Sensors | Installation Instructions
DP-EBDMR-DALI2
DALI-2 Mid-range Presence Detector
OVERVIEW
The DP-EBDMR-DALI2 sensor is fully DALI 2 certified and compatible for use as part of an Encelium X DALI Lighting Control System. The EBDMR sensor has uses a domed faceted lens for an increased detection range and can be programmed as both a presence (PIR) and light sensor. For more information on product specifications and design tools visit encelium.com.
PRODUCT SAFETY
READ THESE INSTRUCTIONS BEFORE USING THE PRODUCT
This device should be installed by a qualified electrician in accordance with the latest edition of the IET wiring regulations.
SAVE THESE INSTRUCTIONS.
DIMENSIONS
DETECTION PATTERN
INSTALLATION
This device is designed to be flush ceiling-mounted.
- Do not site the unit where direct sunlight might enter the sensor.
- Do not site the sensor within 1m of any lighting, forced air heating or ventilation.
- Do not fix the sensor to an unstable or vibrating surface.0.1575 in.
Create cut out
1. Cut a 64mm diameter hole in the ceiling.Wire stripping
2. Strip the wires as shown opposite. Presence detector does not require ground conductor.Wire in plugs
Connect to detector 3. Connect the plug/s to the detector.
Clamp cable
3. Continue tightening the screws until the clamp bar snaps out and is tightly engaged against the cable. The cable clamp must clamp the outer sheath only.
Install detector3. Bend the springs up and push detector through hole in ceiling. When fully inserted the springs snap back to hold the device in place.
To avoid injury, take care when bending springs.
TECHNICAL DATA
Weight ………………………………………………………………….. 150g
Supply voltage DC ……………………………………….9.5–22.5 VDC DALI bus
Nominal Current Consumption………………………………………. 8mA
Max (Peak) Current Consumption………………………………. 18mA
Terminal capacity………………………………………………………… 2.5mm²
Rated impulse voltage………………………………………………………….. 2500V
Purpose ………………………………………………………… Sensing control
Construction…………… Independent flush mounted, electronic control
Type of action ……………………….. Type 1.B action (micro disconnection)
Operating temperature ……………………………………. -10ºC to +35ºC
Humidity…………………………………………………… 5 to 95% non-condensing
Pollution ……………………………………………………………………………… Degree 2
Software …………………………………………………………………………………. Class A
Material (casing)…………………………… Flame retardant ABS and PC/ABS
DALI-2 Certification ………………. IEC62386 Parts 101,103, 303 & 304
Compliance …………………………………………………………….
© Copyright 2024 Legrand All Rights Reserved.
080371r1 02/24