Instruction Manual for Panasonic models including: S-180ME, S-224ME, S-280ME, S-180ME Ducted E3 High Static Splittable Ducted Air Conditioner, S-180ME, Ducted E3 High Static Splittable Ducted Air Conditioner, Static Splittable Ducted Air Conditioner, Ducted Air Conditioner, Air Conditioner, Conditioner

ACXF60-54861 EN

user

S-180 260ME3H Installation Instructions EN (PDF - 2.3 MB)

Ducted E3 High Static Splittable Ducted - Panasonic Vietnam


File Info : application/pdf, 2 Pages, 2.26MB

PDF preview unavailable. Download the PDF instead.

S-180 260ME3H Installation Instructions EN
INSTALLATION INSTRUCTIONS INDOOR UNIT

Model No.: S-180ME** S-224ME** S-280ME**

CAUTION
R410A
REFRIGERANT
This Air Conditioner contains and operates with refrigerant R410A.
THIS PRODUCT MUST ONLY BE INSTALLED OR SERVICED BY QUALIFIED PERSONNEL.
Refer to Commonwealth, State, Territory and local legislation, regulations, codes, installation & operating instructions, before the installation, maintenance and/or service of this product.
Refer to the outdoor unit installation instruction manual for the outdoor unit installation.
Note: Ensure to hand over this installation instruction manual to the person performing the installation and inform the customer to keep it properly stored.

Required tools for Installation Works

1 Phillips screw driver 7 Pipe cutter

2 Flathead screw driver 8 Reamer

3 Level gauge

9 Knife

4 Electric drill, hole core 10 Gas leak detector

drill (ø70 mm)

11 Measuring tape

5 Hexagonal wrench (4 mm)
6 Spanner

12 Thermometer 13 Megohmmeter 14 Multimeter

15 Torque wrench 18 N·m (1.8 kgf·m) 42 N·m (4.3 kgf·m) 55 N·m (5.6 kgf·m) 65 N·m (6.6 kgf·m) 100 N·m (10.2 kgf·m)
16 Vacuum pump
17 Gauge manifold

Explanation of symbols displayed on the indoor unit or outdoor unit.

CAUTION This symbol shows that the Operating Instructions should be read carefully.
This symbol shows that a service
CAUTION personnel should be handling this equipment with reference to the Technical Manual.

SAFETY PRECAUTIONS
· Read the following "SAFETY PRECAUTIONS" carefully before installation. · Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model to be installed. · The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below.
Incorrect installation due to ignoring of the instruction will cause harm or damage, and the seriousness is classified by the following indications.

WARNING This indication shows the possibility of causing death or serious injury.

CAUTION

This indication shows the possibility of causing injury or damage to properties only.

The items to be followed are classified by the symbols:

Symbol with white background denotes item that is PROHIBITED.

Symbol with dark background denotes item that must be carried out.
· Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care and maintenance as stated
in instructions. Please remind the customer to keep the operating instructions for future reference.

WARNING
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer. Any unfit method or using incompatible material may cause product damage, burst and serious injury.
Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit on veranda of a high rise building, child may climb up to outdoor unit and cross over the handrail causing an accident.
Do not use unspecified cord, modified cord, joint cord or extension cord for power supply cord. Do not share the single outlet with other electrical appliances. Poor contact, poor insulation or over current will cause electrical shock or fire.
Do not tie up the power supply cord into a bundle by band. Abnormal temperature rise on power supply cord may happen.

Do not insert your fingers or other objects into the unit, high speed rotating fan may cause injury.

Do not sit or step on the unit, you may fall down accidentally.

Keep plastic bag (packaging material) away from small children, it may cling to nose and mouth and prevent breathing.
When installing or relocating air conditioner, do not let any substance other than the specified refrigerant, eg. air etc mix into refrigeration cycle (piping). Mixing of air etc. will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
Do not pierce or burn as the appliance is pressurized. Do not expose the appliance to heat, flame, sparks, or other sources of ignition. Else, it may explode and cause injury or death.
Do not add or replace refrigerant other than specified type. It may cause product damage, burst and injury etc.
 For R410A model, use new piping, flare nut and tools which is specified for R410A refrigerant. Using of existing (R22) piping, flare nut and tools may cause abnormally high pressure in the refrigerant cycle (piping), and possibly result in explosion and injury. For R32 and R410A, the same flare nut on the outdoor unit side and pipe can be use.
 Since the working pressure for R32/R410A is higher than that of refrigerant R22 models, replacing conventional piping and flare nuts on the outdoor unit side are recommended.
 Thickness for copper pipes used with R410A must meet the requirement. Refer to 1 GENERAL piping thickness table in outdoor unit installation manual.  It is desirable that the amount of residual oil less than 40 mg/10 m.
Engage authorized dealer or specialist for installation. If installation done by the user is incorrect, it will cause water leakage, electrical shock or fire.

For refrigeration system work, install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock or fire.

Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage, fire or electrical shock.
Install at a strong and firm location which is able to withstand weight of the set. If the strength is not enough or installation is not properly done, the set will drop and cause injury.
For electrical work, follow the national regulation, legislation and this installation instruction. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.
Do not use joint cable for indoor / outdoor connection cable. Use the specified indoor/outdoor connection cable, refer to instruction 3 ELECTRICAL WIRING and connect tightly for indoor/outdoor connection. Clamp the cable so that no external force will have impact on the terminal. If connection or fixing is not perfect, it will cause heat up or fire at the connection.
Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will cause fire or electrical shock.
This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD). Otherwise, it may cause electrical shock and fire in case of equipment breakdown or insulation breakdown.
During installation, install the refrigerant piping properly before running the compressor. Operation of compressor without fixing refrigeration piping and valves at opened position will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
During pump down operation, stop the compressor before removing the refrigeration piping. Removal of refrigeration piping while compressor is operating and valves are opened will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare may break and cause refrigerant gas leakage.
After completion of installation, confirm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant contacts with fire.
Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant contacts with fire.

Be aware that refrigerants may not contain an odour.
This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and telephone. Otherwise, it may cause electrical shock in case of equipment breakdown or insulation breakdown.
CAUTION

Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fire.

Prevent liquid or vapor from entering sumps or sewers since vapor is heavier than air and may form suffocating atmospheres.

Do not overcharge the unit, refer to gas charge specification in Outdoor Installation manual. Overcharge will cause over current and damage to compressor.
Do not release refrigerant during piping work for installation, re-installation and during repairing a refrigeration parts. Take care of the liquid refrigerant, it may cause frostbite.
Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.

Do not touch the sharp aluminium fin, sharp parts may cause injury.

Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.

Select an installation location which is easy for maintenance. Incorrect installation, service or repair of this air conditioner may increase the risk of rupture and this may result in loss damage or injury and/or property.
Power supply connection to the room air conditioner. Use power supply cord type designation 60245 IEC 57 or heavier cord. Connect the power supply cord of the air conditioner to a circuit breaker for the permanent connection. It must be a double pole switch with a minimum 3.0mm contact gap. Power supply point should be in easily accessible place for power disconnection in case of emergency.
Installation work. It may need two people to carry out the installation work.
Keep any required ventilation openings clear of obstruction.

