EMERSON LOGOM400 Supervisory Controller Setup
User Guide

Supervisory Controller Setup

This document will guide you through setting up and commissioning the M400 VFD Drive in Supervisory Controllers (E3 and Site Supervisor).
Complete All Programming Before you set up the M400 Drive.
Note that the M400 Drive requires Supervisory Controller firmware version 2.14F01 and above.
The keypad and display give information about the operating status of the drive and tripcodes. It provides the ability to change parameters, stop and start the drive, and the ability to perform a drive reset.

EMERSON M400 Supervisory Controller SetupEMERSON M400 Supervisory Controller Setup - igure 2

Keypad Number Keypad Description
1 (Enter) The Enter button is used to enter parameter view or edit mode, or to accept a parameter edit.
2 (Navigation) The Navigation keys can be used to select individual parameters or to edit parameter values. In keypad mode, the “Up” and “Down” keys are also used to increase or decrease the motor speed.
3 (Start) The Start key is used to start the drive in keypad mode.
4 (Stop/Reset) The Stop / Reset key is used to stop and reset the drive in keypad mode. It can also be used to reset the drive in terminal mode.
5 (Escape) The Escape key is used to exit from the parameter edit/view mode or disregard a parameter edit.

STEP 1: Configuring M400 VFD Drive

Note: Do not connect the device communications to the E2 controller.

  1. Press the right/ left arrow key and go to Pr MM.000 then pressEMERSON M400 Supervisory Controller Setup - ICON. Select Reset 60Hz defs then pressEMERSON M400 Supervisory Controller Setup - ICON.
    Note: Pressing EMERSON M400 Supervisory Controller Setup - ICONallows you to enter and exit parameter edit mode.
  2. Press EMERSON M400 Supervisory Controller Setup - ICON2to return the drive into the No Action display.
  3. Go to Pr 00.005 (Drive Config), then pressEMERSON M400 Supervisory Controller Setup - ICON. Select Preset, then pressEMERSON M400 Supervisory Controller Setup - ICON.
  4. Set Pr 00.010 (User Security Status), then pressEMERSON M400 Supervisory Controller Setup - ICON. Select All Menus, then pressEMERSON M400 Supervisory Controller Setup - ICON.
  5. Set Pr 06.004 (Start/Stop Logic), then pressEMERSON M400 Supervisory Controller Setup - ICON. Select 6, then pressEMERSON M400 Supervisory Controller Setup - ICON.
  6. Set Pr 11.023 (Serial Address), then pressEMERSON M400 Supervisory Controller Setup - ICON. Select 2, then pressEMERSON M400 Supervisory Controller Setup - ICON.
  7. Set Pr 11.024 (Serial Mode), then pressEMERSON M400 Supervisory Controller Setup - ICON. Select 8 1 NP, then pressEMERSON M400 Supervisory Controller Setup - ICON.
  8. Set Pr 11.020 (Serial Reset), then pressEMERSON M400 Supervisory Controller Setup - ICON. Select On to reset communications.
    Note: The device will flash to On and returns to Off, press .
  9. Set Pr 12.000 (Parameter mm.000), then pressEMERSON M400 Supervisory Controller Setup - ICON. Select Save Parameters, then pressEMERSON M400 Supervisory Controller Setup - ICON.
  10. PressEMERSON M400 Supervisory Controller Setup - ICON2 to return the drive into the No Action display.
    Note: The drive is now ready to communicate with the Supervisory controller and is ready for a test/run.
Model Max # of Instances
1 SR 20
2 CXe 16
3 CX 16
4 BXe 16
5 BX 16
6 RXe 16
7 RX 16
8 SMF No

STEP 2: Setting the Baud Rate in the Supervisory Controller

Gear iconEMERSON M400 Supervisory Controller Setup - ICON3 > Configure System Properties > General System PropertiesEMERSON M400 Supervisory Controller Setup - Figure 3EMERSON M400 Supervisory Controller Setup - Figure 4

  • Set the Com Port baud to 19.2

STEP 3: Wiring the M400 VFD Device to Emerson Controllers

Wire the device as shown below:

EMERSON M400 Supervisory Controller Setup - Figure 5

COM wiring is the REVERSE polarity of the Site Supervisor.

  • + On the Com port goes to – on the VFD.
  • – On the Com port goes to the + on the VFD.
  • Do NOT connect the shield to any terminal on the controller or VFD. Connect the shield directly to Earth Chassis at the controller; clip and insulate the shield at the VFD end of the cable.
  • If VFD is the last device at the end of the Com segment, terminate with 150 ohms between terminals 2 and 3.
    EMERSON M400 Supervisory Controller Setup - Figure 6

COM wiring is the same polarity as E2 and E3.

  • + On the Com port goes to + on the VFD.
  • – On the Com port goes to – on the VFD.
  • Do NOT connect the shield to any terminal on the controller or VFD. Connect the shield directly to Earth Chassis at the controller; clip and insulate the shield at the VFD end of the cable.
  • If VFD is the last device at end of the Com segment, terminate with 150 ohms between terminals 2 and 3.
EMERSON M400 Supervisory Controller Setup - Figure 7 EMERSON M400 Supervisory Controller Setup - Figure 8
EMERSON M400 Supervisory Controller Setup - Figure 9 EMERSON M400 Supervisory Controller Setup - Figure 10

STEP 4: Adding the Device to the Supervisory Controller

  1. From the home page click the control inventory iconEMERSON M400 Supervisory Controller Setup - ICON4 to go to the Control Inventory page.
  2. From the HVAC drop-down list, select M400 from the list.

