elausys logo

User Manual

Doc.Ref : INV-KNX-FR-UM

KNX Gateway for Fronius Inverters

Revision :          2.00

ELAUSYS
INV-KNX

KNX Gateway for Fronius Inverters

User Manual

elausys INV-KNX Gateway for Fronius Inverters

1. INTRODUCTION

The KNX gateway for Fronius inverters provides a simple solution to transfer all relevant data from the inverters to KNX.

It allows integrators to take advantage of a fully integrated solar panel inverter, the data can be used to optimize energy consumption, monitoring, trending or to trigger specific action in the KNX installation.

Main features:

  • KNX Interface for Fronius inverters serie
  • Monitoring of Energy, Power, current, voltage, frequency, temperature, …
  • Connected to the inverter over Ethernet
  • Galvanic insulation from the KNX bus
  • Configurable refresh rate of inverter data
  • DIN rail mounted
  • Auxiliary power supply 12-30VDC
  • KNX logic module including logic gates, sequences, triggers, math operation and weekly calendar events.
2. OVERVIEW
2.1 USAGE & LIMITATION

This gateway is intended to be used with an Fronius inverter compatible with the SMA SunSpec modbus interface definition. The inverter is connected to the ethernet network on the same router as the KNX gateway.

All Fronius inverters with SetApp configuration are SunSpec-supported. Fronius inverters with the LCD that have Firmware version 3.xxxx and above only are SunSpec-supported.

2.1 SOFTWARE

The KNX Interface is configured using the ETS tool, the free ETS Demo version can be downloaded from the website of KNX Association. The free version allows to configure up to 5 KNX modules in a project, the KNX gateway is only one module, all devices can be configured using this version.

2.2 CONNECTION DIAGRAM

The KNX bus is connected on the top side of the gateway.
An external power supply 12-30VDC is required and connected on the bottom side of the module, beside the RJ45 connector for the ethernet cable.

elausys INV-KNX Gateway for Fronius Inverters - a1

  1. 12-30VDC
  2. RJ45 Ethernet
2.3 FRONT PANEL

elausys INV-KNX Gateway for Fronius Inverters - a2

The front panel is equipped with two green status LED:

Network: Physical connection to the ethernet network is established.
Connected: Communication with the inverter is established.

Button “P” : KNX Programming mode button
Red LED : KNX Programming status LED

3. PARAMETERS

The KNX interface parameters are defined in the “parameters” tab of the device, in the ETS project.

3.1 INVERTER SETTINGS

The following parameters are defined in the inverter settings section of the parameters:

PARAMETER

VALUES

DESCRIPTION

AC Network
  • Single phase (default) 
  • Tri-Phase
Type of AC network
Number of PV Circuits
  • 1 … 4
NOT APPLICABLE for this type of inverters
Inverter model
  • 0…255
3 = Fronius Inverters
Refresh rate (min)
  • 0…255
Cyclic rate of data polling from the inverter.
Battery 1
  • Not Used / Used
Display group objects to monitor the status of battery 1
Battery 2
  • Not Used / Used
Display group objects to monitor the status of battery 2 (NOT USED for this inverter) 
Powermeter
  • Not Used / Used
Display group objects to monitor the powermeter value (NOT USED for this inverter) 
Timezone
  • UTC-11… UTC+14
Timezone where the device is installed. It is used for logic functions based on the weekly calendar.
Daylight saving time
  • Not Used / Used
Set if daylight saving is used where the device is installed. It is used for logic functions based on the weekly calendar.
Device Options
  • Text string
Device options are not available on this device.
4. LOGIC FUNCTIONS

The KNX logic module is a virtual extension module that is part of the ETS application on the inverters gateways. Each logic module includes 8 logic functions including logic gates, sequences, triggers, math operation and weekly calendar events.

  • Up to 64 logic functions using extension modules
  • Logic Gate with 8 inputs, configurable output delay and inversion
  • Sequence with 4 steps, configurable outputs delays and datatypes
  • Trigger with inputs logic, delays and weekly calendar events
  • Math operations with configurable objects type and delays

Refer to the KNX Logic Module manual for more details on each function.