PRECAUTION FOR USING R410A REFRIGERANT
· The basic installation work procedures are the same as conventional refrigerant (R32, R22) models.
However, pay careful attention to the following points:
Do not perform flare connection inside a building or dwelling or room, when joining the heat exchanger of indoor unit with interconnecting piping. Refrigerant connection inside a building or dwelling or room must be made by brazing or welding. Joint connection of indoor unit by flaring method can only be made at outdoor or at outside of a buidling or dwelling or room. Flare connection may cause gas leak and flammable atmosfere.
The appliance shall be stored, installed and operated in a well ventilated room with indoor floor area larger than Amin (m²) [Refer to Check of Density Limit] and without any continuously operating ignition source. Keep away from open flames, any operating gas appliances or any operating electric heater. Else, it may explode and cause injury or death.
Refer to "PRECAUTION FOR USING R410A REFRIGERANT" in outdoor unit installation manual for other precautions that need to pay attention to.

Check of Density Limit

WARNING CAUTION

Always check the gas density limit for the room in which the unit is installed.
Pay special attention to any location, such as a basement, etc., where leaking refrigerant can accumulate, since refrigerant gas is heavier than air.

When installing an air conditioner in a room, it is necessary to ensure that even if the refrigerant gas accidentally leaks out, its density does not exceed the limit level for that room. If the density could exceed the limit level, it is necessary to provide an opening between the unit and the adjacent room, or to install mechanical ventilation which is interlocked with a leak detector.
(Total refrigerant charged amount: kg)

(Min. indoor volume where the indoor unit is installed: m³)

 Limit density 0.44 (kg/m³)

The limit density of refrigerant R410A which is used in this unit is 0.44 kg/m³ (ISO 5149). The shipped outdoor unit comes charged with the amount of refrigerant fixed for each type, so add it to the amount that is charged in the field. (For the refrigerant charge amount at shipment, refer to the unit's nameplate.) Minimum indoor volume & floor area as against the amount of refrigerant is roughly as given in the following table.
Checking of limit density
Density limit is determined on the basis of the size of a room using an indoor unit of minimum capacity. For instance, when an indoor unit is used in a room (floor area 15 m2 × ceiling height 2.7 m = room volume 40.5 m3), the graph at right shows that the maximum overall refrigerant charge amount of limit density (0.44 kg/m3) that is not required to install a ventilation fan should be calculated as follows.

Due to the room volume, Maximum overall refrigerant charge amount
= (room volume) × (limit density) = 40.5 (m3) × 0.44 (kg/m3) = 17.82 kg

m2

m3

85 229.5

80 216.0

75 202.5

Overall refrigerant charge amount for this system is 72.709 (kg). The formula for the minimum room volume should be determined as follows.
Required minimum room volume = (overall refrigerant charge amount) ÷ (limit density) = 72.709 (kg) ÷ 0.44 (kg/m3) = 165.25 (m3)
Required minimum floor area = (minimum room volume) ÷ (ceiling height) = 165.25 (m3) ÷ 2.7 (m) = 61.2 (m2)
Therefore an opening for ventilation is required.
< Formula for computation > Overall refrigerant charge amount for the air conditioner: kg
(Minimum room volume for indoor unit: m3)

70 189.0

65 175.5

60 162.0

55 148.5 50 135.0

45 121.5

40 108.0

35

94.5

30

81.0

25

67.5

20

54.0

Range below the density limit of 0.44 kg/m³ (Countermeasures not needed)
Range above the density limit of 0.44 kg/m³ (Countermeasures needed)

72.709 (kg) =
40.5 (m³)

15

40.5

10

27.0

= 1.80 (kg/m3) > 0.44 (kg/m³)

5

13.5

Accordingly, it is necessary to install a ventilation fan for this room.

0

0.0

0 10 20 30 40 50 60 70 80 90 100 kg

Total amount of refrigerant

ACCESSORIES SUPPLIED WITH INDOOR UNIT

I N D O O R
U N I T

Part Name Special washer Drain hose

Figure

Q'ty

Remarks

Part Name

8 For indoor unit suspension Hose band

1 For drain hose connection Clamper

Figure

Q'ty

Remarks

1 For securing drain hose

2

For power supply cord / control wiring

1 SELECT THE INDOOR UNIT INSTALLATION LOCATION

1-1. Indoor Unit

Provide a check port on the piping side ceiling for repair and maintenance.  Install the indoor unit once the following conditions are satisfied and after receiving the customer approval.
1. The indoor unit must be within a maintenance space. 2. The indoor unit must be free from any obstacles in path of the air inlet and outlet, and must allow spread of air throughout the room.
 If the height from the floor to ceiling exceeds three meters, air flow distribution deteriorates and the effect is decreased.

WARNING
3. The installation position must be able to support a load four times the indoor unit weight. 4. The indoor unit must be away from heat and sources of steam, but avoiding installation near an entrance. 5. The indoor unit must allow easy draining. 6. The indoor unit must allow easy connection to the outdoor unit. 7. The indoor unit must be at least 3 m away from any noise-generating equipment. The electrical wiring must be shielded with a steel conduit. 8. If the power supply is subject to noise generation, add a suppressor. 9. Do not install the indoor unit in a laundry. Electric shocks may result. 10. Installation height is more than 2.5m.

NOTE

 Thoroughly study the following installation locations

1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat exchanger,

resulting in heat exchange reduction, spraying, dispersing of water drops, etc.

In these cases, take the following actions:

 Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily steam which

should not flow into the suction of the air conditioner.

 Make sure there is enough distance from the cooking room to install the air conditioner in such place where it may not suck in Air conditioner

oily steam.

2. Avoid installing the air conditioner in such circumstances where

cutting oil mist or iron powder exist, especially in factories, etc.
3. Avoid places where inflammable gas is generated, flows-in, contaminated, or leaked.
4. Avoid places where sulphurous acid gas or corrosive gas can be generated.

Ensure ample distance

Cooking table

Use the ventilation fan for smoke-collection hood with sufficient capacity.

5. Avoid places near high frequency generators.

1-2. When transporting the indoor unit to the roof space through the ceiling opening

Transport is possible without separation with a ceiling opening dimension of over 500 × 1,150 mm and a roof space dimension as shown below. After transporting the unit, see section "2. HOW TO INSTALL THE INDOOR UNIT"

1,600

Fan Block 1,000

Unit: mm
Unit Block 1,000

Roof space

Roof space

Ceiling

Over 1,150 Ceiling opening

Criteria for ceiling opening dimension and height of roof space

Width of ceiling opening
1,150

Height of roof space
1,600

Necessity of separating indoor
unit
Unnecessary

1,150 700

900 1,600

Necessary Necessary

Unit: mm

It is possible to separate the indoor unit into Fan Block and Unit Block. Separated transport if necessary

<Case 1>
If a ceiling opening dimension is over 500 × 1,150 mm and a roof space dimension is shown below, the indoor unit can be separated to fit through the space. For separating procedure, see section "1-3. How to separate the indoor unit".

