Rosemount 802 Wireless Multi Discrete I/O Transmitter

Quick Start Guide

Document Number: MS-00825-0100-4082, Rev. AA

Date: March 2024

For Additional Product Information: If QR code is not affixed here, product documents can be located by entering your product's S/N into the search tool [magnifying glass icon] at the top of the webpage found at www.emerson.com

Safety Messages

⚠️ WARNING

Failure to follow safe installation and servicing guidelines could result in death or serious injury. Ensure only qualified personnel perform installation or service. Ground the electronics enclosure in accordance with local and national installation codes.

Explosions could result in death or serious injury. Installation of device in an explosive environment must be in accordance with appropriate local, national, and international standards, codes, and practices. Verify that the operating environment of the device is consistent with the appropriate hazardous locations certifications. Before connecting a handheld communicator in an explosive atmosphere, ensure that the instruments are installed in accordance with intrinsically safe or non-incendive field wiring practices.

Electrostatic hazard that can result in death or serious injury

Warning - Explosion hazard. Do not open when energized.

Avertissement - Risque d'explosion. Ne pas ouvrir lorsque sous tension.

Warning - The surface resistivity of the antenna is greater than one gigaohm. To avoid electrostatic charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.

Conduit/cable entries

The conduit/cable entries in the transmitter housing use a ½-14 NPT thread form. When installing in a hazardous location, use only appropriately listed or Ex certified plugs, glands, or adapters in cable/conduit entries. Ensure external conduit/cable fittings are Type 4X rated or better (C22.2 No 94.2/UL 50E requirement).

Physical access

Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users' equipment. This could be intentional or unintentional and needs to be protected against. Physical security is an important part of any security program and fundamental in protecting your system. Restrict physical access by unauthorized personnel to protect end users' assets. This is true for all systems used within the facility.

NOTICE

Shipping considerations for wireless products (lithium batteries: Black Power Module, model number 701PBKKF): Emerson shipped the transmitter to you without the Black Power Module installed. Remove the Black Power Module prior to shipping the transmitter. Each Black Power Module contains two C size primary lithium batteries. Primary lithium batteries are regulated in transportation by the U.S. Department of Transportation and are also covered by the International Air Transport Association (IATA), International Civil Aviation Organization (ICAO), and European Ground Transportation of Dangerous Goods (ADR). It is the shipper's responsibility to ensure compliance with these or any other local requirements. Before shipping, consult current regulations and requirements.

1 Parts Needed

1.1 In the box

1.2 Ordered Separately

1.3 802 Transmitter Components

The Rosemount 802 Transmitter has the following components:

2 Device Preparation

2.1 Power Up

Note: There are two methods to power up the transmitter: either with the 701P SmartPower™ Module - Black or a 10-30 Vdc external power supply.

Prerequisites: Verify the Wireless Gateway is installed and functioning properly before powering any wireless devices.

Procedure:

  1. Using a Phillips head screwdriver, back out screws so the cover opens.

Figure 2-1: Cover screws

The diagram shows the Rosemount 802 Transmitter with screws labeled 'A' for opening the cover.

Note: The default power position is with the power module terminals exposed.

Figure 2-2: Power module configuration

The diagram shows the internal power module configuration with a plastic plug labeled 'A'.

  1. Remove the plastic plug from the receptacle.
  2. Power the device in one of two ways:
    • Install the 701P SmartPower Module into the 802 Transmitter to power the device.
    • Move the mechanical slider to expose the external power supply terminals and power the transmitter with a 10-30 Vdc power source.

Input voltage: 10-30 Vdc

Input current (maximum): 805 mA

Power supply must be isolated from AC mains and provide transient free DC input power to the transmitter.

Figure 2-3: External power supply configuration

The diagram shows the external power supply configuration, with 'A' indicating the power supply connection point.

2.2 Antenna Position

Position the antenna vertically, approximately 3 ft. (1 m) away from any large structure, building, or conductive surface to allow for clear communication to other devices.

Figure 2-4: Antenna position

The diagram illustrates the antenna being positioned vertically.

2.3 Plug Conduits

Procedure: Plug the unused conduit entries with supplied conduit plugs with approved sealant.

