elo - logo925U-2-XXX
INSTALLATION GUIDEelo 925U-2-XXX Wireless Mesh Networking-

STATUTORY REQUIRMENTS

FCC: This device complies with Part 15.247 of the FCC Rules.
Operation is subject to the following two conditions:

  • This device may not cause harmful interference.
  • This device must accept any interference received, including interference that may cause undesired operation.

FCC: Unlicensed operation limits the radio power. High gain aerials may only be used to compensate for cable losses.

WARNING – EXPLOSION HAZARD

Do not disconnect the device while the circuit is live unless the area is known to be non-hazardous.

NOTE
The 925U-2 module ships from the factory as a bridged meshing radio.
All connections must be SELV <50 Vac and <60Vdc
If communication with the older legacy 915U-2’s is required, radio operating mode can be changed with a firmware downgrade, which is available on the USB Stick in the box. Please follow the “Downgrade procedure” document which is also on the USB.

Models
9250-2-869-869.5 το 969.9MHz – 869 MHz ISM band (Europe)
925U-2-900-902 to 928MHz-900Mhz FHSS band

Antenna installation
When selecting an antenna, consider radio proximity.
Use Figure 1 as a guide for installing an antenna and attaching it to the 925U-2-XXX.

elo 925U-2-XXX Wireless Mesh Networking- antenna

Connecting to the module for configuration

  • Download and install configuration utility software, available from the Elpro Technolgies website. www.elprotech.com
  • Connect to PC using supplied USB cable.
  • Connect to the device by selecting USB connection and using the 1P address 192.168.1111 or 1111 for older firmware (pre V2.28)
  • The PC will automatically be assigned an IP address from the module via DHCP. A new network adaptor will be created using IP address 192.168.1.2 (or 111.2)
  • Username: user
  • Password: user

The following illistrations show the port connections on the 925U-2-XXX.

elo 925U-2-XXX Wireless Mesh Networking- antenna1

Power Supply Wiring
The ground (GND) and “SUP-terminals are connected internally to the ground (Earth) terminal.
Connect the screw terminal on the end plate to ground (Earth) for surge protection.

elo 925U-2-XXX Wireless Mesh Networking- wiring

Expansion I/O Power and RS485 serial connection
An on-board RS-485 terminating resistor provides line termination for long runs.
Only enable terminating resistor on the last device connected on the RS-485 cable.

elo 925U-2-XXX Wireless Mesh Networking- connection

925U-2-XXX
INSTALL GUIDE
Configuration Switches
Use the DIP switches in the side access panel to select analog input voltage or current, and to enable default configuration

elo 925U-2-XXX Wireless Mesh Networking- switches

DIP Description                OFF

ON

1 Al3 Current / Voltage Voltage Current
2 Al3 Current / Voltage Voltage Current
3 Al4 Current / Voltage Voltage Current
4 Al4 Current / Voltage Voltage Current
5 Unused Off On
6 Default configuration Normal Enabled

elo 925U-2-XXX Wireless Mesh Networking- switches1

Input and Output connections
The digital input/output channels can be wired as inputs or outputs.

elo 925U-2-XXX Wireless Mesh Networking- digital input

elo 925U-2-XXX Wireless Mesh Networking- digital input1

CONTACT

Australia
ELPRO Technologies 29 Lathe Street Virginia QLD 4014
T +61 7 3352 8600
E sales@elprotech.com
W elprotech.com
USA
ELPRO Technologies Inc 2028 East Ben White Boulevard #240-5656 Austin, TX 78741-6931
T +1 855 443 5776
E sales@elprotech.com
W elprotech.com

HOW TO ORDER

Simply send us an email at sales@elprotech.com, contact your local distributor, or phone +61 7 3352 8600
An envirada group company

Documents / Resources

elo 925U-2-XXX Wireless Mesh Networking [pdf] Installation Guide
925U-2-XXX Wireless Mesh Networking, 925U-2-XXX, Wireless Mesh Networking, Mesh Networking

References

Leave a comment

Your email address will not be published. Required fields are marked *