EBYTE ME31-XXXA0006 Network I-O Networking Module

EBYTE-ME31-XXXA0006-Network I-O-Networking-Module-PRODUCT

Overview

Product Introduction
ME31-XXXA0006 is a network I/O networking module with 6 analog outputs (0-20mA/4-20mA) and supports Modbus TCP protocol or Modbus RTU protocol for acquisition and control. The device can also be used as a simple Modbus gateway (automatically send commands with non-local Modbus addresses through the serial port/network port).

Functional Features

  • Support standard Modbus RTU protocol and Modbus TCP protocol;
  • Support various configuration software/PLC/touch screen;
  • RS485 acquisition control I/O;
  • RJ45 acquisition control I/O, support 4-way host access;
  • Support OLED display to display status information, and configure device parameters through buttons;
  • 6 analog outputs (0-20mA/4-20mA);
  • Support custom Modbus address setting;
  • Support 8 common baud rate configurations;
  • Support DHCP and static IP;
  • Support DNS function, domain name resolution;
  • Support Modbus gateway function;

Product Application Topology Diagram EBYTE-ME31-XXXA0006-Network I-O-Networking-Module (3)

EBYTE-ME31-XXXA0006-Network I-O-Networking-Module (4)

Quick use

Note】 This test needs to be carried out with the default factory parameters.

Device preparation
The following table lists the items required for this test EBYTE-ME31-XXXA0006-Network I-O-Networking-Module (5)Device connection

RS485 connection EBYTE-ME31-XXXA0006-Network I-O-Networking-Module (6)Note: When the 485 bus high-frequency signal is transmitted, the signal wavelength is shorter than the transmission line, and the signal will form a reflected wave at the end of the transmission line, which will interfere with the original signal. Therefore, it is necessary to add a terminal resistor at the end of the transmission line so that the signal does not reflect after reaching the end of the transmission line. The terminal resistance should be the same as the impedance of the communication cable, the typical value is 120 ohms. Its function is to match the bus impedance and improve the anti-interference and reliability of data communication.

AO analog output connection EBYTE-ME31-XXXA0006-Network I-O-Networking-Module (7)

Simple use EBYTE-ME31-XXXA0006-Network I-O-Networking-Module (8)Wiring: The computer is connected to the RS485 interface of ME31-XXXA0006 through USB to RS485, A is connected to A, and B is connected to B.
Networking: Insert the network cable into the RJ45 port and connect to the PC.
Power supply: Use DC-12V switching power supply (DC 8~28V) to power ME31-XXXA0006.

Parameter Configuration

  1. Step 1: Modify the IP address of the computer to be consistent with the device. Here I am modifying it to 192.168.3.100 to ensure that it is on the same network segment as the device and that the IP is different. If you cannot connect to the device after the above steps, please turn off the firewall and try again; EBYTE-ME31-XXXA0006-Network I-O-Networking-Module (9)
  2. Step 2: Open the network assistant, select the TCP client, enter the remote host IP192.168.3.7 (default parameter), enter the port number 502 (default parameter), and select HEX to send. EBYTE-ME31-XXXA0006-Network I-O-Networking-Module (10)

Control Testing

Modbus TCP control
Use the network assistant to control the first AO output of ME31-XXXA0006 to 10mA. EBYTE-ME31-XXXA0006-Network I-O-Networking-Module (11)Other functions can be tested through the commands in the table below.

Function (function code) Command
Control AO1 output 10mA (0x10) 01 00 00 00 00 0B 01 10 00 00 00 02 04 41 20 00 00
Read AO1 output (0x03) 01 00 00 00 00 06 01 03 00 00 00 02

Modbus RTU control
Use the serial port assistant to read the current AO1 output of ME31-XXXA0006.EBYTE-ME31-XXXA0006-Network I-O-Networking-Module (12)

Other functions can be tested through the commands in the table below.