3 Provisioning & Commissioning

3.1 Provision Transmitter

Prerequisites: You must power up the transmitter before the communication device can interface with it. For HART® wireless transmitter communication via a communication device, an 802 wireless device descriptor (DD) is required.

Procedure: To obtain the latest DD, go to Software & Drivers.

Figure 3-1: Connection diagram

The diagram shows the connection terminals, with 'A' indicating the communication terminals.

Note: The Emerson 475 Field Communicator will not work as a communication device for the 802 Transmitter.

3.2 Commission Transmitter to Gateway

If you ordered the transmitter with a factory-configured network ID and join key, it should join the network with no user input. If you're unsure if you ordered the device with the factory-configured option, you can manually enter the network ID and join key to match the Gateway.

Procedure:

  1. To obtain the network ID and join key, go to Network → Network Settings in the Gateway user interface.

Figure 3-2: Network Settings page in Gateway user interface

The diagram shows the Gateway user interface's Network Settings page, with 'A' indicating the Network ID and 'B' indicating the Join Key.

  1. Use communication device or HART® modem to configure the transmitter by entering the network ID and join key, as shown in Figure 3-1.

Note: It may take several minutes for the device to join the network.

Figure 3-3: Gateway Explorer page

The diagram shows the Gateway Explorer page interface, displaying device status and network information.

4 Terminal Wiring for Input and Output Circuits

The transmitter has three screw terminals for each channel. These terminals are labeled as follows:

Note: All eight channels have a third PWR OUT terminal that outputs continuous voltage, which can be up to 2 Vdc less than the supplied external power to the transmitter. (For example, 28 Vdc into the transmitter, PWR OUT terminal outputs 26 Vdc)

4.1 Discrete Inputs

Note: Optionally, you can use the device to invert any input to change the discrete logic state. This is useful, for instance, if a normally open switch is used to replace a normally closed switch.

Figure 4-1: Discrete input circuit

The diagram shows a discrete input circuit with terminals PWR OUT, I/O, and CMN. 'A' indicates 'Dry contact only'.

4.2 Discrete Output Switch Functionality

The host control system drives the discrete output of the 802 Transmitter through the Wireless Gateway and out to the transmitter. The time required for wireless communication from the Gateway to the transmitter is dependent on many factors, including the size and topology of the network and the total amount of downstream traffic on the wireless network. For a network that is constructed to Emerson's best practices, typical delays in communication of a discrete output from the Gateway to the transmitter are 15 seconds or less. Remember that this delay is only part of the latency that will be observed in a control loop.

Figure 4-2: Discrete output circuit

The diagram shows a discrete output circuit with terminals PWR OUT, I/O, and CMN. 'A' indicates 'External power supply' and 'B' indicates 'Load'.

4.3 Alternative Discrete Output Functionality

All eight channels have a third PWR OUT terminal that outputs continuous voltage, which can be up to 2 Vdc less than the supplied external power to the transmitter. (For example, if the external power supplies 28 Vdc to the transmitter, the PWR OUT terminal will output 26 Vdc.) Figure 4-3 shows the alternative wiring configuration.

Figure 4-3: Alternative discrete output circuit wiring circuit

The diagram shows an alternative discrete output circuit wiring, with 'A' indicating 'Load'.

4.4 Special Considerations for Multi-Output Circuits

Important: If more than one channel is connected to output circuits, it is very important that the CMN terminal of each circuit be at the same voltage. Employing a common ground for all output circuits is one way to ensure that all circuits have CMN terminals at the same voltage. If two output circuits are connected to a single transmitter with a single power supply, both input/output (I/O) and common (CMN) terminals must be connected to each output circuit. The negative power supply wires must be at the same voltage and connected to both CMN terminals.

Figure 4-4: Multiple output circuits with one power supply

The diagram shows multiple output circuits with one power supply, with 'A' indicating 'Load'.

4.5 Switching Greater Currents or Voltages

Note: Maximum switching capacity is 28 Vdc and 100 mA per channel. If you need to switch a greater voltage or current, use an interposing relay circuit.

Figure 4-5 shows an example of a circuit to switch higher currents or voltages.