1,500

Unit Block

Unit: mm 1,500

900

Roof space

Roof space

Ceiling

Over 1,150 Ceiling opening

<Case 2>
If a ceiling opening dimension is over 500 × 700 mm and a roof space dimension is shown below, the indoor unit can be separated to fit through the space. For separating procedure, see section "1-3. How to separate the indoor unit".

Unit: mm

Unit Block

1,000

1,000

Roof space

Roof space

1,600

Ceiling

Over 700 Ceiling opening

1-3. How to separate the indoor unit
(1) Remove the wire cover.
1. Loosen two screws.

2. Move to the left and remove the wire cover through the round hole.

Two screws

Move to the left.

Remove the wire cover.

(2) Remove the fan cover unit. 1. Remove two screws (Type 180 only)

2. Move the fan cover unit upward and remove it through the round hole.

Fan cover unit

Loosen the upper side 2 bolts

Remove the lower side 2 bolts

Two screws
3. Move the fan cover unit upward and remove it through the round hole. Round hole

(3) Remove the motor relay connector.

Remove one motor relay connector. (Type 180) Remove two motor relay connector. (Type 224 & Type 280)

Remove the wire from the fixed mounting bracket.

(4) Separate the fan motor unit and heat exchanger unit.

1. Loose the upper side three bolts and remove the lower side three bolts.

WARNING Do not remove the upper side three bolts. The motor unit may drop during work of unit separation and can lead to personal injury or death.

Type 180

Type 224 & Type 280

Loosen the upper side three bolts.

Loosen the upper side three bolts.

Access to the middle bolt from this hole

Remove the lower side three bolts
2. Move upward and remove the fan motor unit through the round hole. Round hole

Remove the lower side three bolts

1-4. How to assemble the indoor unit

(1) Attach the fan motor unit.

1. Pass the bolts for the heat exchanger unit through the round holes.
Mount the unit with three holes located in the center of the upper side.

2. Attach three bolts in the lower side and then fasten three bolts in the upper side. (Tightening torque : 2.45 ~ 3.4 N · m) Type 180 Fasten three bolts.
Attach the Middle bolt through this hole

3. Attach the motor wire.
Attach one motor connector. (Type 180) Attach two motor connectors. (Type 224 & Type 280) (Connectors at each end should be matched with the same color.)

Attach three bolts. Type 224 & Type 280
Fasten three bolts.

Wire with the fixed mounting bracket.

Attach three bolts. (2) Attach the fan cover unit and wire cover.
Attach the fan cover unit and wire cover in reverse order of separating unit.
2 HOW TO INSTALL THE INDOOR UNIT

2-1. Required Minimum Space for Installation and Service

(1) Dimensions of suspension bolt pitch and unit

1,006
465 (Suspension bolt pitch)

Min. 650 (Space for service)
Inspection access (600×600) (Field supply)

Min. 690 (Space for service)

Min. 20 Ceiling face Min. 150 486

Unit: mm

(60) 292 (Space for service)

Min.700 (Space for service)

1,070 1,288.5 (Suspension bolt pitch)

964

1,288.5 (Suspension bolt pitch)

1,291

166 29

32

Min. 800 (Space for service)

Drain port
Refrigerant tubing joint

Electrical component
box

627 (Suspension bolt pitch) Min. 916 (Space for service)

(2) Dimensions of indoor unit
977 916

260 70

Inspection access For communication

(600x1800)

wiring port

(Field supply)

For power supply wiring port

Inspection access (600×600) (Field supply)

Unit: mm

100

100

434

67 300

486 42 320 100

50

100

60

4-37×12 hole 26-ø3.2 hole 486

(63) 554

360

465

(Suspension bolt pitch)

28-ø3.2 hole

(60)

1,291 1,456

1,287

1,287

10×100 pitch = 1,000 1,070
1,288.5 (Suspension bolt pitch)

1,288.5 35.5 (Suspension bolt pitch)
964 9×100 pitch = 900

12

190 185 29

627
(Suspension bolt pitch)

Electrical component box 4

5

260 70

381

3

7 6

68 484

168

32 29

1

Refrigerant liquid tubing (Flare) Type 180/224/280 : ø12.7

Refrigerant gas tubing (Brazing) 2 Type 180 & Type 224 : ø19.05
Type 280 : ø22.22

3 Power supply port

4 Communication port

5 Drain port VP25

6 Air intake duct connecting side flange

7 Air discharge duct connecting side flange

Min. indoor floor area (when the ceiling is 2.7 m high)
Min. indoor volume L*
20 ~ 50

2-2. Suspending the Indoor Unit
Depending on the ceiling type: (1) Check the suspension bolt pitch. (2) Ensure that the ceiling is strong enough to support the weight of the unit. (3) To prevent the unit from dropping, firmly fasten the suspension bolts as shown in the figure below.

Unit: mm

NOTE

Hole-in-anchor
Hole-in-plug Concrete

Insert

Suspension bolt (field supply)
Fig. 3-1

Hexagonal nut (field supply) Special washer (field supply) Special washer (field supply) Hexagonal nut (field supply) Suspension bolt (field supply) Hexagonal nut (field supply) Special washer (supplied) Special washer (supplied)
Hexagonal nut (field supply)
Suspension lug
* Choose "L" dimension according to the status of the ceiling.
Fig. 3-2

Suspension bolt (field supply)

M10 or 3/8"

WARNING
It is important that you use extreme care in supporting the indoor unit inside the ceiling. Ensure that the ceiling is strong enough to support the weight of the unit. Before suspending the unit, test the strength of each attached suspension bolt.

(1) When placing the unit inside the ceiling, determine the pitch of the suspension bolts referring to the dimensional data given previously. Tubing must be laid and connected inside the ceiling when suspending the unit. If the ceiling is already constructed, lay the tubing into position for connection to the unit before placing the unit inside the ceiling.
(2) Screw in the suspension bolts allowing them to protrude from the ceiling as shown in Fig. 3-1. (Cut the ceiling material, if necessary.)
(3) Suspend and fix the indoor unit using the 2 hexagonal nuts (field supply) and special washers (supplied with the unit) as shown in Fig. 3-2.