5. COMMUNICATION OBJECTS
5.1 GENERAL

General communication objects of the device.

GO

NAME DESCRIPTION

1

Module status Sends 0 when the module is operating normally, sends an error code when applicable.

2

Firmware version Returns the firmware version of the device when the object is read.
5.2 INVERTERS OBJECTS

GO

NAME DESCRIPTION

3

AC Current AC Total Current value

4

AC Current A AC Current phase A

5

AC Current B AC Current phase B

6

AC Current C AC Current phase C

7

AC Voltage AC Total Voltage (NOT USED)

8

AC Voltage AB AC Voltage phase AB

9

AC Voltage BC AC Voltage phase BC

10

AC Voltage CA AC Voltage phase CA

11

AC Voltage AN AC Voltage phase AN

12

AC Voltage BN AC Voltage phase BN

13

AC Voltage CN AC Voltage phase CN

14

DC Current DC Total Current value (NOT USED)

15

DC Voltage DC Total Voltage (NOT USED)

16

PV1 Voltage PV1 Voltage

17

PV1 Current PV1 Current

18

PV2 Voltage PV2 Voltage

19

PV2 Current PV2 Current

20

PV3 Voltage PV3 Voltage (NOT USED)

21

PV3 Current PV3 Current (NOT USED)

22

PV4 Voltage PV4 Voltage (NOT USED)

23

PV4 Current PV4 Current (NOT USED)

24

AC Power AC Power

25

DC Power DC Power (NOT USED)

26

AC Frequency AC Frequency

27

AC VA AC Apparent power

28

AC VAR AC Reactive power

29

AC PF Power factor

30

AC Energy Total AC Energy

31

Efficiency Inverter efficiency (NOT USED)

32

Insulation Insulation resistance (NOT USED)

33

Temperature Cabinet temperature (NOT USED)

40

Daily Energy Yield (NOT USED)

41

Battery 1 Running Status 0: OFF
1: EMPTY
6: DISCHAGING
7: CHARGING
9: FULL
10: HOLDING
11: TESTING

42

Battery 1 power (NOT USED)

43

Battery 1 SOC Battery’s state of capacity

44

Battery 1 current day charge (NOT USED)

45

Battery 1 current day discharge (NOT USED)

46

Battery 1 total charge (NOT USED)

47

Battery 1 total discharge (NOT USED)

48

Battery 2 Running Status (NOT USED)

49

Battery 2 power (NOT USED)

50

Battery 2 SOC (NOT USED)

51

Battery 2 current day charge (NOT USED)

52

Battery 2 current day discharge (NOT USED)

53

Battery 2 total charge (NOT USED)

54

Battery 2 total discharge (NOT USED)

55

Powermeter (NOT USED)
5.3 GROUP OBJECT LIST

GO

Name Function Size Flags Type ID Type Name Description

1

Module status Status code 1 byte C R – T – 20.011 DPT_ErrorClass_System Device status

2

Firmware version Text String 14 bytes C R – T – 16.000 Character string Firmware version of the device

3

AC Current Actual value 4 bytes C R – T – 14.019 Electric current (A) AC Total Current value 

4

AC Current A Actual value 4 bytes C R – T – 14.019 Electric current (A) AC Current phase A

5

AC Current B Actual value 4 bytes C R – T – 14.019 Electric current (A) AC Current phase B

6

AC current C Actual value 4 bytes C R – T – 14.019 Electric current (A) AC Current phase C

7

AC Voltage Actual value 4 bytes C R – T – 14.027 Electric potential (V)  AC Total Voltage

8

AC Voltage AB Actual value 4 bytes C R – T – 14.027 Electric potential (V)  AC Voltage Phase AB value

9

AC Voltage BC Actual value 4 bytes C R – T – 14.027 Electric potential (V)  AC Voltage Phase BC value

