BACnet Protocol Implementation Conformance Statement
Date: 2/14/2024 | Vendor Name: Ebtron, Inc. |
Product Name: Gold Series GTC108e | Application Software Version: 1.00 |
Product Model Number: GTC108e | Firmware Revision: 8.33 |
Product Description: Airflow and Temperature Measurement Device | BACnet Protocol Revision: 22 |
BACnet Standardized Device Profile (Annex L)
□ BACnet Operator Workstation (B-OWS)
□ BACnet Building Controller (B-BC)
□ BACnet Advanced Application Controller (B-AAC)
□ BACnet Application Specific Controller (B-ASC)
■ BACnet Smart Sensor (B-SS)
□ BACnet Smart Actuator (B-SA)
BACnet Interoperability Building Blocks Supported (Annex K)
DS-RP-B | DS-RPM-B |
DS-WP-B | DS-WPM-B |
DS-COV-B | DM-DDB-B |
DM-DOB-B | DS-DCC-B |
DM-RD-B |
Segmentation Capability
□ Segmented requests supported Window Size
□ Segmented responses supported Window Size
Standard Object Types Supported: (See Table 1)
Data Link Layer Options
□ BACnet IP, (Annex J)
□ ISO 8802-3, Ethernet (Clause 7)
□ ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
□ ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)
■ MS/TP master (Clause 9), baud rate(s): 76,800 38,400 19,200 9,600
□ MS/TP slave (Clause 9), baud rate(s):
□ Point-To-Point, EIA 232 (Clause 10), baud rate(s):
□ Point-To-Point, modem, (Clause 10), baud rate(s):
□ LonTalk, (Clause 11), medium:
□ Other:
Device Address Binding
Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.) □Yes ■ No
Networking Options
□ Router, Clause 6 – List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.
□ Annex H, BACnet Tunneling Router over IP
□ BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign Devices? □ Yes □ No
Character Sets Supported
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
■ ANSI X3.4/UTF-8
□ IBM tm/Microsoft tm DBCS
□ ISO 8859-1
□ ISO 10646 (UCS-2)
□ ISO 10646 (UCS-4)
□ JIS C 6226
If this product is a communication gateway, describe the types of non-BACnet equipment/networks(s) that the gateway supports:
TABLE 1 – Standard Object Types Supported (GTC108e) | |||||||
Object | Create Object Service | Delete Object Service | Optional Properties Supported | Writeable Properties | Proprietary Properties | Property Range Restrictions | Special Requirements |
Device – GTC108e | No | No |
|
|
|
None | None |
Analog Input 1 – AMD Airflow | No | No |
|
|
None | Units: FPM, CFM, MPS, LPS | None |
Analog Input 2 – AMD Temperature | No | No |
|
|
None | Units: °C or °F | None |
Analog Input 4 – AMD Alarm Status | No | No |
|
|
None | None | None |
Analog Input 5 – AMD Fan Alarm Status | No | No |
|
|
None | None | Fan Array |
Analog Value 1 – AMD Area | No | No |
|
None | Units: sq ft or sq m | Fan Array | |
Analog Value 2 – Fan 1 Area | No | No |
|
None | Units: sq ft or sq m | Fan Array | |
Analog Value 3 – Fan 2 Area | No | No |
|
None | Units: sq ft or sq m | Fan Array | |
Analog Value 4 – Fan 3 Area | No | No |
|
None | Units: sq ft or sq m | Fan Array | |
Analog Value 5 – Fan 4 Area | No | No |
|
None | Units: sq ft or sq m | Fan Array | |
Analog Value 6 – Fan 5 Area | No | No |
|
None | Units: sq ft or sq m | Fan Array | |
Analog Value 7 – Fan 6 Area | No | No |
|
None | Units: sq ft or sq m | Fan Array | |
Analog Value 8 – Fan 7 Area | No | No |
|
None | Units: sq ft or sq m | Fan Array |
Object | Create Object Service | Delete Object Service | Optional Properties Supported | Writeable Properties | Proprietary Properties | Property Range Restrictions | Special Requirements |