Figure 4-5: Wiring an interposing relay to switch greater currents or voltages

The diagram shows wiring an interposing relay. 'A' indicates 'Power supply' and 'B' indicates 'Load'.

5 Mount Transmitter Remotely

Emerson has designed the 802 Transmitter to be installed only in the remote mount configuration, where the sensor is mounted separately from the housing and then connected to the transmitter via conduit.

Procedure:

  1. Install the transmitter according to standard installation practices. Make sure to use thread sealant on all connections.
  2. To reduce sensor wiring length, mount the transmitter centrally to all of the measurements. When installing the transmitter, make sure the conduit entries are facing downward. If using the mounting bracket (option code B6), mount the transmitter to a 2-in. (51 mm) pipe.

Figure 5-1: 802 mounting bracket (bottom view)

The diagram shows the 802 mounting bracket in a bottom view.

Postrequisites: For additional remote mounting information, see Emerson.com.

6 Grounding the Transmitter

The transmitter operates best with the housing grounded. Floating systems, however, can cause extra noise that may affect the accuracy of the transmitter. If the signal appears noisy or erratic, grounding at a single point may solve the problem. Ground the transmitter through the process connection using the internal or external grounding terminal.

7 Product Certifications

Revision 2.5

7.1 European Directive Information

A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EC Declaration of Conformity can be found at Emerson.com/Rosemount.

7.2 Telecommunication Compliance

All wireless devices require certification to ensure they adhere to regulations regarding the use of the radio frequency (RF) spectrum. Nearly every country requires this type of product certification. Emerson is working with governmental agencies around the world to supply fully compliant products and remove the risk of violating country directives or laws governing wireless device usage.

7.3 Federal Communications Commission (FCC) and Innovation, Science, and Economic Development Canada (ISED)

This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions: This device may not cause harmful interference; this device must accept any interference received, including interference that may cause undesired operation. This device must be installed to ensure a minimum antenna separation distance of 7.9 in. (20 cm) from all persons.

This device contains license-exempt transmitter(s)/receiver(s) that comply with Innovation, Science, and Economic Development Canada's license exempt RSS(s). Operation is subject to the following two conditions:

  1. This device may not cause interference.
  2. This device must accept any interference, including interference that may cause undesired operation of the device.

Changes or modification to the equipment not expressly approved by Emerson could void the user's authority to operate the equipment.

L'émetteur/récepteur exempt de licence contenu dans le present appareil est conforme aux CNR d'Innovation, Sciences et Développement économique Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes :

  1. L'appareil ne doit pas produire de brouillage;
  2. L'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.

Les changements ou les modifications apportés à l'équipement qui n'est pas expressément approuvé par Emerson pourraient annuler l'autorité de l'utilisateur à utiliser cet équipement.

7.4 Ordinary Location Certification

As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a Nationally Recognized Test Laboratory (NRTL), as accredited by the Federal Occupational Safety and Health Administration (OSHA).

7.5 Installing in North America

The US National Electrical Code® (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes.

7.6 USA

7.6.1 N5 USA Division 2, Non-Incendive

Certificate: FM24US0017X

Markings: NI Class I, Division 2, Groups A, B, C, D, T4 (-50 °C ≤ Ta ≤ +70 °C)

Field wiring shall be rated for +172 °F (+78 °C). Enclosure Type 4X/IP66

Specific Conditions for Safe Use (X): Only the Emerson SmartPower™ 701PBKKF shall be used for replacement.

7.7 Canada

7.7.1 N6 Canada Division 2, Non-Incendive

Certificate: FM24CA0008X

Markings: NI Class I, Division 2, Groups A, B, C, D, T4 (-50 °C ≤ Ta ≤ +70 °C)

Field wiring shall be rated for +172 °F (+78°C). Enclosure Type 4X/IP66

Specific Conditions for Safe Use (X): Only the Emerson SmartPower™ 701PBKKF shall be used for replacement.

7.8 Declaration of Conformity

EMERSON

EU DECLARATION OF CONFORMITY

CE RMD 1168-AA

This declaration of conformity is issued under the sole responsibility of:

Rosemount Inc.
6021 Innovation Blvd
Shakopee, MN 55379
USA

that the following products,

Rosemount™ 802 Wireless Multi Discrete I/O Transmitter

comply with the provisions of the European Union Directives, including the latest amendments, valid at the time this declaration was signed.

