EMERSON-logo

EMERSON EXD-HP1 2 Controller with ModBus Communication Capability

EMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-product

Product Information

Specifications

  • Power supply: AC 24V
  • Power consumption: EXD-HP1: 15VA, EXD-HP2: 20VA
  • Plug-in connector: Removable screw terminals wire size 0.14…1.5 mm2
  • Protection class: IP20
  • Digital Inputs: Potential free contacts (free from voltage)
  • Temperature sensors: ECP-P30
  • Pressure sensors: PT5N
  • Output alarm relay: SPDT contact 24V AC 1 Amp inductive load; 24V AC/DC 4 Amp resistive load
  • Stepper motor output: Coil: EXM-125/EXL-125 or EXN-125 Valves: EXM/EXL-… or EXN-…
  • Type of action: 1B
  • Rated impulse voltage: 0.5kV
  • Pollution Degree: 2

Product Usage Instructions

Mounting
The EXD-HP1/2 controller can be mounted on a standard DIN rail. Ensure that the controller is equipped with core cable ends or metallic protective sleeves when connecting wires. When connecting the wires of EXM/EXL or EXN valves, follow the colour coding as listed below:

Terminal EXM/L-125 wire color EXN-125 wire color
EXD-HP1 Brown Red
6 Blue Blue
7 Orange Orange
8 Yellow Yellow
9 White White
10
EXD-HP2 Brown Red
30 Blue Blue
31 Orange Orange
32 Yellow Yellow
33 White White
34

Interfacing and Communication
If Modbus communication is not being used, it is necessary to establish interfaces between the EXD-HP1/2 controller and the upper-level system controller. The external digital input should be operated in the function system’s compressor/demand. Ensure that necessary precautions are in place to protect the system.

Operating Conditions
The digital input status for the compressor is as follows:

  • Compressor starts/run: closed (Start)
  • Compressor stops: open (Stop)

Note:
Connecting any EXD-HP1/2 inputs to the supply voltage will permanently damage the EXD-HP1/2.

Electrical Connection and Wiring
When making electrical connections and wiring, follow these instructions:

  • Use a class II category transformer for a 24VAC power supply.
  • Do not ground the 24VAC lines.
  • It is recommended to use individual transformers for the EXD-HP1/2 controller and third-party controllers to avoid possible interference or grounding problems in the power supply.
  • Strip the wire insulation approximately 7 mm at the end.
  • Insert the wires into the terminal block and tighten the screws securely.
  • Ensure that the wires are properly connected and there are no loose connections.

Display/Keypad Unit (LEDs and Button Functions)
The display/keypad unit of the EXD-HP1/2 controller has the following LED indicators and button functions:

  • ON: Data display
  • ON: alarm
  • ON: ModBus
  • Circuit 1

FAQ (Frequently Asked Questions)

  • Q: Can the EXD-HP1/2 controller be used with flammable refrigerants?
    A: No, the EXD-HP1/2 controller has a potential ignition source and does not comply with ATEX requirements. It should only be installed in a non-explosive environment. For flammable refrigerants, use valves and accessories that are approved for such applications.
  • Q: How should I dispose of the EXD-HP1/2 controller once it reaches the end of its life?
    A: The EXD-HP1/2 controller should not be disposed of as commercial waste. It is the user’s responsibility to pass it to a designated collection point for safe recycling of Waste Electrical and Electronic Equipment (WEEE directive 2019/19/EU). For further information, contact your local environmental recycling centre.

General information

EXD-HP1/2 are stand-alone superheat and or economizer controllers. EXD-HP1 is intended for the operation of one EXM/EXL or EXN valve whereas EXD-HP2 is designed for the operation of two independent EXM/EXL or two EXN valves.

Note:
It is possible to use only Circuit 1 from EXD-HP2. In this case, circuit 2 must be disabled (C2 parameter) and the sensors and the valve for the second circuit are not needed.

ModBus communication is described in a Technical Bulletin and it is not covered by this document.

