Enlighted RM-6E-8W Radio Module
Shipped Components
- Enlighted Radio Module, 8-pin, (RM-6E-8W)
Supplemental Components
- Enlighted Radio Module Cable
- Enlighted Control Unit
Tools you may Need
- 7/8” Drill bit (1/2” knock out trade size)
- Hand drill
Caution
- A qualified electrician must perform installation and maintenance under local, state, and national electrical codes (NEC) and requirements.
- To avoid the possibility of exceeding the FCC and ISED radio frequency exposure limits, human proximity to the radiator shall not be less than 20cm during normal operation.
Fixture Mount Radio Module Installation
- Step 1: De-energize the luminaire.
Note: For fixture mounting, use the fixture carrier and nut that is shipped with the module. The fixture mount can accommodate up to 0.25” thickness materials.
- Step 2: Determine the location for the module in the fixture and cut a ½ inch (7/8” diameter) knockout in the fixture.
- Step 3: Insert the fixture carrier through the hole in the fixture.
- Step 4: From behind the fixture, align the tabs of the nut with the keys on the fixture carrier.
- Step 5: Slide the tabs of the nut along the keys of the carrier to fasten the carrier.
- Step 6: Insert the 8-pin end of the module cable through the carrier.
- Step 7: Connect the 8-pin connector to the module.
- Step 8: Guiding the wire from above, push the module into the carrier until it securely clicks into the carrier.
- Step 9: Leave four inches of slack cable in the sequence loop to avoid pinching of the cable and to bring the module down if it needs to be replaced.
Note: Do not pull the cable forcefully as this might damage the cable or connector.
- Step 10: See section Connecting the Radio Module Cable to the Control Unit on Page 5.
Tile Mount Radio Module Installation
Note: For tile mounting, the tile carrier and nut must be ordered separately. The tile mount can accommodate up to 1.5” thick tiles.
- Step 1: De-energize the luminaire.
- Step 2: Make a 7/8th diameter hole in the ceiling tile.
- Step 3: Insert the tile carrier through the hole into the tile.
- Step 4: Thread the plain end of the nut from behind the tile to secure the carrier.
If the tile is thicker than normal, flip the nut and thread the ribbed end of the nut to secure the carrier.
- Step 6: Connect the 8-pin connector to the module.
- Step 7: Guiding the wire from above, push the module into the carrier until it securely clicks into the carrier.
- Step 8: Leave four inches of slack cable in the sequence loop to avoid pinching of the cable and to bring the module down if it needs to be replaced.
Note: Do not pull the cable forcefully as this might damage the cable or connector. - Step 9: See section Connecting the Radio Module Cable to the Control Unit on Page 5.
Connecting the Radio Module Cable to the Control Unit
- Step 1: Connect one end of the Radio Module cable to the Control Unit (CU). For wiring connections from the Control Unit to the module, refer to the Control Unit Installation Guide.
- Step 2: Energize the luminaire and confirm that the green LED is on solid.
LED Description
Note: The purpose of wiring test is to serve as a sanity check regarding connectivity to the Radio Module. However, the overall responsibility of the quality of the device must meet the QC criteria for the light fixture manufacturer.
LED Status | Description/Solution |
LED not ON |
|
Solid Green | The un commissioned Radio Module has powered up successfully and completed the wiring test with no unexpected conditions – waiting for discovery. |
Blinking Red | The un commissioned Radio Module has powered up and completed the wiring test with one or more conditions unexpected of a typical LED fixture – waiting for discovery. |
Solid Red | Faulty Radio Module – replace the Radio Module. |
Solid Blue | Radio Module received a request to identify itself. |
Blinking Blue | The un commissioned Radio Module powered up successfully, but the module is unable to detect an energy measurement device (CU or Driver), waiting for discovery. |
Blinking Magenta | When the Radio Module is connected to the control unit that is currently in the process of an emergency test or an emergency test pending. |
Company Contact Information
- Location: 3979 Freedom Circle, #210, Santa Clara, CA 95054
- Phone: +1.650.964.1094
- Web: enlightedinc.com
- DoCs: https://www.enlightedinc.com/eu-docs/
- Support Portal: support.enlightedinc.com
- Model No. RM-6E
- Product Code: RM-6E-8W
- Power: 180mW
- FCC ID: AQQ-SU6E
- IC: 10138A-SU6E
FCC
This device complies with Part 15 of the FCC Rules and Innovation, Science and Economic Development Canada’s license-exempt RSS standard(s). Operation is subject to the following two conditions:
- This device may not cause harmful interference, and
- This device must accept any interference received, including interference that may cause undesired operation of the device.
Changes or modifications not expressly approved by Enlighted could void the user’s authority to operate the equipment.
Copyright ©2024 Enlighted Inc. All rights reserved. All other brand or product names are trademarks of their respective companies or organizations.
FAQ
- Q: What should I do if the LED status is Blinking Magenta?
A: If the LED status is Blinking Magenta, it indicates that the Radio Module is in a specific state. Check for any specific instructions related to this status in the user manual or contact customer support for assistance.
Documents / Resources
![]() |
Enlighted RM-6E-8W Radio Module [pdf] Installation Guide RM-6E, RM-6E-8W, RM-6E-8W Radio Module, RM-6E-8W, Radio Module, Module |