925U-2-XXX
INSTALLATION GUIDE
STATUTORY REQUIRMENTS
FCC: This device complies with Part 15.247 of the FCC Rules.
Operation is subject to the following two conditions:
- This device may not cause harmful interference.
- This device must accept any interference received, including interference that may cause undesired operation.
FCC: Unlicensed operation limits the radio power. High gain aerials may only be used to compensate for cable losses.
WARNING – EXPLOSION HAZARD
Do not disconnect the device while the circuit is live unless the area is known to be non-hazardous.
NOTE
The 925U-2 module ships from the factory as a bridged meshing radio.
All connections must be SELV <50 Vac and <60Vdc
If communication with the older legacy 915U-2’s is required, radio operating mode can be changed with a firmware downgrade, which is available on the USB Stick in the box. Please follow the “Downgrade procedure” document which is also on the USB.
Models
9250-2-869-869.5 το 969.9MHz – 869 MHz ISM band (Europe)
925U-2-900-902 to 928MHz-900Mhz FHSS band
Antenna installation
When selecting an antenna, consider radio proximity.
Use Figure 1 as a guide for installing an antenna and attaching it to the 925U-2-XXX.
Connecting to the module for configuration
- Download and install configuration utility software, available from the Elpro Technolgies website. www.elprotech.com
- Connect to PC using supplied USB cable.
- Connect to the device by selecting USB connection and using the 1P address 192.168.1111 or 1111 for older firmware (pre V2.28)
- The PC will automatically be assigned an IP address from the module via DHCP. A new network adaptor will be created using IP address 192.168.1.2 (or 111.2)
- Username: user
- Password: user
The following illistrations show the port connections on the 925U-2-XXX.
Power Supply Wiring
The ground (GND) and “SUP-terminals are connected internally to the ground (Earth) terminal.
Connect the screw terminal on the end plate to ground (Earth) for surge protection.
Expansion I/O Power and RS485 serial connection
An on-board RS-485 terminating resistor provides line termination for long runs.
Only enable terminating resistor on the last device connected on the RS-485 cable.
925U-2-XXX
INSTALL GUIDE
Configuration Switches
Use the DIP switches in the side access panel to select analog input voltage or current, and to enable default configuration
DIP | Description | OFF |
ON |
1 | Al3 Current / Voltage | Voltage | Current |
2 | Al3 Current / Voltage | Voltage | Current |
3 | Al4 Current / Voltage | Voltage | Current |
4 | Al4 Current / Voltage | Voltage | Current |
5 | Unused | Off | On |
6 | Default configuration | Normal | Enabled |
Input and Output connections
The digital input/output channels can be wired as inputs or outputs.
CONTACT
Australia
ELPRO Technologies 29 Lathe Street Virginia QLD 4014
T +61 7 3352 8600
E sales@elprotech.com
W elprotech.com
USA
ELPRO Technologies Inc 2028 East Ben White Boulevard #240-5656 Austin, TX 78741-6931
T +1 855 443 5776
E sales@elprotech.com
W elprotech.com
HOW TO ORDER
Simply send us an email at sales@elprotech.com, contact your local distributor, or phone +61 7 3352 8600
An envirada group company
Documents / Resources
![]() |
elo 925U-2-XXX Wireless Mesh Networking [pdf] Installation Guide 925U-2-XXX Wireless Mesh Networking, 925U-2-XXX, Wireless Mesh Networking, Mesh Networking |