Signature & Date of Issue: [Signature] February 26, 2024

Name: Mark Lee (Vice President, Quality)

Place of Issue: Boulder, CO, USA

Authorized Representative in Europe:

Emerson S.R.L., company No. J12/88/2006
Emerson 4 street, Parcul Industrial
Tetarom II, Cluj-Napoca 400638, Romania

Regulatory Compliance Shared Services Department

Email: europeproductcompliance@emerson.com Phone: +40 374 132 035

EMC Directive (2014/30/EU)
Harmonized Standards: EN 61326-1:2021

RED Directive (2014/53/EU)
Harmonized Standards: EN 300 328 V2.2.2, EN 301 489-1 V2.2.3, EN 301 489-17 V3.2.4, EN 62311: 2020

Models: 802, 802 Wireless Multi Discrete I O Transmitter, 802, Wireless Multi Discrete I O Transmitter, Multi Discrete I O Transmitter, Discrete I O Transmitter, I O Transmitter, O Transmitter, Transmitter

File Info : application/pdf, 16 Pages, 2.47MB

PDF preview unavailable. Download the PDF instead.

rosemount-802-wireless-multi-channel-discreet-io-transmitter-quick-start-guide ?srsltid=AfmBOoqqb8TMpnMX4pKO4W9T9 YZRxjJ2obqd

References

Antenna House PDF Output Library 7.3.1863

Related Documents

Preview Rosemount 3051HT Hygienic Pressure Transmitter Quick Start Guide | Emerson
This Quick Start Guide provides essential information for installing, configuring, and trimming the Rosemount 3051HT Hygienic Pressure Transmitter. It covers system readiness, mounting, wiring, switch settings, HART Revision capabilities (5 and 7), and product certifications (3-A, EHEDG, ASME-BPE, ATEX, IECEx). Includes detailed diagrams and procedures for optimal operation.
Preview DeltaV M-series Traditional I/O Product Data Sheet
This document provides detailed information on the DeltaV M-series Traditional I/O subsystem, including its benefits, product description, various I/O card specifications, terminal block compatibility, system compatibility, certifications, and ordering information. It covers analog input, analog output, discrete input, and discrete output cards, along with their technical specifications and application guidelines.
Preview Emerson Synchros WirelessHART Platform Quick Start Guide
This guide provides basic guidelines for the Emerson Synchros WirelessHART Platform for commissioning and provisioning sensor modules. It covers device preparation, provisioning, commissioning, battery information, and product certifications.
Preview Rosemount TankMaster WinSetup Configuration Software for Tank Gauging Systems
This reference manual provides detailed information on Emerson's Rosemount TankMaster WinSetup configuration software, essential for setting up and managing industrial tank gauging systems. It covers installation, configuration, user management, and service functions for monitoring tank levels and inventory.
Preview DeltaV Distributed Control System Version 13 Update - Enhanced Performance, Integration, and Security
Explore the enhancements in DeltaV™ Distributed Control System Version 13 (v13), focusing on improved operation performance with Alarm Mosaic, faster integration via Ethernet I/O Cards, and enhanced system security. Discover new features for alarm management, connectivity, and system administration.
Preview Emerson Wireless Field Link: Quick Start Guide for Industrial Wireless Communication
Get started with the Emerson Wireless Field Link. This quick start guide provides essential installation, setup, and operational information for the Rosemount 781 Wireless Field Link, focusing on industrial wireless communication and safety.
Preview Emerson Wireless 1410S Gateway: Quick Start Guide for Industrial Wireless Connectivity
This Quick Start Guide provides essential information for the Emerson Wireless 1410S Gateway, covering installation, configuration, and safety procedures for reliable industrial wireless communication. Learn how to set up your gateway efficiently.
Preview Emerson Rosemount 1410 Wireless Gateway Technical Drawings
Technical drawings and specifications for the Emerson Rosemount 1410 Wireless Gateway and related components, including the 781 Wireless Field Link.