U37 FIREPLACE
Installation Reference Guide
REFER TO OWNER'S MANUAL FOR SPECIFIC INSTALLATION REQUIREMENTS AND ADDITIONAL PRODUCT INSTRUCTIONS
Minimum Framing Dimensions

Note: When framing the unit, care must be taken to consider the final floor thickness, the bottom of the fireplace must sit flush with the finished floor to ensure proper fit of the surround components
Note: Vent size: 8 x 11" Rigid Co-Axial

1" 25mm
Clearance from framing studs to venting

Minimum Depth (2" facing mat.) Maximum Depth (½" facing mat.)
Width

22 3/4" 578 mm 24 1/4" 616 mm 46 1/4 " 1175 mm

Header Height 44 1/2" 1130mm Enclosure Ceiling 79 ½" 2020 mm

44 / "
1283 mm
46 / "
1359 mm
79 ½"
2172 mm
Refer to Table on left

Clearance to Combustibles

A - Finishing edge to side wall B - Minimum clearance to enclosure ceiling C - Minimum clearance to mantel height D - Front of door to edge of floor protection E - Minimum alcove width

3 1/2" 79 ½" 38 5/8"
0" 44 3/4"

89 mm 2020 mm 981 mm
0 mm 1137 mm

 - Additional ceiling height required if using 5x8 co-axial venting, refer to installation manual.

A
E D

B C

Non-Combustible Board Placement

Wood Framing Header Non Combustible Board
Drywall Sidewall
3½"

COMBUSTIBLE NON COMBUSTIBLE
32 5/8" 37 5/8"

Fireplace Dimensions
12"

Minimum Venting Requirements
This appliance uses a 11" (280 mm) exhaust / 8" (203mm) air intake vent pipe system. For safe and proper operation of the appliance follow the venting instructions exactly. Deviation from the minimum vertical length can create difficulty in burner start-up and sooting. Allow several minutes for the flame to stabalize after ignition under extreme vent configurations. It is recommended for vent lengths that pass through unheated spaces (garages, attics, crawl spaces) be insulated to minimize condensation.
NOTE: At least 3" (76mm) of clearance is required above vent when passing through an exterior wall when horizontally terminating.

22¾" - 24¼" [578 - 629mm]
4 3/4" [121mm] First Elbow Only

30" Minimum [762mm]

12" NonCombustible
Zone

79½ [2007mm]

 69¼" 1759mm
Use one 24" vent section to achieve minimum rise in order for this dimension to work.

 Additional ceiling and thimble height required if using 5x8 co-axial venting, refer to installation manual

MANTEL HEIGHT

Mantel Projections

Mantel graph dimensions are measured from the bottom of the fireplace, if you wish to reference the mantel height from the tiling edge subtract 32 5/8 inches (829mm) from the mantel height depicted on the graph. If you plan to install a TV above your fireplace refer to the appropriate section of the owner's manual for available options. It is acceptable to install a combustible mantel over top of the non-combustible board. If using the Cool Surface System, refer to the graph on the following page to determine the required mantel height.
48

46

12" MANTEL

44
8" MANTEL 42

40

4" MANTEL

38

2

4

6

8

10

12

14

MANTEL DEPTH

Mantel Projections with Cool Surface System
Activating the Cool Surface System decreases the required height of the mantel. Use the graph on the right to determine the mantel height when using the Cool Surface System. Mantel graph dimensions are measured from the bottom of the fireplace, if you wish to reference the mantel height from the tiling edge subtract 32 5/8 inches (829mm) from the mantel height depicted on the graph. If you plan to install a TV above your fireplace refer to the appropriate section of the owner's manual for available options. It is acceptable to install a combustible mantel over top of the noncombustible board.

MANTEL HEIGHT

40

38

12" MANTEL 36

8" MANTEL 34

4" MANTEL

32

2

4

6

8

10

12

14

MANTEL DEPTH

Cool Surface System Framing
Framing Option 1: Front Discharge (flush wall installations)
Construct the framing in a way that provides a minimum 42 inch (1067mm) by 3 inch (76mm) gap at the top of the facing wall. It is essential that these dimensions are respected and not to deviate away from them when using combustible materials inside the chase (see Figure 1).
Note: If you wish to construct the CSS air discharge part way up a tall wall then it is essential to build a false ceiling inside the chase at the desired height to direct the rising heat out of the gap.

42" 1067mm Minimum

2" 51mm Minimum

CSS Air Discharge

Non-Combustible board NOT

mandatory for CSS Install

37

5 8

"

1133mm

12 " 305mm

5" 127mm Maximum

72

1 2

"

1842mm

Minimum

Figure 1: Framing Option 1
Framing Option 2: Open Chase (built-out installations)
This could be considered the most discreet option when considering the CSS. The chase must be constructed in a way that stops short of the ceiling, leaving it totally vented above. Minimum framing dimensions must be followed when constructing this option and not to deviated from them when using combustible materials. Consider Optional 3: Valance to work in conjunction with this option.

6" 152mm Minimum

2" 51mm Minimum

Wall Mounted Object

4

3 4

"

121mm

Minimum

3" MIN
Figure 3: Open Chase Iso View

Figure 2: Open Chase

Cool Surface System Framing
Framing Option 3: Valance
A valance may be desired to accentuate or hide the CSS outlet. Consider framing option 1 or 2 to utilize the valance feature. This is an optional decorative feature that covers up the CSS outlet gap. Minimum opening and valance dimensions must be followed to ensure safe heat dissipation. Combustible materiel is acceptable when constructing the valance. It is acceptable to wrap the valance around the three sides of a built out chase (Option 2).

Minimum 4" 102mm

6" 152mm Minimum

1" 25mm Maximum

6" 152mm Minimum

2" 51mm

4

3 4

"

121mm

Minimum

Figure 5: Valance Iso View

Wall Mounted Object

Figure 4: Valance Install

Framing Option 4: Side Discharge
Construct the framing in a way that provides two gaps, one on each side of the chase as shown in Figure 7. Each gap should be a minimum of 21 inch (533mm) by 3 inch (76mm). It is essential that these dimensions are followed and not to deviated from them when using combustible materials inside the chase (see Figure 6).

3" 76mm Minimum

5" 127mm Maximum

4

3 4

"

121mm

Minimum

21" 533mm Minimum

Figure 7: Side Discharge Iso View

Figure 6: Side Discharge
Optional: False Ceiling
If your ceiling dimension is greater than the minimum (See Figure 1) You may want the CSS air discharge lower on the wall. This false ceiling is required to properly evacuate heat from the chase. (See Figure 8).

2" 51mm Minimum

False Ceiling

4

3 4

"

121mm

Minimum

Figure 9: False Ceiling Iso View

Figure 8: False Ceiling