CAUTION

The top of the unit must be installed horizontally.
Carpenter's level

Electrical component box

Horizontal level

Vinyl hose filled with water · Check the unit is placed horizontally.
Make sure the unit is installed level using a level or a vinyl hose filled with water. In using a vinyl hose instead of a level, adjust the top surface of the unit to the surface of the water at both ends of the vinyl hose and make horizontal adjustment on all 4 corners of the unit. If the air discharge side of the unit is installed downward, splashing water or water leak may occur. Also, the dust may accumulate inside the drain pan caused by draining residual water. · When lifting the unit, do not attempt to hold the electrical component box in hand.
2-3. Installing the Refrigerant Tubing
The size of the refrigerant tubing is as shown in the table below. Table 2-1

Type Gas tube
Liquid tube

180/224

280

ø19.05 (~ 100 m) (Brazing connection)

ø22.22 (~ 100 m) (Brazing connection)

ø12.7 (Flare connection) Tightening torque (approximate) : 49 ~ 55 N · m
Thickness of connecting tube : 0.8 mm

NOTE
To fasten the flare nuts, apply specified torque.
· When brazing, must be cool the pipe by wet cloths after removing the insulation tube and the cover plate.
· When brazing the gas tubing, cool the tubing with dampened shopcloths as you work, as shown in the figure below, to protect the unit's thermistor from the heat generated by brazing.
· When brazing, be careful not to heat the electrical component box. Doing so may cause the unit to be damaged.
· Pipe insulation must be made after leak detection for tubing connection area was performed.
· Be sure to insulate both the gas tubing and liquid tubing. · In addition, wrap the insulation material (field supply) around the tubing joints, and fasten in
place with vinyl tape or other means. Failure to insulate the tubing may result in water leakage from condensation. · Plug all gaps at tube through-holes in the unit with insulation or a similar substance to prevent air leakage.

Insulation tube Cover plate

Thermistor Wet cloth (inside unit)

2-4. Installing the Drain Piping

2-4-1. Before Performing the Installation Drain Piping
(1) (Prepare standard hard PVC pipe (O.D. 32 mm) for the drain and use the supplied drain socket to prevent water leaks. The PVC pipe must be purchased separately. When doing this, apply adhesive for the PVC pipe at the connection point. See section "2-4-2. Installing the Drain Pipe".

(2) Limitations of Drain Hose Connection

(3) Ensure the drain pipe has a downward slant (1/100 or more).

CAUTION Do not make a trap in the middle of the supplied drain pipe. Doing so will cause abnormal sound.

Downward slant Min. 1/100

Trap prohibited

Correct

Incorrect

(4) The drain pipe with a trap should be installed away from the indoor unit. (5) Do not attach any air purge equipment.
If attached, drain water may result in splashing out of the drain pipe. (6) When the drain piping is completed, perform the water leak test and check for a
water leak. If detected, it may result in water leakage or condensation. (7) When the drain piping is completed, perform the drainage test if the water drains smoothly. If not draining smoothly, it may result in water leakage or condensation. (8) When the drain piping work is finished securely, wrap the insulation material around the indoor side drain pipe. At this time, do not wrap together with the refrigerant tubing. If wraped together, the drain pipe is lifted and water drainage will not be operated. Consequently, the water comes out of the drain pan and it can lead to water leakage.

Inspection plug

*b *a

*a: over 100mm
*b: over 50mm
Note:
Since the drain trap area easily accumulates the dust inside the drain pipe, necessarily install the plug in order to clean out the drain trap.

2-4-2. Installing the Drain Pipe
CAUTION
(1) How to Connect Drain Port and Drain Hose
· First insert the supplied hose band into the drain port pipe. Then make sure the head of the screw is facing toward a technical engineer when placing the screw of the hose band at an upward angle.
· Insert the soft PVC socket of the supplied drain hose to the drain port pipe. Never apply the adhesive to the both ends of the soft PVC socket and the drain port pipe.
· Insert the drain hose to the point where there is a difference in level as shown in the figure below and fasten it with the hose band 5 mm away from that position.
· Tightening torque must be 2.5 ~ 3.4 N·m. · Tightening position of the hose band must be upward.
(2) How to Install the Drain Pipe
· Connect the hard PVC pipe (O.D. 32 mm) to the side of the soft PVC socket of the drain hose. · Apply approx. 2 g of adhesive on the side of the soft PVC socket of the drain hose and the side of the hard PVC pipe. · Do not apply force to the drain port when connecting the drain pipe. Install and fix it near the indoor unit as close as possible.

Hose band (supplied)

Hard PVC pipe (VP25 field supplied)

* Apply approx. 2 g of adhesive on the side of the soft PVC socket of the drain hose and the side of the hard PVC pipe. Wipe off the protrusion-adhesive with a soft cloth.

Drain port

(Drainage check section on drain port, transparent)
Uneven surface

Soft PVC socket Soft PVC socket
Drain hose (supplied)

Fasten the hose band as shown the diagram below. (Torque: 2.5 N·m - 3.4 N·m)

25 mm

Note: Hard PVC pipe is inserted in a fixed

position (inserted 25 mm)

Indoor unit

Indoor unit

until it hits Drain hose.

* Drain port may possibly be damaged and cause the water leakage if PVC adhesive is used.
Do not use adhesive here.

Adhere with PVC adhesive.

Uneven surface 5 mm

Drain insulator (Field supply)

* After checking the drainage, wrap the supplied drain hose with drain pipe insulator (field supply) all around the pipe.

Tube Insulator (Field Supply)

Tube Insulator (Field Supply)

Hose band (supplied)

Clampers (Field Supply)

(3) Insulating the Drain Hose
· Selection of heat insulation materials for drain hose (Drain insulator). When using the heat insulation materials (field supply), kindly use the same size and performance as refrigerant tubes. Check for its size as below table.

Insulation Material Polyethylene foam (same as heat insulators for refrigerant tubes)

Thermal insulation thickness Insulation thickness must 10mm or greater

CONTINUE TO THE NEXT PAGE

ENGLISH
ACXF60-54861 1/2
PRINTED IN MALAYSIA

2-5. Caution for Ducting Work

· This unit has high static pressure.

In case of small pressure resistance (for instance, a short duct), install an airflow control damper (field supply) for adjusting airflow volume

·

as airflow volume / airflow noise increases. If the air conditioner is to be installed in a room

such

as

an

office

or

meeting

room

which

needs

a

low

sound

level,

provide

a

supply

and

·

return Use a

sound absorption chamber flexible canvas connection

with an acoustic liner. or vibration isolation hanger

(field

supply)

to

break

transmission

of

mechanical

vibration

of

the

unit.

Canvas connection

Airflow control damper

Sound absorbing chamber

Sound absorbing chamber

Thermal insulation
Air discharge

Indoor unit
Inspection opening

Sound absorbing chamber

Thermal insulation
Air filter (field supply) Air intake
Ceiling panel

CAUTION
· Use incombustible duct materials. · Use thermal insulation to prevent duct condensation. · An air filter (field supply) must be installed at the air intake side.
If not installed, the heat exchanger will get dirty and the unit will reduce the quality. · Obtain and install an air filter (field supply) which can easily wash away the dust by lukewarm, soapy water or suck up with a vacuum cleaner. · Clean the air filter periodically to collect dust and other particles from the air. · Use duct static pressure within a range of specification value.

3 ELECTRICAL WIRING

As to main power source and cable size of outdoor unit, read the installation manual attached to the outdoor unit.

