Contents
hide
ELPRO 415U-2-CX Long Range Wireless Ethernet Gateway
Product Usage Instructions
- When selecting an antenna, consider radio proximity.
- Follow Figure 1 as a guide for installing the antenna and attaching it to the 415U-2-Cx.
- Connect the Coax to the building earth by IEC60728-11:2005 standards.
- Ensure proper grounding by following the guidelines provided.
- Attach the antenna to the mast securely.
- Create a stress relief loop to prevent damage to the coaxial cable.
- Install a surge arrestor for protection (recommended).
- Use weatherproof connections (recommended: 3MTM 23 self-bonding tape) for durability.
- Maintain a minimum of one wavelength distance between components.
EXPLOSION HAZARD
WARNING – EXPLOSION HAZARD
- Do not disconnect the device while the circuit is live unless the area is known to be non-hazardous.
NOTE
- All connections must be SELV <50 Vac and <60Vdc.
Models
- 415U-2-C1 – 148 to 174MHz
- 415U-2-C3 – 360 to 400MHz
- 415U-2-C4 – 400 to 480MHz
- 415U-2-C5 – 470 to 520MHz
- 415U-2-C9 – 928 to 960MHz
Antenna installation
- When selecting an antenna, consider radio proximity.
- Use Figure 1 as a guide for installing an antenna and attaching it to the 415U-2-Cx.
Connecting to the module for configuration
- Download and install the configuration utility software, available from the Elpro Technolgies website. www.elprotech.com
- Connect to the PC using the supplied USB cable.
- Connect to the device by selecting the USB connection and using the IP address 192.168.111.1 or 1.1.1.1 for older firmware (pre V2.28)
- The PC will automatically be assigned an IP address from the module via DHCP. A new network adaptor will be created using IP address 192.168.1.2 (or 1.1.1.2)
- Username: user
- Password: user
The following illistrations show the port connections on the 415U-2-Cx.
Power Supply Wiring
- The ground (GND) and “SUP –“ terminals are connected internally to the ground (Earth) terminal.
- Connect the screw terminal on the end plate to ground (Earth) for surge protection.
Expansion I/O Power and RS485 serial connection
- An on-board RS‑485 terminating resistor provides line termination for long runs.
- Only enable the terminating resistor on the last device connected on the RS‑485 cable.
INSTALL GUIDE
Configuration Switches
- Use the DIP switches in the side access panel to select analog input voltage or current, and to enable the default configuration.
Input and Output connections
- The digital input/output channels can be wired as inputs or outputs.
Digital Input
Digital Output
AI1, AI2 – Differential 4-20mA inputs
AI3, AI4 – Single Ended 4-20mA inputs
AO1 & AO2 – Analog Output (0-20mA)
AI3 & AI4 – Single-ended voltage input
HOW TO ORDER
- Simply send us an email at sales@elprotech.com, contact your local distributor, or phone +61 7 3352 8600
CONTACT
Australia
- ELPRO Technologies
- 29 Lathe Street
- Virginia QLD 4014
- T +61 7 3352 8600
- E sales@elprotech.com
- W elprotech.com
USA
- ELPRO Technologies Inc
- 2028 East Ben White Boulevard
- #240-5656 Austin, TX 78741-6931
- T +1 855 443 5776
- E sales@elprotech.com
- W elprotech.com
FAQ
- Q: How do I ensure proper grounding for the antenna installation?
- A: To ensure proper grounding, follow the guidelines provided in sections 6.2 g) and 6.2 i) of IEC60728-11:2005 when connecting Coax to the building earth.
Documents / Resources
![]() |
ELPRO 415U-2-CX Long Range Wireless Ethernet Gateway [pdf] Installation Guide 415U-2-CX Long Range Wireless Ethernet Gateway, 415U-2-CX, Long Range Wireless Ethernet Gateway, Wireless Ethernet Gateway, Ethernet Gateway |