Function (function code) Command
Read current AO1 output (0x03) 01 03 00 00 00 02 C4 0B
Control AO1 current output 10mA (0x10) 01 10 00 00 00 02 04 41 20 00 00 E6 59

Technical Specification

Specifications

Category Name Parameters
Power supply Operating Voltage DC8~28V
Power indicator Blue LED indication
  Serial port CommunicationInterface RJ45, RS485
Baud rate 9600bps (customizable)
Protocol Standard Modbus TCP, Modbus RTU protocol
MODBUS Device address Can be modified by Modbus command and host computer
    AO output Number of AO channels 6 way
AO output type Current output, 2-wire connection
AO output range 0~20mA \4~20mA
AO resolution 16 bits
Output accuracy 3‰
Output indication OLED screen display
     Other Product Size 121mm * 72mm * 34mm (L*W*H)
Product weight 135 ±5 g
Working temperature and humidity -40 ~ +85℃, 5% ~ 95%RH (nocondensation)
Storage temperature and humidity -40 ~ +105℃, 5% ~ 95%RH (nocondensation)
Installation method Din-rail installation

Device Default Parameters

Category Name Parameters
Ethernet parameters Operating mode TCP server (up to 4-way client access)
Local IP 192.168.3.7
local port 502
Subnet mask 255.255.255.0
Gateway address 192.168.3.1
DHCP Close
Native MAC Determined by the chip (fixed)
Target IP 192.168.3.3
Target port 502
DNS server 114.114.114.114
Active upload Close
Serial parameters Baud rate 9600bps (8 types)
Check method None (default), Odd, Even
Data bit 8
Stop bit 1
MODBUS parameter Modbus master-slave Slave
Address 1

Mechanical Dimensional Drawing

EBYTE-ME31-XXXA0006-Network I-O-Networking-Module (13)Port and indicator light description

 

EBYTE-ME31-XXXA0006-Network I-O-Networking-Module (14)

No. Label Illustrate
1 TX(LED) Serial port send data indicator light
2 RX(LED) Serial port receiving data indicator light
3 LINK(LED) Network connection light
4 NET(LED) Network data sending and receiving indicator light
5 PWR(LED) Power input indicator
6 GND Negative pole of power input terminal, DC 8V~28V, 5.08mm Phoenix

terminal.

7 VCC Positive pole of power input terminal, DC 8V~28V, 5.08mm Phoenix

terminal.

8 AO3 Analog output current (positive pole), channel 3, 5.08mm Phoenix terminal.
9 AGND Analog output current (negative pole), channel 3, 5.08mm Phoenix terminal.
10 AO4 Analog output current (positive pole), channel 4, 5.08mm Phoenix terminal.
11 AGND Analog output current (negative pole), channel 4, 5.08mm Phoenix terminal.
12 AO5 Analog output current (positive pole), channel 5, 5.08mm Phoenix terminal.
13 AGND Analog output current (negative pole), channel 5, 5.08mm Phoenix terminal.
14 AO6 Analog output current (positive pole), channel 6, 5.08mm Phoenix terminal.
15 AGND Analog output current (negative pole), channel 6, 5.08mm Phoenix terminal.
16 Ethernet Ethernet interface, standard RJ45 interface.
17 AGND Analog output current (negative pole), channel 2, 5.08mm Phoenix terminal.
18 AO2 Analog output current (positive pole), channel 2, 5.08mm Phoenix terminal.
19 AGND Analog output current (negative pole), channel 1, 5.08mm Phoenix terminal.
20 AO1 Analog output current (positive pole), channel 1, 5.08mm Phoenix terminal.
21 GND Signal ground, 5.08mm Phoenix terminal.
22 485-A The A of the serial port is connected to the A interface of the external device,

and the 5.08mm Phoenix terminal.

23 485-B The B of the serial port is connected to the B interface of the external device,

and the 5.08mm Phoenix terminal.

Product Function Introduction

AO output

AO output range
Analog output (AO), the current output type can be configured as 0~20mA or 4~20mA, the precision is 3‰, and the resolution is 16 bits.
The power-on default output value can be set (when the working mode is switched, the power-on value will be output according to the lowest value of the current range).