3-1. General Precautions on Wiring

WARNING

 This air conditioner must be installed in accordance with national wiring regulations.
 Cables connected to indoor unit must be approved polychloroprene sheathed type 60245 IEC 57 or heavier.
 The units must be connected to the supply cables for fixed wiring by qualified technician. Circuit breaker must be incorporated in the fixed wiring in accordance with the national wiring regulations. The circuit breaker must be approved, suitable for the voltage and current ratings of equipment and have a contact separation by 3mm in all poles. When the supply cable is damaged, it must be replaced by qualified technician.
 Be sure to install a current leakage breaker, main switch and fuse to the main power supply, otherwise electric shocks may result.

 Be sure to connect the unit to secure earth connection. If the earthing work is not carried out properly, electric shocks may result.

 Wiring shall be connected securely by using specified cables and fix them securely so that external force of the cables may not transfer to the terminal connection section. Imperfect connection and fixing leads to fire, etc.

(1) Select a power source that is capable of supplying the current required by the air conditioner. (2) Feed the power source to the unit via a distribution switch board designed for this purpose, the switch should disconnect all poles with a
contact separation of at least 3 mm. (3) Always ground the air conditioner with a grounding wire and screw to meet the LOCAL REGULATIONS. (4) Be sure to connect the indoor/outdoor unit connection wires correctly to terminal board. (5) Be sure to turn off the main power before installing and connecting the remote controller. (6) Each wiring connection must be done in accordance with the wiring system diagram.
Wrong wiring may cause the wires overloaded and overheated.

NOTE
If momentarily turning on the power supply for both the indoor and outdoor units, do not turn the power off after at least 1 minute has passed. (For the system's automatic setting.) Turning off the power supply on the way may cause an abnormal operation.

3-2. Wiring System Diagrams

Power supply 220-230-240V~ 50Hz 220-230V~ 60Hz
Remote controller
WHT 1 BLK 2

L N
Ground
D
1 2

Power supply 220-230-240V~ 50Hz 220-230V~ 60Hz
Remote controller WHT 1 BLK 2

L N
Ground
D
1 2

Group control :

Power supply 220-230-240V~ 50Hz 220-230V~ 60Hz

L N
Ground

Indoor unit (No. 1)
L N

B
U1 U2
R1 R2
Indoor unit (No. 2)
L N

B
U1 U2

R1 R2
Indoor unit (No. 3)
L N

B

E

U1

U2

R1 R2

C C

Outdoor unit INV unit
A
L1 U1
L2 U2
L3
N
1 2

L1 L2 L3

Power supply 380-400-415V 3N~ 50Hz

N 380-400V 3N~ 60Hz

Ground

Take care of faulty wiring 220~240V connecting prohibited

U1 U2 R1 R2

C

Remote control (Optional) wiring

Inter-unit (between outdoor and indoor units) control wiring

LN
Indoor power supply

Indoor unit

Indoor power supply

Outdoor power supply
C

Power supply 220-230-240V~ 50Hz 220-230V~ 60Hz

L N

Remote controller
WHT 1 BLK 2

Ground
D
1 2

Indoor unit (No. n)
L N
B
U1 U2
R1 R2

Inter-unit (between outdoor and indoor units) control wiring Refrigerant pipe
Outdoor unit

NOTE

( : Functional earthing)

(1) See the section "3-3. Recommended Wire Length and Wire Diameter for Power Supply System" for explanation of "A", "B", "C", "D", and "E" in the above diagram.
(2) The basic connection diagram of the indoor unit shows the 6P terminal board, so the terminal boards in your equipment may differ from the diagram.
(3) Attach the terminal cover after fixing the wires at the terminal board.

WARNING

Make sure that screws of the terminal are securely tightened.

3-3. Recommended Wire Length and Wire Diameter for Power Supply System

Indoor unit

Model

Power Supply

(B) Power Supply Cable

Time Delay

Min. Wire

Recommended Wire Length and Wire Diameter for Power Supply Cable

Fuse or Circuit

Size (mm2) Wire Size (mm2) Max. Length (m) Wire Size (mm2) Max. Length (m) Wire Size (mm2) Max. Length (m) Wire Size (mm2) Max. Length (m) Capacity (A)

S-180ME3H 220-230-240V~ 1.5

1.5

26

2.5

43

4.0

69

6.0

104

10

S-224ME3H 220-230-240V~ 1.5

1.5

23

2.5

39

4.0

62

6.0

93

10

S-280ME3H 220-230-240V~ 1.5

1.5

23

2.5

39

4.0

62

6.0

93

10

Control wiring
(C) Inter-unit (between outdoor and indoor units)
control wiring
0.75 mm2 (AWG #18) Use shielded wiring*
Max. 1,000 m

(D) Remote (E) Control wiring control wiring for group control

0.75 mm2 (AWG #18)
Max. 500 m

0.75 mm2 (AWG #18)
Max. 200 m (Total)

Inter-unit (between outdoor and indoor units) control wiring & Remote control (Optional) wiring

Use shielded wires for integrated control system wiring and ground the shield on both sides, otherwise misoperation from noise may occur. Connect wiring as shown in Section 3-2 Wiring System Diagrams.

Shielded wire

(Functional earthing)

(Functional earthing)

NOTE

··

For For

outdoor unit wire length and wire diameter for Optional Parts connecting wiring size, refer to

power supply system (A), Installation Manual of the

refer to the installation Optional Parts.

instruction

manual

that

comes

with

that

outdoor

unit.

If branching in the inter-unit control wiring, the number of branch points should be 16 or fewer

Central Controller

Outdoor unit

Branch point

Outdoor unit

Indoor unit

Indoor unit

Indoor unit

More than 2m required

Outdoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit Ground terminal fixing for ( : Functional earthing)
Power cable

Indoor unit

Indoor unit

Remote control wiring

Inter-unit (between outdoor and indoor units) control wiring

10 + 1 mm

Earth wiring: Clamper Indoor power supply Make the earth wiring 20~30mm (supplied) *1 longer than L, N.

WIRE STRIPPING AND CONNECTING REQUIREMENT

Wire stripping

Indoor/outdoor connecting
terminal board

Conductor fully Conductor over Conductor not

inserted

inserted

fully inserted

5 mm or more
No loose strand (gap between wires) when inserted

ACCEPT PROHIBITED PROHIBITED

This equipment must be properly earthed. Note: Isolating Devices (Disconnecting means) should have minimum 3.0 mm contact gap. Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reasons.  Earth lead wire shall be longer than other lead wires as shown in the figure for the electrical safety in case of the cord slipping out of anchorage.

4 REFRIGERANT PIPING

Must ensure mechanical connections be accessible for maintenance purposes. The liquid tubing side is connected by a flare nut, and the gas tubing side is connected by brazing.
4-1. Connecting the Refrigerant Tubing
Cautions During Brazing
· Replace air inside the tube with nitrogen gas to prevent copper oxide film from forming during the brazing process. (Oxygen, carbon dioxide and Freon are not acceptable.)
· Do not allow the tubing to get too hot during brazing. The nitrogen gas inside the tubing may overheat, causing refrigerant system valves to become damaged. Therefore allow the tubing to cool when brazing.
· Use a reducing valve for the nitrogen cylinder. · Do not use agents intended to prevent the formation of oxide film. These agents adversely affect the refrigerant and refrigerant
oil, and may cause damage or malfunctions.