Technical Data

Power supply 24VAC/DC ±10%; 1A
Power consumption EXD-HP1: 15VA        EXD-HP2: 20VA
Plug-in connector Removable screw terminals wire size 0.14. 1.5 mm2
Protection class IP20
Digital Inputs Potential free contacts (free from voltage)
Temperature sensors ECP-P30
Pressure sensors PT5N
Operating/surrounding temp. 0…+55°C
Output alarm relay SPDT contact 24V AC 1 Amp inductive load; 24V AC/DC 4 Amp resistive load
Activated/energized: During normal operation (no alarm condition)
Deactivated/de-energized: During alarm condition or power supply is OFF
Stepper motor output Coil: EXM-125/EXL-125 or EXN-125

Valves: EXM/EXL-… or EXN-…

Type of action 1B
Rated impulse voltage 0.5kV
Pollution Degree 2
Mounting: For standard DIN rail
Marking  
Dimensions (mm)

EMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (1)

Warning -Flammable refrigerants:
EXD-HP1/2 has a potential ignition source and does not comply with ATEX requirements. Installation only in non-explosive environments. For flammable refrigerants only use valves and accessories approved for it!

Safety instructions

  • Read operating instructions thoroughly. Failure to comply can result in device failure, system damage or personal injury.
  • It is intended for use by persons having the appropriate knowledge and skill.
  • Before installation or service disconnect all voltages from the system and device.
  • Do not operate the system before all cable connections are completed.
  • Do not apply voltage to the controller before the completion of wiring.
  • Entire electrical connections have to comply with local regulations.
  • Inputs are not isolated, potential free contacts need to be used.
  • Disposal: Electrical and electronic waste must NOT be disposed of with other commercial waste. Instead, it is the user’s responsibility to pass it to a designated collection point for the safe recycling of Waste Electrical and Electronic Equipment (WEEE directive 2019/19/EU). For further information, contact your local environmental recycling centre.

Electrical connection and wiring

  • Refer to the electrical wiring diagram for electrical connections.
  • Note: Keep controller and sensor wiring well separated from supply power cables. The minimum recommended distance is 30mm.
  • EXM-125, EXL-125 or EXN-125 coils are supplied with fixed cable and JST terminal block at the cable end. Cut the wires close to the terminal block. Remove the wire insulation approximately 7 mm at the end. It is recommended that the wires end to be equipped with core cable ends or metallic protective sleeve. When connecting the wires of EXM/EXL or EXN, consider the colour coding as follows:
    EXD Terminal EXM/L-125 wire color EXN-125 wire color
    EXD-HP1 6             BR

    7             BL

    8             OR

    9             YE

    10          WH

    Brown Blue Orange

    Yellow White

    Red Blue Orange

    Yellow White

    EXD-HP2 30          BR

    31          BL

    32           OR

    33          YE

    34          WH

    Brown Blue Orange Yellow White Red Blue Orange Yellow White
  • The digital input DI1 (EXD-HP1) and DI1/D12 (EXD-HP1/2) are the interfaces between EXD-HP1/2 and the upper-level system controller if the Modbus communication has not been used. The external digital shall be operated in the function system’s compressor/demand.
  • If the output relays are not utilized, the user must ensure appropriate safety precautions are in place to protect the system.
Operating condition Digital input status
Compressor starts/run closed (Start)
Compressor stops open (Stop)

Note:
Connecting any EXD-HP1/2 inputs to the supply voltage will permanently damage the EXD-HP1/2.

Wiring base board (EXD-HP 1/2):

EMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (2)

Note: 

  • The base board is for the function of superheat control or Economizer control.
  • Alarm relay, dry contact. The relay coil is not energized during alarm conditions or power off.
  • Hot gas discharge sensor input is mandatory only for the economizer control function.

Warning:
Use a class II category transformer for a 24VAC power supply. Do not ground the 24VAC lines. We recommend using individual transformers for the EXD-HP1/2 controller and for third-party controllers to avoid possible interference or grounding problems in the power supply.

Wiring: Upper board (EXD- HP 2):

EMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (3)

Note:

  • The upper board is only for the function of superheat control.
  • The upper board does not need to be wired if the circuit 2 is disabled.