Modbus Gateway
The device can transparently transmit non-native Modbus commands from the network/serial port to the serial port/network, and the local Modbus commands are directly executed.

 Modbus TCP/RTU protocol conversion
After it is turned on, the Modbus TCP data on the network side will be converted to Modbus RTU data.

Modbus Address Filtering
This function can be used when some host software or configuration screen is used as the host to access the serial port of the device, and the gateway function of the device is used, the slave is at the network end, and the Modbus TCP to RTU function is turned on. Multiple slaves on the bus may cause data confusion. At this time, enabling address filtering can ensure that only the specified address can pass through the device; when the parameter is 0, the data will be transparently transmitted; when the parameter is 1-255, only the set slave machine address data.

Modbus TCP Protocol Data Frame Description
TCP frame format:

Transaction ID Protocol ID Length Device address Function code Data segment
2 Bit 2 Bit N+2 Bit 1 Bit 1 Bit N Bit

Transaction ID: It can be understood as the serial number of the message. Generally, 1 is added after each communication to distinguish different communication data messages.
Protocol identifier: 00 00 means Modbus TCP protocol.
Length: Indicates the length of the next data in bytes.

Example: get DI status

Example: get DI status

01 00 00 00 00 06 01 02 00 00 00 04
Transaction ID Protocol ID Length Device address Function code Data segment

Modbus RTU protocol data frame description

RTU frame format:

Device address Function code Data segment Check code CRC
1 Bit 1 Bit N Bit 2 Bit

Example: get DI status command 

01 02 00 00 00 04 79 C9
Device Modbus address Function code Data segment CRC check code

Active upload

  • The device supports the function of uploading analog input values at regular intervals. Setting the value of the corresponding register can control the interval time and whether to upload.
  • Devices with digital input will actively upload once after successfully connecting to the server, and then the digital input will be uploaded following the status change. Devices with analog input will report the status of analog input according to the configured active upload time period (the configuration period is 1-65535 ).
  • When it is set to 0, the upload is disabled; if it is set to other positive integer value N, the upload will be performed at intervals of N seconds.
[Note] The device can only be valid if it is configured in client mode, and the register value is non-zero to enable active upload.

 Custom Module Information

Modbus Address
The device address is 1 by default, and the address can be modified, and the address range is 1-247.

Module Name
Users can configure the device name according to their own needs to distinguish, support English, digital format, up to 20 bytes.

Network parameters
Unless otherwise specified: the following network-related parameters default to IPV4-related parameters.

  1. MAC of the device: the user can obtain it by reading the specified register, and this parameter cannot be written.
  2. IP address: device IP address, readable and writable.
  3. Modbus TCP port: the port number of the device, readable and writable.
  4. Subnet mask: address mask, readable and writable.
  5. Gateway address: gateway.
  6. DHCP: Set the way the device obtains IP: static (0), dynamic (1).
  7. Target IP: When the device works in client mode, the target IP or domain name of the device connection.
  8. Destination port: When the device is working in client mode, the destination port of the device connection.
  9. DNS server: The device is in the client mode and resolves the domain name of the server.
  10. Module working mode: switch the working mode of the module. Server: The device is equivalent to a
    server, waiting for the user’s client to connect. The maximum number of connections is 4. Client: The device actively connects to the target IP and port set by the user.
  11. Active upload: When this parameter is not 0, and the device is in the client mode, the discrete input status of the device will be uploaded to the server when it is connected for the first time or the input changes, and the analog input will be uploaded according to the configured time period.

Serial Port Parameters
Parameters for setting serial communication:

Default parameters:

  • Baud rate: 9600 (03);
  • Data bit: 8bit;
  • Stop bit: 1bit;
  • Check digit: NONE(00);

 Baud rate:

Baud rate code value table
0x0000 1200
0x0001 2400
0x0002 4800
0x0003(default) 9600
0x0004 19200
0x0005 38400
0x0006 57600
0x0007 115200

 Check Digit:

Check Digit
0x0000(default) NONE
0x0001 ODD
0x0002 EVEN

OLED display and parameter configuration
The display interface includes an information display page (DO status display page) and a parameter setting page (partial parameters).

