EnerSys CXPS-HX Distributed Power System

Product Usage Instructions
AC Conduit Access
Ensure the unit is powered off before accessing the AC conduit. The top or bottom entry can be used for AC conduit access.
Cable Routing
Use the removable plate to facilitate cable routing within the unit for a neat and organized setup.
Terminal Blocks and Fuses
Connect cables to the terminal blocks for power distribution. The TPL fuse distribution panels support fuses up to 1200A for protection.
Rectifier Shelves
The unit comes with 5 X 4.6kW rectifier shelves with a maximum capacity of 2875A. Ensure proper installation and connection of rectifier modules.
Safety Certification
The product is designed for NEBS compliance and meets CSA/UL 62368-1 safety standards. Refer to the datasheets for detailed safety information.
Product Features
- −48VDC power system providing 2875A output capacity
- Front access AC input termination panel increases useable floor space, reduces installation time and simplifies maintenance
- Flexible top and bottom AC feed options from a single bay
- Front access DC output connections including:
- TPL fuses up to 1200A
- GJ breakers up to 600A
- Each distribution panel designed to accommodate the full rectifier capacity
- Dual bay kit links two 2875A bays doubling capacity, breakers, and termination
The Cordex® CXPS-HX front access system provides high capacity DC power for large communication network applications.
- This system combines the capabilities of tiered distribution, advanced microprocessor based supervision, and modular rectifiers in a single integrated bay. Two bays can easily be linked together and share a central controller to double the system capacity.
- The Cordex® Distributed Power System is cost effective due to the internal copper bus work, and is delivered ready to assemble with factory tested components. No overhead bus work is required. An optional external return bus is available. Cable access is from the top and load connections are terminated from the side or rear of the bay. Hot swappable Cordex ® power modules and internal buss work provides a safe work environment with easy installation and maintenance.
Description
Cordex® CXPS-HX Power System 2875A Front Access DC Solution
The Cordex® CXPS-HX series is a compact, true front access, multi capacity -48VDC power system designed for space constrained communication applications. The front access HX-Plant optimizes floor space, streamlines installation, and simplifies maintenance, empowering organizations to achieve seamless connectivity and operational excellence.
- Optimizes floor space: The true front access system allows for installation directly against a wall, increasing useable floor space
- Streamlines installation: Front access AC input terminal blocks that are factory wired to the rear of the rectifier shelves, reducing installation time
- Simplifies maintenance: Site visits and general maintenance made simpler via ease of access to AC, DC, and battery connections

Technical Data
Cordex® CXPS-HX Power System 2875A Front Access DC Solution
P/N: Refer online to ordering guide for P/N and configurations
| Electrical | Distribution | ||||
| DC Output | Fuses | ||||
| TPL Fuses | •Up to 1200 A per fuse•6 fuse holders per panel•Max. 2 fuse panels per bay | ||||
| Output Voltage | −48 VDC | ||||
| TPL Fuse Panel Capacity | 2875 A per tier | ||||
| Output Capacity | •138 kW One bay system•276 kW Two bay system | ||||
| GJ Breakers | •Up to 3-pole 600 A breakers•5 breaker positions per panel•Max. 2 breaker panels per bay | ||||
| Max. Bus Capacity | •2875 A One bay system•5000 A Two bay system | ||||
| GJ Breaker Panel Capacity | 2875 A per tier | ||||
| Current per Cordex HP 4.6 kW Module | 95.8 A @ −48 VDC | ||||
| Related Components | |||||
| AC Input | |||||
| Nominal Input Voltage | •Single phase, 208 to 277 VAC•3-phase, 208 VAC•3-phase, 277/480 VAC (48/4.6 kW) | Cordex HP 48 V 4.6 kW Rectifier Module | See datasheet and the rectifier documentation for more detailed information | ||
| Cordex CXC HP System Controller | See datasheet and the controller documentation for more detailed information | ||||
| AC Connectors | Front access DIN-Rail terminal blocks | ||||
| AC Access | Top and bottom | Certification | |||
| Mechanical | Safety | CSA/UL 62368-1 | |||
| Dimensions H × W × D | 84 × 30 × 26 in. | NEBS | Designed for NEBS compliance | ||
| Weight | 600 lbs per bay (w/o modules) | ||||
| Environmental | |||||
| Temperature | 0 to 40°C (32 to 104°F) | ||||
| Humidity | 0 to 95% RH non-condensing | ||||
| Elevation | −500 to 2800 m (−1640 to 9186 ft) | ||||
World Headquarters
- 2366 Bernville Road
- Reading, PA 19605 USA
- +1 610-208-1991 / +1 800-538-3627
EnerSys EMEA
- EH Europe GmbH
- Baarerstrasse 18
- 6300 Zug Switzerland
EnerSys Asia
- No. 85, Tuas Avenue 1
- Singapore, 639518
- +65 6558 7333
For more information visit www.enersys.com © 2024 EnerSys. All Rights Reserved. Trademarks and logos are the property of EnerSys and its affiliates except for CSA® and UL® which are not the property of EnerSys. Subject to revisions without prior notice. E.&O.E.
FAQ
- Q: Where can I find more detailed information about the rectifier module and system controller?
- A: Refer to the datasheets and documentation provided for the rectifier module and system controller for comprehensive information on their operation and specifications.
- Q: How many rectifier shelves does the unit support?
- A: The unit comes with 5 rectifier shelves, each supporting up to 4.6kW, with a maximum capacity of 2875A.
- Q: What safety certifications does the product have?
- A: The product is certified to meet CSA/UL 62368-1 standards and is designed for NEBS compliance, ensuring safe operation in various environments.
Documents / Resources
![]() |
EnerSys CXPS-HX Distributed Power System [pdf] Owner's Manual CXPS-HX, CXPS-HX Distributed Power System, Distributed Power System, Power System |