Preparation for Start-up

  • Vacuum the entire refrigeration circuit.
  • Warning: Electrical Control Valves EXM/EXL or EXN are delivered in partially open position. Do not charge the system with refrigerant before the closure of the valve.
  • Apply supply voltage 24V to EXD-HP1/2 while the digital input (DI1/DI2) is OFF(open). The valve will be driven to a close position.
  • After the closure of the valve, start to charge the system with refrigerant.

Setup of parameters

(need to be checked/modified before start-up)

  • Make sure that digital input (DI1/DI2) is off (open). Turn the power supply ON.
  • Four main parameters Password (H5), type of function (1uE), refrigerant type (1u0/2u0) and pressure sensor type (1uP/2uP) can be set only when digital input DI1/DI2 is off (open) while the power supply is ON (24V). This feature is for added safety to prevent accidental damage to compressors and other system components.
  • Once the main parameters have been selected/saved the EXD-HP1/2 is ready for startup. All other parameters can be modified at any time during operation or standby if it is necessary.

Display/keypad unit

Display/keypad unit (LEDs and button functions)

EMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (4)

Procedure for parameter modification:
The parameters can be accessed via the 4-button keypad. The configuration parameters are protected by a numerical password. The default password is “12”. To select the parameter configuration:

  • Press theEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (5) button for more than 5 seconds, A flashing “0” is displayed
  • PressEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (6) until “12” is displayed; (password)
  • PressEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (7) to confirm the password
  • PressEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (6) orEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (8) to show the code of the parameter that has to be changed
  • PressEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (7) to display the selected parameter value
  • PressEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (6) orEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (8) to increase or decrease the value
  • PressEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (7) to temporarily confirm the new value and display its code
  • Repeat the procedure from the beginning “pressEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (6) orEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (8) to show…”

To exit and save the new settings:

  • PressEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (5) to confirm the new values and exit the parameters modification procedure.

To exit without modifying/saving any parameters:

  • Do not press any button for at least 60 seconds (TIME OUT).

Reset all parameters to factory setting:

  • Make sure that digital input (DI1/DI2) is Off (open).
  • PressEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (6) andEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (8) together for more than 5 seconds.
  • A flashing “0” is displayed.
  • PressEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (6) orEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (8) until the password is displayed (Factory setting = 12).
  • If the password was changed, select the new password.
  • PressEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (7) to confirm the password
  • Factory settings are applied

Note:
In standard mode, the actual superheat is shown on the display. In the case of liquid injection and economizer function this change to discharge temperature.

  • To display other data of circuit 1 of EXD-HP1/2 or 2 of EXD-HP2:
    • PressEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (7) andEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (8) together for 3 seconds to show data from Circuit 1
    • PressEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (7) andEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (6) together for 3 seconds to show data from Circuit 2
  • To display data of each circuit: PressEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (7) the button for 1 second until the index number according to the below table appears. Release theEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (7) button and the next variable data will appear. By repeating above procedure, variable data can be displayed in a sequence as Measured superheat (K) → Measured suction pressure (bar) → Valve position (%) → Measured suction gas temperature (°C) → Calculated saturated temperature (°C) → Measured discharge temperature (°C) (if economizer function is selected) →REPEATING….
Variable data Circuit 1 (EXD-HP1/2) Circuit 2 (EXD-HP2)
Default Superheat K 1               0 2               0
Suction pressure bar 1               1 2               1
Valve position % 1               2 2               2
Suction gas temp °C. 1               3 2               3
Saturation temp. °C 1               4 2               4
Discharge temp. °C 1               5

Note

  1. Discharge temp. is available only if the economizer function is selected.
  2. After 30 minutes, the display reverts to index 0.

Manual alarm reset/clearing functional alarms (except hardware errors):
PressEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (5) andEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (7) together for 5 seconds. When the clearing is done, a “CL” message appears for 2 seconds.

Manual mode operation

PressEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (5) andEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (8) together for 5 seconds to access to manual mode operation.