Information Display Interface
Including the DO status display page, short press the up and down buttons to switch the interface.

Equipment parameter display interface
Press the left or right button to enter the password input interface, complete the correct password input, and display the device parameter information interface (password interface: default password: 0000. Short press the middle to verify the password; The left and right buttons can switch the password bit; Up and down keys can switch the value of the current bit. The password has a total of 4 digits, and each input is a number ranging from 0-9):

The parameter setting interface from top to bottom is:

  1. Modbus address;
  2. Baud rate;
  3. Data bits;
  4.  Check Digit;
  5. Stop bit;
  6. Local port;
  7. Local IP address;
  8. Network mode;
  9. Gateway; Subnet mask;
  10. DNS;
  11. MAC address;
  12. DHCP;
  13. Target IP;
  14. Destination port;
  15.  Modbus TCP/RTU protocol conversion;
  16. Active upload;
  17. Modbus address filtering;;

 Equipment Parameter Configuration Interface
Press and hold the confirmation button to enter the password input interface, complete the correct password input, and enter the configuration interface (password interface: default password: 0000; short press the middle to verify the password, the left and right buttons switch the password bit, and the up and down buttons switch the value of the current bit , the password has a total of 4 digits, and each input range is a number from 0-9). Select the setting item, enter the parameter configuration page and short press the up and down keys to switch the setting item;

Select the setting item, short press to confirm or right click, the setting item gets the cursor to represent the selection and enter the setting item; Adjust the parameter value: After selecting the setting item, the up and down keys can change the value or optional value; the left and right keys move the cursor in the parameter item; Confirm the parameter value: After adjusting the parameter value, press the enter key to exit the current setting item. Save parameter settings and restart: After setting the parameters, move the cursor to save and restart, then short

press the confirmation key to enter the confirmation save and restart state. Short press the confirmation key (press other keys to exit the confirmation state) to save the parameters and restart the device.
Exit without saving parameters: move the cursor to exit, then short press the confirmation key to enter the confirmation exit state, short press the confirmation key (press other keys to exit the confirmation state), and then exit the parameter configuration interface without saving the parameters . Among them, the data bit and stop bit cannot be set. After the DHCP mode is turned on, the local IP address, gateway, and subnet mask cannot be configured and are only assigned by the router;

Screen Sleep
The device screen has a sleep function, which is off by default and can be set to on in the configuration interface. In any interface, when there is no button operation for 180 seconds, the screen will enter the sleep mode. At this time, the interface displays Ebyte robot. Press any button can exit the sleep mode. When the screen is in sleep mode, the running efficiency of device programs will be improved.

MODBUS parameter configuration
Note: According to the usage requirements, some software (such as KingView) requires adding +1 when converting from hexadecimal to decimal in order to operate on registers (all decimal values in the table have already been adjusted by +1).

AO Register List

Register function Register address(HEX) Register address(DEC) Register type  Number  Operate  Data Range/Remarks Related function code
Analogoutput value  0x0000  4-0001 Holding register  12  RW 32-bit floating point type, unit mA R:0x03 W:0x10
Analog outputvalue  0x0064  4-0101 Holding register  6  RW Analog channel output quantity, 2-byte integer, unit (uA) R:0x03 W:0x10
AO output mode  0x0514  4-1301 Holding register  6  RW AO channel output range 0x0000: 0~20mA0x0001: 4-20mA R:0x03 W:0x06、0x10
AO power- on output initial value   0x00C8   4-0201  Holding register   12   RW Output engineering quantity when the analog channel is powered on, a 4-byte floatingpoint number, the default is 0  R 0x03 W 0x10

