.5 mm²
plug-in screw terminal blocks
for wires up to 2.5 mm² (on
request)
Micro-MaTch connector
Maximum permitted length for connection cables:
power supply: 10 m (32.8 ft) analogue inputs: 10 m (32.8 ft)
digital inputs: 10 m (32.8 ft) digital outputs: 10 m (32.8 ft).
Operating temperature: from 0 to 55 °C (from 32 to 131 °F).
Storage temperature: from -25 to 70 °C (from -13 to 158 °F).
Operating humidity: relative humidity without condensate from 10
to 90%.
Pollution status of the control device: 2
Compliance:
RoHS 2011/65/EC WEEE 2012/19/EU REACH (EC) Regulation
no. 1907/2006
EMC 2014/30/EU LVD 2014/35/EU.
Power supply:
230 VAC (+10% -15%), 50/60 Hz (±3 Hz), max. 2 VA insulated in EV3143N7
115 VAC (+10% -15%), 50/60 Hz (±3 Hz), max. 2 VA insulated in EV3143N5.
Earthing methods for the control device: none.
Rated impulse-withstand voltage: 4 KV.
Over-voltage category: III.
Software class and structure: A.
Analogue inputs: 2 for PTC or NTC probes (probe 1 and probe 2).
PTC probes: Type of sensor: KTY 81-121 (990 W @ 25 °C, 77 °F)
Measurement field: from -50 to 150 °C (from -58 to 302 °F)
Resolution: 0.1 °C (1 °F).
NTC probes: Type of sensor: ß3435 (10 KW @ 25 °C, 77 °F)
Measurement field: from -40 to 105 °C (from -40 to 221 °F)
Resolution: 0.1 °C (1 °F).
Digital inputs: 1 dry contact (door switch/multi-purpose).
Dry contact: Type of contact: 5 VDC, 1.5 mA
Power supply: none
Protection: none.
Digital outputs: 3 electromechanical relays.
K1 relay: SPST, 16 A res. @ 250 VAC
K2 relay: SPDT, 8 A res. @ 250 VAC.
K3 relay: SPST, 5 A res. @ 250 VAC.
Type 1 or Type 2 actions: type 1.
Additional features of Type 1 or Type 2 actions: C.
Displays: custom display, 3 digits, with function icons.
Alarm buzzer: built-in.
Communications ports: 1 TTL MODBUS slave port for BMS.

N.B.
The device must be disposed of according to local regulations governing the collection of electrical and electronic equipment.

This document and the solutions contained therein are the intellectual property of EVCO and thus protected by the Italian Intellectual Property Rights Code (CPI). EVCO imposes an absolute ban on the full or partial reproduction and disclosure of the content other than with the express approval of EVCO. The customer (manufacturer, installer, or end-user) assumes all responsibility for the configuration of the device. EVCO accepts no liability for any possible errors in this document and reserves the right to make any changes at any time without prejudice to the essential functions and safety features of the equipment.

EVCO - Logo
EVCO S.p.A.
Via Feltre 81, 32036 Sedico (BL) ITALY
Tel. +39 0437/8422 | Fax +39 0437/83648
email info@evco.it | web www.evco.it

Documents / Resources

EVCO EV3143 Advanced Controller [pdf] Instruction Manual
EV3143 Advanced Controller, EV3143, Advanced Controller
EVCO EV3143 Advanced Controller [pdf] User Manual
EV3143 Advanced Controller, EV3143, Advanced Controller, Controller

References

Leave a comment

Your email address will not be published. Required fields are marked *