List of parameters in scrolling sequence by pressingEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (8) the button

Code Parameter description and choices Min Max Factory setting Field setting
1Ho Manual mode operation; circuit 1 0 1 0  
0 = off;      1 = on
1HP Valve opening (%) 0 100 0  
2Ho Manual mode operation; circuit 2 0 1 0  
0 = off       1 = on
2HP Valve opening (%) 0 100 0  

Note:
During manual operation, functional alarms such as low superheat are disabled. It is recommended to monitor the system operation when the controller is operated manually. Manual operation is intended for the service or temporary operation of the valve at a specific condition. After achieving the required operation, set the parameters 1Ho and 2Ho at 0 so the controller automatically operates the valve(s) according to its setpoint(s).

List Of Parameters

List of parameters in scrolling sequence by pressingEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (8) button:

Code Parameter description and choices Min Max Factory setting
H5 Password 1 1999 12
Adr ModBus address 1 127 1
br Modbus baudrate 0 1 1
PAr Modbus parity 0 1 0
-C2 Circuit 2 of EXD-HP2 enabled 0 1 0
0 = Enabled; 1 = Disabled  
-uC Units conversion 0 1 0
0 = °C, K, bar;                 1 = F, psig

This Parameter affects only the display. Internally the units are always SI-based.

HP- Display mode 0 2 1
0 = No display 1 = Circuit 1 2 = Circuit 2 (only EXD-HP2)
Parameters Circuit 1
1uE Function 0 1 1
0 = Superheat control

1 = Economizer control (Only for R410A/R407C/R32)

1u4 Superheat control mode 0 4 0
0 = Standard control coil heat exchanger 1 = Slow control coil heat exchanger

2 = fixed PID

3 = fast control plate heat exchanger (not for 1uE = 1) 4 = Standard plate heat exchanger (not for 1uE = 1)

1u0 Refrigerant 0 15 2
0 = R22         1 = R134a      2 = R410A     3 = R32         4 = R407C

5 = R290*      6 = R448A     7 = R449A     8 = R452A     9 = R454A*

10 = R454B* 11 = R454C* 12 = R513A  13 = R452B* 14 = R1234ze*

15 = R1234yf *

*) EXN not permitted

*) Warning -Flammable refrigerants: EXD-HP1/2 has a potential ignition source and does not comply with ATEX requirements. Installation only in non-explosive environments. For flammable refrigerants only use valves and accessories approved for it!

1uP Installed pressure sensor type 0 3 2
0 = PT5N-07…

2 = PT5N-30…

1 = PT5N-18…

3 = PT5N-10P-FLR

       
1uu Start valve opening (%) 10 100 20
1u9 Start opening duration (second) 1 30 5
1uL Low superheat alarm function 0 2 1
0 = disable (for flooded evaporator) 2 = enable manual reset 1 = enable auto reset  
1u5 Superheat set-point (K)

If 1uL = 1 or 2 (enabled auto or manual reset) If 1uL = 0 (disabled)

 

3

0.5

 

30

30

 

6

6

1u2 MOP function 0 1 1
0 = disable 1 = enable        
1u3 MOP set-point (°C) saturation temperature Factory setting according to selected refrigerant

(1u0). The default value can be changed

see MOP table
Code Parameter description and choices Min Max Factory setting
1P9 Low pressure alarm mode circuit 1 0 2 0
0 = disabled                                        1 = enabled auto reset 2 = enabled manual reset
1PA Low pressure alarm cut-out circuit 1 -0.8 17.7 0
1Pb Low pressure alarm delay circuit 1 5 199 5
1Pd Low-pressure alarm cut-in circuit 1 0.5 18 0.5
1P4 Freeze protection alarm function 0 2 0
0 = disabled,                    1 = enabled auto-reset, 2 = enabled manual reset
1P2 Freeze alarm cut-out circuit 1 -20 5 0
1P5 Freeze protection alarm delay, sec. 5 199 30
1P- Superheat control circuit 1 fixed PID (Kp factor) Display 1/10K 0.1 10 1.0
1i- Superheat control circuit 1 fixed PID (Ti factor) 1 350 100
1d- Superheat control circuit 1 fixed PID (Td factor) Display 1/10K 0.1 30 3.0
1EC Hot gas temperature sensor source 0 1 0
0 = ECP-P30