Module related registers

Register function Register address (HEX) Register address (DEC) Register type  Number  Operate  Data Range/Remarks Related function code
Moduleaddress 0x07E8 4-2025 Holdingregister 1 RW Modbus address,1~247 configurable addresses R:0x03W:0x06
Modulemodel 0x07D0 4-2001 Holdingregister 12 R Get the current model R:0x03
Firmwareversion 0x07DC 4-2013 Holdingregister 1 R Get firmware version number R:0x03
Modulename 0x07DE 4-2015 Holdingregister 10 RW Custom module name R:0x03W:0x10
Modulerestart 0x07EA 4-2027 Holdingregister 1 W Write 0x5BB5 to reboot. W:0x06
Restore factoryparameters  0x07E9  4-2026 Holding register  1  W Write 0x5BB5 to restore factory settings.  W:0x06
Serialbaud rate 0x0834 4-2101 Holdingregister 1 RW See baud rate code table,Default is 9600 (0x0003) R:0x03W:0x06、0x10
Serial checkdigit  0x0836  4-2103 Holding register  1  RW 0x0000 no checksum (default) 0x0001 odd parity0x0002 even parity R:0x03 W:0x06、0x10

Network related registers

Register function Register address(HEX) Register address(DEC) Register type  Number  Operate  Data Range/Remarks Related function code
Module MACaddress  0x0898  4-2201 Holding register  3  R  Device MAC parameters  R:0x03
Local IPaddress 0x089B 4-2204 Holdingregister 2 RW Default: 192.168.3.7 R:0x03W:0x06、0x10
local port 0x089D 4-2206 Holdingregister 1 RW 1~65535, default: 502 R:0x03W:0x06、0x10
Subnet maskaddress  0x089E  4-2207 Holding register  2  RW  Default: 255.255.255.0 R:0x03 W:0x06、0x10
Gatewayaddress 0x08A0 4-2209 Holdingregister 2 RW Default: 192.168.3.1 R:0x03W:0x06、0x10
DHCP mode setting  0x08A2  4-2211 Holding register  1  RW 0x0000 static IP (default) 0x0001 Obtain IP automatically R:0x03 W:0x06、0x10
Target IP/domain name  0x08A3  4-2212 Holding register  64  RW String format stored in IP/domain name Default IP: 192.168.3.3 R:0x03 W:0x06、0x10
Server port 0x08E3 4-2276 Holdingregister 1 RW 0-65535, default 502 R:0x03W:0x06、0x10
DNS server IP address  0x08E4  4-2277 Holding register  2  RW  Default 8.8.8.8 R:0x03 W:0x06、0x10
Modulework mode 0x08E6 4-2279 Holdingregister 1 RW 0x0000 server mode0x0001 client mode R:0x03W:0x06、0x10
Activeupload 0x08E7 4-2280 Holdingregister 1 RW 0x0000 disabled, others:1~65535s cycle sending R:0x03W:0x06、0x10
MOSBUS TCP/RTUconversionenable   0x08E8   4-2281  Holding register   1   RW  0, close, 1 open protocol conversion  R:0x03 W:0x06、0x10
 MODBUS address filtering   0x08E9   4-2282   Holding register   1   RW 0: transparent transmission, 1-255: when the data is not local, check the slave address of the command , and it can be passed when it is theset value   R:0x03 W:0x06、0x10

Examples of Modbus command operation instructions

  1. Read coil (DO) status Use the read coil state (01) function code to read the output coil state, for example
01 01 00 00 00 04 3D C9
Modbus address Function code Register first

address

Number of output coils read CRC check

code

After sending the above command to the device through the 485 bus, the device will return the following values:

01 01 01 01 90 48
Modbus address Function code Bytes of data Returned status data CRC check code

The status data 01 returned above indicates that the output DO1 is turned on.