EMERSON M400 Supervisory Controller Setup - Figure 11

STEP 5: Commissioning the Device to the Supervisory Controller

From the Control Inventory screen select the Modbus address for the M400 and click the checkmarkEMERSON M400 Supervisory Controller Setup - ICON5 to save and start commissioning. (Best practices tip: set the Modbus number to match the connected Com Port and the Address to match the M400 addressing in STEP 1).
Drive Setup:

  1. Click the M400 to go to the M400 setup page.
  2. Go to the General tab.
  3. Set CfgSyncAction on the to Write to Device.
  4. On the Inputs tab, set DIRECTION to forwarding or Reverse. This verifies that the drive should run correctly.
  5. Set RUN to OFF. This verifies that the drive should inhibit.
  6. Inputs tab on the Details screen:
    EMERSON M400 Supervisory Controller Setup - Figure 12
  7. Inputs tab on the Details screen:EMERSON M400 Supervisory Controller Setup - Figure 13
  8. Go to the Setpoints tab to set the values for MOTOR VOLT, MOTOR RPM, and MOTOR FLA from the motor plate of the device.EMERSON M400 Supervisory Controller Setup - Figure 14
  9. Go to the Status screen and the device will appear online:EMERSON M400 Supervisory Controller Setup - Figure 15
  10. General tab screen Verify Write to Device is set (default).EMERSON M400 Supervisory Controller Setup - Figure 16
  11. From the Details screen, click Commands on the far right and select NVM_SAVE:EMERSON M400 Supervisory Controller Setup - Figure 17
  12. From the Details screen, click Commands on the far right and select DRIVE-RESET. The drive is now reset with the needed configuration.EMERSON M400 Supervisory Controller Setup - Figure 18

STEP 6: Verification of Settings

  1. After commissioning the new device, verify that the following values are set in the drive:
    • 0.009 (MOTOR_PWR_FACTOR) = 0.85 or the value that you set
    • 6.004 (Start/Stop Logic) = 6
    • 8.023 (Digital input 3) = 0.000
    The following parameters must be set up in the Inputs tab to run the drive.
    • RUN (ON)
    • DIRECTION (FORWARD, REVERSE)
    • REF FREQ (the speed setting of the motor)EMERSON M400 Supervisory Controller Setup - Figure 19
  2. Use Table 1- Menu 0 Guide to verify values set in the M400 drive.
    Note: Table 1- Menu 0 Guide gives diagnostic information about the system. It allows you to double-check to make sure that the E2 controller sent the correct parameters.
    Table 1 – Menu 0 Guide
    Menu 0 Pr Description Value to Write Comments Parameter Type
    1 Drive Configuration Preset Sets drive mode to Preset 11. Mode
    2 Serial Baud Rate 19200 Sets baud to 19200 11. Mode
    3 Serial Address 2 Set the address for each drive on the network. 11. Mode
    4 Serial Mode 81 NP Set to match the mode of E2E 11. Mode
    5 Reset Serial Communications Toggle ON/ Set this to ON / OFF to reset communications. Connects 11. Mode
    6 Motor Rated Current See Motor Set from the motor nameplate. 5. Motor
    7 Motor Rated Speed See Motor Set from the motor nameplate. 5. Motor
    8 Motor Rated Voltage See Motor Set from the motor nameplate. 5. Motor
    9 Motor Power Factor See Motor Set from the motor nameplate. (Use 0.85 if absent.) 5.010 Motor
    10 Security / Parameter Access Set to All Menus Set to all Menus to see access Menu 1 to 22 11. Access
    12 STO 1 State RO 0=disabled, 1=enabled 8. Info
    13 STO 2 State RO 0=disabled, 1=enabled 8.040 Info
    14 Reference Selected RO Shows reference selected. Hz desired. 1. Info
    15 Valu e of reference in r pm RO Shows reference in rpm. 1
    1.069
    Info
    16 Hz sent from the controller RW Can see the speed sent from the controller here 1. Info
    20 Preset Speed 2 (Manual) RW Use this to set manual f-test speed. 1. Manual
    21 Preset Selector 0 or 2 Use this to turn on the manual f-test speed. 1. Manual
    30 Current Trip (Trip 0) RO Gives a code for the current trip. (Trip 0) 10.020 Trip
    31 Trip 1 RO Previous trip – before Trip 0 10. Trip
    32 Trip 2 RO Previous trip – before Trip1 10. Trip
    33 Trip 3 RO Previous trip – before Trip 2 10. Trip
    34 Trip 4 RO Previous trip – before Trip 3 10. Trip
    35 Trip 5 RO Previous trip – before Trip 4 10. Trip
    36 Trip 6 RO Previous trip – before Trip 5 10. Trip
    37 Trip 7 RO Previous trip – before Trip 6 10. Trip
    38 Trip 8 RO Previous trip – before Trip 7 10. Trip
    39 Trip 9 RO Previous trip – before Trip 8 10. Trip

Document Part # 026-4176 Rev 2

This document may be photocopied for personal use.
Visit our website at www.climate.emerson.com for the latest technical documentation and updates.
Join Emerson Technical Support on Facebook. http://on.fb.me/WUQRnt
For Technical Support call 833-409-7505 or email ColdChain.TechnicalServices@Emerson.com

The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or
applicability. Emerson reserves the right to modify the designs or specifications of such products at any time without notice. Responsibility for the proper selection, use, and maintenance of any product remains solely with the purchaser and end-user.
©2022 Emerson is a trademark of Emerson Electric Co.

Documents / Resources

EMERSON M400 Supervisory Controller Setup [pdf] User Guide
M400 Supervisory Controller Setup, M400, Supervisory Controller Setup, Controller Setup

References

Leave a comment

Your email address will not be published. Required fields are marked *