1 = Via Modbus input

1PE Economizer control circuit 1 fixed PID (Kp factor)      Display 1/10K 0.1 10 2.0
1iE The economizer control circuit 1 fixed PID (Ti factor) 1 350 100
1dE Economizer control circuit 1 fixed PID (Td factor)      Display 1/10K 0.1 30 1.0
1uH High superheat alarm mode circuit 1

0 = disabled                1 = enabled auto-reset

0 1 0
1uA High superheat alarm setpoint circuit 1 16 40 30
1ud High superheat alarm delay circuit 1 1 15 3
1E2 Positive correction of measured Hotgas temperature. 0 10 0
Parameters Circuit 2 (only EXD-HP2)
Code Parameter description and choices Min Max Factory setting
2u4 Superheat control mode 0 4 0
0 = Standard control coil heat exchanger 1 = Slow control coil heat exchanger

2 = fixed PID

3 = fast control plate heat exchanger 4 = Standard plate heat exchanger

2u0 System Refrigerant 0 5 2
0 = R22         1 = R134a      2 = R410A     3 = R32         4 = R407C

5 = R290*      6 = R448A     7 = R449A     8 = R452A     9 = R454A*

10 = R454B* 11 = R454C* 12 = R513A  13 = R452B* 14 = R1234ze*

15 = R1234yf *

*) EXN not permitted

*)     Warning -Flammable refrigerants: EXD-HP1/2 has a potential ignition source and does not comply with ATEX requirements. Installation only in non-explosive environments. For flammable refrigerants only use valves and accessories approved for it!

2uP Installed pressure sensor type (When DI2 is off) 0 3 1
0 = PT5N-07…          1 = PT5N-18…

2 = PT5N-30…          3 = PT5N-10P-FLR

2uu Start valve opening (%) 10 100 20
2u9 Start opening duration (second) 1 30 5
2uL Low superheat alarm function 0 2 1
0 = disable (for flooded evaporator)              1 = enable auto reset 2 = enable manual reset
2u5 Superheat set-point (K)

If 2uL = 1 or 2 (enabled auto or manual reset) If 2uL = 0 (disabled)

 

3

0.5

 

30

30

 

6

6

2u2 MOP function 0 1 1
0 = disable                          1 = enable
2u3 MOP set-point (°C) saturation temperature Factory setting according to selected refrigerant (2u0). The default value can be changed see MOP table
 

2P9

Low-pressure alarm mode circuit 2 0 2 0
0 = disabled                     1 = enabled auto reset 2 = enabled manual reset
2PA Low-pressure alarm cut-out (bar) circuit 2 -0.8 17.7 0
2Pb Low-pressure alarm delay (sec) circuit 2 5 199 5
2Pd Low-pressure alarm cut-in (bar) circuit 2 0.5 18 0.5
2P4 Freeze protection alarm function 0 2 0
0 = disable,                      1 = enable auto-reset, 2 = enable manual reset
Code Parameter description and choices Min Max Factory setting
2P2 Freeze alarm cut-out circuit 2 -20 5 0
2P5 Freeze protection alarm delay, sec. 5 199 30
2P- Superheat control circuit 2

(Kp factor), fixed PID Display 1/10K

0.1 10 1.0
2i- Superheat control circuit 2 (Ti factor), fixed PID 1 350 100
2d- Superheat control circuit 2 (Td factor), fixed PID       – Display 1/10K 0.1 30 3.0
2uH High superheat alarm mode circuit 2 0 1 0
0 = disabled                1 = enabled auto-reset
2uA High superheat alarm setpoint (K) circuit 2 16 40 30
2ud High superheat alarm delay (Min) circuit 2 1 15 3
Selection for both circuits and discharge temperature control
Code Parameter description and choices Min Max Factory setting
Et Valve type 0 1 0
0 = EXM / EXL         1 = EXN
Note: EXD-HP2 can drive two similar valves i.e. both valves must be either EXM/EXL or EXN.
1E3 Discharge Temperature Setpoint Start Setpoint 70 140 85
1E4 Discharge Temperature Control band 2 25 20
1E5 Discharge Temperature limit 100 150 120