Control coil (DO) state

Support operation of single coil (05), operation of multiple coils (0F) function code operation.
Use the 05 command to write a single command, for example:

01 05 00 00 FF 00 8C 3A
Modbus address Function code Register first address Continuity: FF 00Close: 00 00 CRC check code

After sending the above command to the device through the 485 bus, the device will return the following values:

01 05 00 00 FF 00 8C 3A
Modbus address Function code Register firstaddress Operation method CRC check code

The DO1 coil is turned on.
Use 0F function code as the command to write multiple coils, for example:

01 0F 00 00 00 04 01 0F 7E 92
Modbus address Function code Initial address Number of coils Bytes of data Control coil data CRC check code

After sending the above command to the device through the 485 bus, the device will return the following values:

01 0F 00 00 OO O4 54 08
Modbus address Function code Register address Number of coils CRC check code

The coils are all on.

 Read the holding register
Use 03 function code to read one or more register values, for example:

01 03 05 78 00 01 04 DF
Modbus address Function code Register firstaddress Number of registers read CRC check code

After sending the above command to the device through the 485 bus, the device will return the following values:

01 03 02 00 00 B8 44
Modbus address Function code Bytes of data Returned data CRC check code

The above 00 00 means that DO1 is in level output mode.

 Operation holding register
Support operation of single register (06), operation of multiple registers (10) function code operation. Use 06 function code to write a single holding register, for example: set the working mode of DO1 to pulse mode:

01 06 05 78 00 01 C8 DF
Modbus address Function code Register address Write value CRC check code

After sending the above command to the device through the 485 bus, the device will return the following values:

01 06 05 78 00 01 C8 DF
Modbus address Function code Register address Write value CRC check code

If the modification is successful, the data in the 0x0578 register is 0x0001, and the pulse output mode is turned on.
Use function code 10 to write multiple holding register commands, for example: set the working mode of DO1 and DO2 at the same time.

01 10 05 78 00 02 04 00 01 00 01 5A 7D
Modbus

address

Function

code

Register head

address

Number of

registers

Number of bytes of

written data

Written data CRC check

code

After sending the above command to the device through the 485 bus, the device will return the following values:

01 10 05 78 00 02 C1 1D
Modbus address Function

code

Register address Number of registers CRC check code

If the modification is successful, the values of the two consecutive registers starting with 0x0578 are 0x0001 and 0x0001 respectively, marking DO1 and DO2 to enable pulse output.

Configuration Software

Acquisition and Control

  1. Step 1: Connect the device to the configuration software.
    1. You can configure the device by selecting the interface (serial port/network port); if you choose the network port, you must first select the network card and then search for the device. EBYTE-ME31-XXXA0006-Network I-O-Networking-Module (15)
    2. If you choose a serial port, you need to select the corresponding serial port number, and the same baud rate, data bit, stop bit, parity bit and address segment search range as the device, and then search. EBYTE-ME31-XXXA0006-Network I-O-Networking-Module (16)
  2. Step 2: Select the corresponding device. EBYTE-ME31-XXXA0006-Network I-O-Networking-Module (17)
  3. Step 3: Click the device online to enter the IO monitoring. The following is the IO monitoring screen display. EBYTE-ME31-XXXA0006-Network I-O-Networking-Module (18)

Parameter configuration interface

  1. Step 1: Connect the device refer to “Acquisition and Control”.
  2. Step 2: You can configure device parameters, network parameters, DI parameters, AI parameters, DO parameters, and AO parameters (for example: if the device has no AO function, the AO parameters cannot be configured) EBYTE-ME31-XXXA0006-Network I-O-Networking-Module (19)
  3. Step 3: After configuring the parameters, click Download Parameters. After the prompt message in the log output shows that the parameters are saved successfully, click Restart the device. After the device restarts, the modified parameters will take effect.
    EBYTE-ME31-XXXA0006-Network I-O-Networking-Module (1)

Revise history

Version Revision date Revision Notes Maintenance man
1.0 2023-6-6 Initial version LT
1.1 2024-10-18 Content revision LT

About us

FAQ

  • Q: Where can I find the latest version of the user manual?
    A: The latest version of the user manual can be obtained from the manufacturer’s website or customer support.