10

AC Voltage CA Actual value 4 bytes C R – T – 14.027 Electric potential (V)  AC Voltage Phase CA value

11

AC Voltage AN Actual value 4 bytes C R – T – 14.027 Electric potential (V)  AC Voltage Phase AN value

12

AC Voltage BN Actual value 4 bytes C R – T – 14.027 Electric potential (V)  AC Voltage Phase BN value

13

AC Voltage CN Actual value 4 bytes C R – T – 14.027 Electric potential (V)  AC Voltage Phase CN value

14

DC Current Actual value 4 bytes C R – T – 14.019 Electric current (A) DC Total Current value

15

DC Voltage Actual value 4 bytes C R – T – 14.027 Electric potential (V)  DC Total Voltage

16

PV1 Voltage Actual value 4 bytes C R – T – 14.027 Electric potential (V)  PV1 Voltage

17

PV1 Current Actual value 4 bytes C R – T – 14.019 Electric current (A) PV1 Current

18

PV2 Voltage Actual value 4 bytes C R – T – 14.027 Electric potential (V)  PV2 Voltage

19

PV2 Current Actual value 4 bytes C R – T – 14.019 Electric current (A) PV2 Current

20

PV3 Voltage Actual value 4 bytes C R – T – 14.027 Electric potential (V)  PV3 Voltage

21

PV3 Current Actual value 4 bytes C R – T – 14.019 Electric current (A) PV3 Current

22

PV4 Voltage Actual value 4 bytes C R – T – 14.027 Electric potential (V) PV4 Voltage

23

PV4 Current Actual value 4 bytes C R – T – 14.019 Electric current (A) PV4 Current

24

AC Power Actual value 4 bytes C R – T – 14.056 Power (W)  AC Power

25

DC Power Actual value 4 bytes C R – T – 14.056 Power (W)  DC Power

26

AC Frequency Actual value 4 bytes C R – T – 14.033 Frequency (Hz) AC Frequency

27

AC VA Actual value 4 bytes C R – T – 14.056 Power (W)  AC Apparent power

28

AC VAR Actual value 4 bytes C R – T – 14.056 Power (W)  AC Reactive power

29

AC PF Actual value 4 bytes C R – T – 14.057 Power factor (cos phi) Power factor

30

AC Energy Actual value 4 bytes C R – T – 13.013 Active energy (kWh)  Total AC Energy

31

Efficiency Actual value 2 bytes C R – T – 8.010 Percentage (%) Inverter efficiency

32

Insulation Actual value 4 bytes C R – T – 14.056 Resistance (Ohm)  Insulation resistance

33

Temperature Actual value 2 bytes C R – T – 9.001 Temperature (°C) Cabinet temperature

40

Daily Energy Yield Actual value 4 bytes C R – T – 13.013 Energy (kWh)

41

Battery 1 Running Status Actual value 2 bytes C R – T – Status code

42

Battery 1 power Actual value 4 bytes C R – T – 14.056 Power (W)

43

Battery 1 SOC Actual value 1 byte C R – T – 5.001 Percentage (%) State of charge (%)

44

Battery 1 current day charge Actual value 4 bytes C R – T – 13.013 Energy (kWh)

45

Battery 1 current day discharge Actual value 4 bytes C R – T – 13.013 Energy (kWh)

46

Battery 1 total charge Actual value 4 bytes C R – T – 13.013 Energy (kWh)

47

Battery 1 total discharge Actual value 4 bytes C R – T – 13.013 Energy (kWh)

48

Battery 2 Running Status Actual value 2 bytes C R – T – Status code

49

Battery 2 power Actual value 4 bytes C R – T – 14.056 Power (W)

50

Battery 2 SOC Actual value 1 byte C R – T – 5.001 Percentage (%) State of charge (%)

51

Battery 2 current day charge Actual value 4 bytes C R – T – 13.013 Energy (kWh)

52

Battery 2 current day discharge Actual value 4 bytes C R – T – 13.013 Energy (kWh)