4-2. Connecting Tubing Between Indoor and Outdoor Units
(1) Tightly connect the indoor-side refrigerant tubing extended from the wall with the outdoor-side tubing. Indoor Unit Tubing Connection

Indoor unit type

180/224

280

Gas tubing (mm)

ø19.05

ø22.22

Liquid tubing (mm)

ø12.7

(2) To fasten the flare nuts, apply specified torque.

Torque wrench

· When removing the flare nuts from the tubing connections, or when tightening them after connecting the tubing, be sure to use a torque wrench and a spanner. If the flare nuts are over-tightened, the flare

Indoor unit

Spanner

may be damaged, which could result in refrigerant leakage and cause injury or asphyxiation to room

occupants. · For the flare nuts at tubing connections, be sure to use the flare nuts that were supplied with the unit,

Outdoor unit

or else flare nuts for R410A, R32 (type 2). The refrigerant tubing that is used must be of the correct wall thickness as shown in the table

below.

Tube diameter ø12.7 (1/2")

Flare nut tightening torque (approximate) 55±6 N·m {550±60 kgf·cm}

Min. tube thickness 0.8 mm (Material Temper - O)

ø19.05 (6/8")

­

1.2 mm (Material Temper - O)

ø22.22 (7/8")

­

1.0 mm (Material Temper - 1/2 H · H)

· Because the pressure is approximately 1.6 times higher than conventional refrigerant R22 pressure, the use of ordinary flare nuts (type 1) or thin-walled tubes may result in tube rupture, injury, or asphyxiation caused by refrigerant leakage.
· In order to prevent damage to the flare caused by over-tightening of the flare nuts, use the table above as a guide when tightening. · When tightening the flare nut on the liquid tube, use an adjustable wrench with a nominal handle length of 200 mm.
4-3. Insulating the Refrigerant

CAUTION Be sure to perform heat insulation on the drain, liquid and gas piping. Imperfection in heat insulation work leads to water leakage.
(1) Selection of heat insulation materials for refrigerant tube. When using heat insulation materials (field supply), kindly check for its sizes and performance.
· Material for insulation material: Polyethylene foam. · Heat transfer rate: less than 0.051W/m·K. · Material withstand temperature: 120°C or above (gas tubing).
For other tubing 80°C or above · Must be easy to use, age resistance and not easily absorb moisture. · Be sure to match the below insulation material size with tube sizes.

Piping size, mm (In) 12.7 (1/2")

Thermal insulation size (I.D.) 14 ~ 16 mm

Thermal insulation Thickness

19.05 (3/4")

20 ~ 24 mm

Insulation thickness must be 10mm or greater

ø22.22 (7/8")

22 ~ 25 mm

(2) Taping the flare nuts
· Wind the white insulating tape around the flare nuts at the gas tube connection. · Then cover up the tubing connection with tube insulator (field supply) and fill in the
gap with black insulation tape. · Finally fasten with clampers (field supply)

Flare insulator (Field supply) Flare union
Unit side

NOTE
If noise bothers you from the area between indoor and outdoor units' connection pipes, it is effective to wind the soundproofing materials (field supply) to reduce noise.

Tube insulator (Field supply) Flare nut Heat resistant 120°C or above

CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. Never grasp the drain or refrigerant connecting outlets when moving the unit.

(3) Taping the tubes · Refrigerant tubes (and electrical wiring if local permit) should be taped together with armouring
tape in 1 bundle. Keep the drain hose separate from refrigerant tube to prevent condensation. · Wrap the armouring tape from bottom of the outdoor unit to the tubing here it enters the wall.
Overlap half of each previous turn. · Clamp the tubing to the wall, using 1 clamp approx. per each meter apart.
NOTE
Do not wind the armouring tape too tightly since this will decrease the heat insulation effect. Also ensure that the condensation drain hose splits away from the bundle and drips clear of the unit and the tubing.

Electrical wiring

Clamp

Insulated tubes

Drain hose

Two tubes arranged together

Gas tubing Liquid tubing

If the exterior of the outdoor unit valves has been finished with a
CAUTION square Duct covering, make sure you allow sufficient space to access the valves and to allow the panels to be attached and removed.

Insulation

(4) Finishing the Installation

· After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to prevent rain and draft from entering.

(5) Precautions in high humidity circumstances
· This air-conditioner has been tested according to the "JIS Standard Conditions with Mist" and have been confirmed that there are no faults. However, if it is operated for a long time in high humid atmosphere (dew point temperature: more than 23 °C ), water drops are liable to fall. In this case, add heat insulation material according to the following procedures: 1. Heat insulation material to be prepared. Adiabatic glass wool with thickness 10~20mm
2. Stick the wool on all air-conditioners that are located in the ceiling atmosphere
3. In addition to the normal heat insulation (thickness: more than 10mm) refrigerant piping, add a further of 10~30 mm thickness material.

Apply putty here Tubing

4-4. Additional Precautions for R410A models

For connection joint of all models Please make flare after inserting flare nut (locate at joint portion of tube assembly) onto the copper pipe. (In case of using long piping) Connect the piping
· Align the center of piping and sufficiently tighten the flare nut with fingers. · Further tighten the flare nut with torque wrench in specified torque as stated in the table.

Spanner or Wrench

Torque wrench

(1) Vacuum Drying
· After completing the piping connection, execute vacuum drying for the connecting piping and the indoor unit.
The vacuum drying must be carried out by using the service ports of both the liquid and gas side valves.

5 HOW TO INSTALL THE TIMER REMOTE
CONTROLLER OR HIGH-SPEC WIRED REMOTE CONTROLLER (OPTIONAL PART)
NOTE
Refer to the Installation Instructions attached to the optional Timer Remote Controller or optional High-spec Wired Remote Controller.

6 PRECAUTIONS ON TEST RUN

· Request that the customer be present when the test run is performed.
At this time, explain the operation manual and have the customer perform the actual steps.
· Check that the 220-230-240 VAC power is not connected to the U1 &
U2 terminal board terminal. * If 220-230-240 VAC is accidentally applied, the Fuse on indoor unit
Electronic Controller (Communication) will blow in order to protect the PCB. In this case, recover the connection by disconnect 2P connector wires that originally connected to the indoor unit Electronic Controller (Communication) OC connector and shift the connector wires to EMG connector on same indoor unit Electronic Controller (Communication). If operation is still not possible after shift to EMG connector, cut the jumper JP040 on the same indoor unit Electronic Controller (Communication).