Analog Value 9 – Fan 8 Area | No | No |
|
None | Units: sq ft or sq m | Fan Array | |
Analog Value 10 – Traverse Status | No | No |
|
Present Value | None | Only write 0 – 3 | None |
Analog Value 21 – Node 1 Velocity | No | No |
|
None | Units: FPM, MPS | Enabled in AV 10 | |
Analog Value 22 – Node 2 Velocity | No | No |
|
None | Units: FPM, MPS | Enabled in AV 10 | |
Analog Value 23 – Node 3 Velocity | No | No |
|
None | Units: FPM, MPS | Enabled in AV 10 | |
Analog Value 24 – Node 4 Velocity | No | No |
|
None | Units: FPM, MPS | Enabled in AV 10 | |
Analog Value 25 – Node 5 Velocity | No | No |
|
None | Units: FPM, MPS | Enabled in AV 10 | |
Analog Value 26 – Node 6 Velocity | No | No |
|
None | Units: FPM, MPS | Enabled in AV 10 | |
Analog Value 27 – Node 7 Velocity | No | No |
|
None | Units: FPM, MPS | Enabled in AV 10 | |
Analog Value 28 – Node 8 Velocity | No | No |
|
None | Units: FPM, MPS | Enabled in AV 10 | |
Analog Value 41 – Node 1 Temperature | No | No |
|
None | Units: °C or °F | Enabled in AV 10 | |
Analog Value 42 – Node 2 Temperature | No | No |
|
None | Units: °C or °F | Enabled in AV 10 | |
Analog Value 43 – Node 3 Temperature | No | No |
|
None | Units: °C or °F | Enabled in AV 10 | |
Analog Value 44 – Node 4 Temperature | No | No |
|
None | Units: °C or °F | Enabled in AV 10 | |
Analog Value 45 – Node 5 Temperature | No | No |
|
None | Units: °C or °F | Enabled in AV 10 | |
Analog Value 46 – Node 6 Temperature | No | No |
|
None | Units: °C or °F | Enabled in AV 10 | |
Analog Value 47 – Node 7 Temperature | No | No |
|
None | Units: °C or °F | Enabled in AV 10 | |
Analog Value 48 – Node 8 Temperature | No | No |
|
None | Units: °C or °F | Enabled in AV 10 | |
Analog Value 101 – Fan 1 Flow | No | No |
|
None | Units: FPM, CFM, MPS, LPS | Fan Array | |
Analog Value 102 – Fan 2 Flow | No | No |
|
None | Units: FPM, CFM, MPS, LPS | Fan Array | |
Analog Value 103 – Fan 3 Flow | No | No |
|
None | Units: FPM, CFM, MPS, LPS | Fan Array | |
Analog Value 104 – Fan 4 Flow | No | No |
|
None | Units: FPM, CFM, MPS, LPS | Fan Array | |
Analog Value 105 – Fan 5 Flow | No | No |
|
None | Units: FPM, CFM, MPS, LPS | Fan Array |
Object | Create Object Service | Delete Object Service | Optional Properties Supported | Writeable Properties | Proprietary Properties | Property Range Restrictions | Special Requirements |
Analog Value 106 – Fan 6 Flow | No | No |
|
None | Units: FPM, CFM, MPS, LPS | Fan Array | |
Analog Value 107 – Fan 7 Flow | No | No |
|
None | Units: FPM, CFM, MPS, LPS | Fan Array | |
Analog Value 108 – Fan 8 Flow | No | No |
|
None | Units: FPM, CFM, MPS, LPS | Fan Array | |
Analog Value 111 – Fan 1 Temperature | No | No |
|
None | Units: °C or °F | Fan Array | |
Analog Value 112 – Fan 2 Temperature | No | No |
|
None | Units: °C or °F | Fan Array | |
Analog Value 113 – Fan 3 Temperature | No | No |
|
None | Units: °C or °F | Fan Array | |
Analog Value 114 – Fan 4 Temperature | No | No |
|
None | Units: °C or °F | Fan Array | |
Analog Value 115 – Fan 5 Temperature | No | No |
|
None | Units: °C or °F | Fan Array | |
Analog Value 116 – Fan 6 Temperature | No | No |
|
None | Units: °C or °F | Fan Array | |
Analog Value 117 – Fan 7 Temperature | No | No |
|
None | Units: °C or °F | Fan Array | |
Analog Value 118 – Fan 8 Temperature | No | No |
|
None | Units: °C or °F | Fan Array | |
Network Port 1 | No | No |
|
|
None | None | None |