53

Battery 2 total charge Actual value 4 bytes C R – T – 13.013 Energy (kWh)

54

Battery 2 total discharge Actual value 4 bytes C R – T – 13.013 Energy (kWh)

55

Powermeter Actual value 4 bytes C R – T – 14.056 Power (W)
6. CONFIGURATION
6.1 NETWORK CONFIGURATION

By default, the IP address of the KNX gateway is set to 192.168.1.51
Using a laptop connected to the gateway, open a web browser and navigate to the IP address of the gateway.

elausys INV-KNX Gateway for Fronius Inverters - b1

Set a fixed IP address of your choice for the KNX gateway and configure the modbus TCP settings as below:

  • Mode : Connect
  • IP : IP Address of the inverter
  • Server Port : 502
  • Uni Id : 1
6.2 KNX PHYSICAL DEVICE

ELAUSYS devices are configured using the ETS tool. You should first download and install the free version of ETS tool before you continue.

The INV-KNX Interface must be assigned a physical address on the KNX network. Assign a free address to the module, in our example we choose 1.1.2.

elausys INV-KNX Gateway for Fronius Inverters - b2

6.3 ETS PARAMETERS

Once a KNX physical address is set, open the parameter tab to configure the interface.

elausys INV-KNX Gateway for Fronius Inverters - b3

Select the type of AC network (single phase or tri-phase).

Set the inverter model to 3 for Fronius inverters.

Choose the refresh rate (min) for the complete set of data.

Select if battery 1 is available on the inverter.

Device options should remain empty.

6.4 ETS GROUP OBJECTS

A group address (GA) must be assigned to each group object (GO) needed by the application.
Open the Group Objects tab of the device and assign a GA to the objects as needed.

elausys INV-KNX Gateway for Fronius Inverters - b4

When GO and parameters are all configured, download the KNX Interface application to the device. The first download requires to press the programming button on the device to set the device in KNX programming mode then perform a full download.

6.5 INVERTER CONFIGURATION

MODBUS over TCP Support
MODBUS TCP function- is disabled by default.

  • Install Fronius Datamanager (=> see the Fronius Datamanager operating instructions.)
  • Open Internet browser
  • Enter the following in the address field of the Internet browser:
    – the IP address of the Fronius Datamanager (can be accessed via System Information)
    – or host name and domain name of the Fronius Datamanager.
    – The web interface’s start page is displayed.
  • Select the “Settings” section (1).
  • Open the “Modbus” section (2).

elausys INV-KNX Gateway for Fronius Inverters - b5

  • Select data export : tcp
  • Set modbus port : 502
  • Set Sunspec model type: int+SF

elausys INV-KNX Gateway for Fronius Inverters - b6

7. FIRMWARE VERSION

This user manual and related ETS application is valid for firmware versions V2.2.0.0 and above.
The firmware version can be read from the gateway webpage using a web browser.
It is displayed on the top right of the page.

elausys INV-KNX Gateway for Fronius Inverters - c1

In case an updated firmware would be available, the device can be updated from the FW Update page, the binary file should be selected before pressing the Update button.

8. DATASHEET

TECHNICAL DATA

VALUE

Auxiliary power supply terminal

Screw terminal 12-30VDC / GND

Power consumption KNX bus typ.

< 16 mA @ 29VDC

Operating temperature

+5°C to + 45°C

Enclosure Dimensions (Space Units)

2 SU

Mounting

DIN RAIL

KNX terminal

Pluggable micro terminal, Red/Black, 4 pole PUSH WIRE for solid conductor wire 0.6-0.8 mm²

KNX bus voltage

29 VDC

© ELAUSYS SPRL

This document cannot be reproduced fully or partially without written authorization

Documents / Resources

elausys INV-KNX Gateway for Fronius Inverters [pdf] User Manual
INV-KNX Gateway for Fronius Inverters, INV-KNX, Gateway for Fronius Inverters, Fronius Inverters, Inverters

References

Leave a comment

Your email address will not be published. Required fields are marked *