Electronic Controller (Communication)

OC (CN040, blue)
EMG (CN044, brown)
Jumper (JP040)

7 EXTERNAL STATIC PRESSURE SETTING

Choose one of the methods (selection of "a", "b", "c" within the range of dotted line as shown in the flowchart below) and make settings. a. No setting changes: When using as it is factory preset at shipment.
(If resetting after external static pressure setting once, it might be different from factory preset.) b. Manual setting (on indoor unit Electronic Controller (Main)): This is static pressure setting excepting factory preset at shipment. Dip switch select method. c. Manual setting (by wired remote controller): Static pressure setting excepting factory preset at shipment.

Flow of External Static Pressure

NOTE

Start of external static pressure setting Setting of shipment : Line 1 (Refer Fig. 7-2)

Is it designed and

installed at the setting line at

No

shipment on PQ line drawing?

See section 7-5.

Yes

No

Selection methods of external static pressure setting

Operating by timer remote controller
Yes

(1) Refer to Tables 7-2, 7-3, 7-4 and Fig. 7-2 for details on the relationship between the value of item code "5d" and the external static pressure.
(2) (When set in group control (connecting multiple indoor units with one timer remote controller), set each indoor unit to item code "5d". When amending the setting after selecting [b. Manual setting] (due to airflow path changes, etc.), it is necessary to cancel [b. Manual setting] (switching OFF positions). When [b. Manual setting] has not been cancelled, [c. Manual setting] will be activated if selected, but [b. Manual setting] takes precedence when the power is switched back on after power outages, etc.
CAUTION

a. No setting changes

b. Manual setting (Setting on indoor unit Electronic
Controller (Main))
Setting switches of TP6 or TP3 or TP1 See section "7-1. How to Set on Indoor
Unit Electronic Controller (Main)".

c. Manual setting (Setting on wired remote controller)
Item code 5d : Setting 1, 3, 6 (*Note 1) (*Note 2)
See section 7-2, 7-3, or 7-4

Completion of external static pressure setting
7-1. How to Set on Indoor Unit Electronic Controller (Main)

 Make sure the external static pressure is in a range of specifications. Then proceed the external static pressure setting. Improper settings can cause noise, a shortage of airflow volume and water leakage. Refer to Fig. 7-2 for the external static pressure setting range.
 Be sure to set the [External Static Pressure Setting] once again after amending the airflow path for the duct or air outlet after setting the external static pressure.

(1) Turn off the power breaker to halt the supply of electricity to the indoor unit Electronic Controller (Main). (2) Open the lid of the electrical component box and confirm the location where the Select switch on the indoor unit Electronic Controller (Main) is
placed. (Fig. 7-1) (3) Set the On/Off switches in the Off position which are now set in the On position.
Select the positions of the Select SW001 switches respectively to make the desired external static pressure settings referring to the Table 7-1.

Table 7-1 External static pressure SW setting

Indoor Unit Electronic Controller (Main)

External static pressure at the time of rated airflow volume

180

224/280

180Pa

200Pa

120Pa

130Pa

75Pa

75Pa

SW001

TP6

TP3

TP1

ON

1

2

3

ON

1

2

3

ON

1

2

3

ON TP6 TP3 TP1
SW001
Setting at shipment

7-2. Operating the Timer Remote Controller (CZ-RTC4/CZ-RTC4A)

Fig. 7-1

How to set the external static pressure

(1) Press and hold down the , and buttons simultaneously for 4 or more seconds. (

, the Unit No., Item Code and Detailed Data will blink on

the LCD display.)

(2) The indoor unit numbers in the group control will be sequentially displayed whenever the Unit Select button is pressed .

Only the fan motor for the selected indoor unit will operate during this time.

(3) Specify the " " item code by pressing the / buttons for the temperature setting buttons and confirm the values. ("

" set at shipment)

(4) Press the / buttons for the time to amend the values for the set data.

1

Refer to Table 7-2 and Fig. 7-2 and select a value "

", "

" or "

".

1

4

(5) Press the button. The display will stop blinking and remain illuminated.



1

3



(6) Press the button. The fan motor will stop operating and the LCD display will return

4

to the normal stop mode.

2

Table 7-2 Setting the external static pressure

"
5

Indoor unit

180

224/280

External static pressure of the rated air flow volume

180 Pa 120 Pa 75 Pa

200 Pa 130 Pa 75 Pa

Item code

6

1

NOTE:

Failure to set this parameter may result in decreased airflow and condensation.

7-3. Operating the High-spec Wired Remote Controller (CZ-RTC5B)
How to set the external static pressure

[ ] START

20:30 (THU)

(1) Keep pressing the

,

and

buttons simultaneously

for 4 or more seconds.

The "Maintenance func" screen

appears on the LCD display.

Maintenance func 20:30 (THU)

0. ECONAVI info. 1. Outdoor unit error data 2. Service contact 3. RC setting mode

Sel.

Page [ ] Confirm

(2) Press the

or

button

Maintenance func 20:30 (THU)

to see each menu. If you wish

5. Sensor info.

to see the next screen instantly,

press the

or

button.

Select "8. Detailed settings" on the

LCD display and press the

6. Servicing check 7. Simple settings 8. Detailed settings

Sel.

Page [

] Confirm

button.

The "Detailed settings" screen

Detailed settings

20:30 (THU)

appears on the LCD display.

Select the "Unit no." by pressing

the

or

button for

Unit no. 3-1

Code no. 10

Set data 0006

changes.

Sel. Next

(3) Select the "Code no." by pressing

the

or

button.

Change the "Code no." to "5D"

by pressing the

or

button (or keeping it pressed).

Detailed settings

20:30 (THU)

Unit no. Code no. Set data

3-1

5D

0001

Sel. Next

(4) Select the "Set data" by pressing Table 7-3 Setting the external

the

or

button.

static pressure

Select one of the "Set data" among "0006", "0003" or "0001"

Indoor unit

Item code

according to the desired external 180

224/280

static pressure setting by

pressing the

or

button.

(See Table 7-3 and Fig. 7-2.)

Then press the

button.

External static pressure of the rated air flow volume

180 Pa

200 Pa

120 Pa

130 Pa

75 Pa

75 Pa

(5) Select the "Unit no." by pressing

the

or

button and

press the

button.

The "Exit detailed settings and

restart?" (Detailed setting-end)

screen appears on the LCD

display.

Select "YES" and press the

button.

Detailed settings

20:30 (THU)

Unit noE.xit adneCdtaoriledesedtasnreot?t.tings Set data

1-1

10

0001

YES

NO

Sel. Next

7-4. Operating the Wired Remote Controller (CZ-RTC6 series)

Stop the system before performing these steps. How to set the external static pressure

(1) Keep pressing the , and buttons simultaneously for 4 or more seconds. The "Maintenance func" screen appears on the LCD display. Maintenance func
XX / XX

ECONAVI nanoeX RC. setting mode

[]

[]

(2) Press the or button to see each menu. Select "Detailed settings" on the LCD display and press the button.

Maintenance func XX / XX
Simple settings Detailed settings Auto address

[]

[]

The "Detailed settings" screen appears on the LCD display.