MOP table (°C)

Refrigerant Min. Max. Factory setting Refrigerant Min. Max. Factory setting
R22 -40 +50 +15 R452A -45 +66 +15
R134a -40 +66 +15 R454A -57 +66 +10
R410A -40 +45 +15 R454B -40 +45 +18
R32 -40 +30 +15 R454C -66 +48 +17
R407C -40 +48/ +15 R513A -57 +66 +13
R290 -40 +50 +15 R452B -45 +66 +25
R448A -57 +66 +12 R1234ze -57 +66 +24
R449A -57 +66 +12 R1234yf -52 +66 +15

Control (valve) start-up behavior

(Parameter 1uu/2uu and 1u9/2u9)

EMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (9)

Upload/download Key: Function
For serial production of systems/units, the upload/download key allows the transmission of configured parameters among a range of identical systems.

Uploading procedure:
(storing configured parameters in key)

  • Insert the key while the first (reference) controller is ON and pressEMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (6) the button; the “uPL” message appears followed by the “End” message for 5 seconds.
  • Note: If the “Err” message is displayed for failed programming, repeat the above procedure.

Downloading procedure:
(configured parameters from key to other controllers)

  • Turn off the power to the new controller
  • Insert a loaded Key (with stored data from the reference controller) into the new controller and turn on the power supply.
  • The stored parameters of the key will be downloaded automatically into the new controller memory; The “doL” message appears followed by an “End” message for 5 seconds.
  • The new controller with the new loaded parameters setting will start to operate after the “End” message disappears.
  • Remove the key.
  • Note: If the “Err” message is displayed for failed programming, repeat the above procedure.

EMERSON-EXD-HP1-2-Controller-with-ModBus-Communication-Capability-fig- (10)

Error/Alarm handling

Alarm code Description Related parameter Alarm relay Valve What to do? Requires manual reset after resolving alarm
1E0/2E0 Pressure sensor 1/2 error Triggered Fully close Check the wiring connection and measure the signal 4 to 20 mA No
1E1/2E0 Temperature sensor 1/2 error Triggered Fully close Check the wiring connection and measure the resistance of the sensor No
1Ed Discharge hot gas temperature sensor 3 error Triggered Operating Check the wiring connection and measure the resistance of the sensor No
1Π-/2Π- EXM/EXL or EXN

electrical connection error

Triggered Check the wiring connection and measure the resistance of the winding No
1Ad Discharge hot gas temperature above the limit   Triggered Operating Check valve opening/ check liquid flow for flash gas free/check discharge hot gas temperature sensor No
1AF/2AF  

Freeze protection

1P4/2P4: 1 Triggered Fully close Check the system for causes of low pressure such as insufficient load on the evaporator No
1AF/2AF

blinking

1P4/2P4: 2 Triggered Fully close Yes
1AL/2AL Low superheat (<0,5K) 1uL/2uL: 1 Triggered Fully close Check the wiring connection and operation of the valve No
1AL/2AL blinking 1uL/2uL: 2 Triggered Fully close Yes
1AH/2AH High superheat 1uH/2uH: 1 Triggered Operating Check the system No
1AP/2AP  

Low pressure

1P9/2P9: 1 Triggered Operating Check the system for causes of low pressure such as refrigerant loss No
1AP/2AP blinking 1P9/2P9: 2 Triggered Operating Yes
Err Failed uploading/downloading Repeat the procedure for uploading/downloading No

Note:
When multiple alarms occur, the highest priority alarm is displayed until being cleared, then the next highest alarm is displayed until all alarms are cleared. Only then will parameters be shown again.

Emerson Climate Technologies GmbH

Documents / Resources

EMERSON EXD-HP1 2 Controller with ModBus Communication Capability [pdf] Instruction Manual
EXD-HP1 2 Controller with ModBus Communication Capability, EXD-HP1 2, Controller with ModBus Communication Capability, ModBus Communication Capability, Communication Capability

References

Leave a comment

Your email address will not be published. Required fields are marked *