(3) Select the "Unit no." by pressing the or button. After selecting "Unit no.", press the button and proceed to Step 4. If the button is pressed, proceed to Step 6.

Detailed settings

Unit no.

1-1

Code no. 000010

Set data []

00015 []

(4) Keep pressing the button for 2 seconds or more during selecting "Code no.".
Change the "Code no." one digit at a time so that it becomes [00005D] along with the following procedures.

Change the value by pressing the button.
After changing the value, press the and set the next digit.

or button

Change the value by pressing the button.
After changing the value, press the and set the next digit.

or button

Change the value by pressing the button.
After changing all digits, press the proceed to Step 5.

or button and

Detailed settings

Unit no. Code no. Set data []

1-1 000010 00015 []


Code no. 000001 - XXXXXX
000010

Set data 00015

[]

[]

Fig. A

Code no. 000001 - XXXXXX

00005D

Set data 00015

[]

[]

Fig. B

Code no. 000001 - XXXXXX

00005D

Set data []

00015 []
Fig. C

(5) Select one of the "Set data" among "0006", "0003" or "0001" according to the desired external static pressure setting by pressing the or button. (See Table 7-4.) After selecting "Set data", press the button. (If setting continuously, follow the procedures from Fig. A.) If you wish to change the selected indoor unit or finish setting, press the button twice (the display returns to Step 3).

Table 7-4 Setting the external static pressure

Indoor unit

180

224/280

External static pressure of the rated air flow volume

180 Pa

200 Pa

120 Pa

130 Pa

75 Pa

75 Pa

NOTE Failure to set this parameter may result in decreased airflow and condensation.
(6) If the button is pressed under the display Step 3, the following display (Detailed settingend screen) appears.Then select "YES" by pressing the or button and press the button.

Code no. 000001 - XXXXXX
00005D

Set data [] [

00011 ] Confrm
Fig. D

Item code

Detailed settings Exit detailed

Unit nos.ettings 1-1

Codaenndo.restart?10

YES

Set data 0001

NO

[]

[]

7-5. Indoor Fan Performance
Type 180 (External static pressure 75 Pa) Item code 5d = 0001

External static pressure (Pa)

120

110 100
90

Limit line

H

80

70

M

60

50

L

40

30

20

10 0

Limit line

45 50 55 60 65 70 75 80 85

Air Volume (m3/min)

Type 224 & Type 280
(External static pressure 75 Pa) Item code 5d = 0001

External static pressure (Pa)

130

120

110 100
90
80

Limit line

H

70

M

60

50

40

L

30

20

10

0

50 55 60 65 70 75 80 85 90 95 100

Air Volume (m3/min)

External static pressure (Pa)

External static pressure (Pa) Limit line

(External static pressure 120 Pa) Item code 5d = 0003
Setting at shipment

160

150

1

140

H

130

120

110

M

100

90

80

L

70

60

50 40

Limit line

30

45 50 55 60 65 70 75 80 85

Air Volume (m3/min)

(External static pressure 130 Pa) Item code 5d = 0003

Setting at shipment

200

180

1

160 140 120

Limit line

M

H

100

80

L

60

40 20

Limit line

50 55 60 65 70 75 80 85 90 95 100

Air Volume (m3/min)

External static pressure (Pa) Limit line

External static pressure (Pa) Limit line

(External static pressure 180 Pa) Item code 5d = 0006

220

200

H

180

160

M

140

120

L

100

80

Limit line

60 45 50 55 60 65 70 75 80 85 Air Volume (m3/min)

(External static pressure 200 Pa) Item code 5d = 0006

260

240 220

H

200

180

160

M

140

120

L

100 80

Limit line

60

50 55 60 65 70 75 80 85 90 95 100

Air Volume (m3/min)

Fig. 7-2

8 APPENDIX

 Name of Parts High Static Pressure Ducted
Air intake side duct flange (rear) Electrical component box
Water drain Air outlet side duct flange

Electrical Component Box

Electronic Controller
(Main)
Electronic Controller (Communication)

Electronic Controller (FM Power)

 Care and Cleaning

WARNING

· Engage authorized dealer or specialist for cleaning. · For safety, be sure to turn the air conditioner off and also to disconnect the

·

power before cleaning.

·

Do not pour water on the indoor unit to clean it. This will damage the internal components and cause an electric shock hazard.

·

Air intake and outlet side (Indoor unit)

Clean the air intake and outlet side of the indoor unit with a vacuum cleaner brush, or wipe them with a clean, soft cloth.

·

If these parts are stained, use a clean cloth moistened with water. When cleaning the air outlet side, be careful not to force the vanes out of place.

CAUTION
Never use solvents or harsh chemicals when cleaning the indoor unit. Do not wipe plastic parts using very hot water. Some metal edges and the fins are sharp and may cause injury if handled improperly; be especially careful when you clean these parts. The internal coil and other components of outdoor unit must be cleaned regularly. Consult your dealer or service center.

Air filter · In case of Installing the Duct (field supply)

Period (Depends on filter's specifications) When cleaning the air filter, consult your dealer or service center.

CAUTION

· Certain metal edges and the condenser fins are sharp and may cause injury if handled improperly; special care should be taken when you clean these parts.
· The internal coil and other components must also be cleaned periodically. Consult your dealer or service center.

Care: After a prolonged idle period

Check the indoor and outdoor unit air intakes and outlets for blockage; if there is a blockage, remove it. Care: Before a prolonged idle period · Operate the fan for half a day to dry out the inside. · Disconnect the power supply and also turn off the circuit breaker.

· Clean the air filter and replace it in its original position.

NOTE
Should the power fail while the unit is running If the power supply for this unit is temporarily cut off, the unit will automatically resume operation once power is restored using the same settings before the power was interrupted.

Important Information Regarding The Refrigerant Used

NOTE Refer to the Installation Instructions attached to the outdoor unit.

CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETE

 After completing work, be sure to measure and record trial run properties, and store measuring data, etc.
 Measuring items are room temperature, outside temperature, suction temperature, blow out temperature, wind velocity wind volume, voltage, current, presence of abnormal vibration and noise, operating pressure, piping temperature, compressive pressure, airtight pressure.
 As to the structure and appearance, check the following items.

Is circulation of air adequate?

Is there any leakage of refrigerant?

Are the terminal screws loosened?

Is draining smooth? Is heat insulation complete (refrigerant and drain piping)?

Is remote controller switch operated? Is there any faulty wiring?

M3...69-98N·cm {7-10kgf·cm} M4...157-196N·cm {16-20kgf·cm} M5...196-245N·cm {20-25kgf·cm}

HAND OVER

Optional Parts

 Teach the customer the operation and maintenance procedures, using the  Refer to Installation manual of optional parts (sold separately). operation manual (air filter cleaning, temperature control, etc.)

As for work specifications of the outdoor unit, read the OUTDOOR UNIT INSTALLATION MANUAL attached to the outdoor unit.

ENGLISH