Dwyer Bulletin P-DHC-QS Series DHC Digihelic Differential Pressure Controller
QUICK START GUIDE
- Mount on the surface or in the panel using provided screws and mounting lugs.
- Attach provided cable and wire using the table on the reverse side.
- Set zero calibration. Apply zero pressure to both ports and navigate the menu to zero the device. Menu -> CAL -> ZERO ->Hit enter button.
- Scan the QR code with a smart device to open the product web page for additional resources.
WIRING INFORMATION
Function | 15 Pin Connector Terminal | Cable Color |
12-28 VAC/VDC
Power |
1 | Brown |
12-28 VAC/VDC
Power |
6 | Yellow |
4-20 mA Output Signal | 11 | Red |
0-10 V Output
Signal |
7 | Light
Purple |
External Input Signal | 8 | Light Green |
Signal Common | 2 | Black |
Relay #1 N/O | 12 | Violet |
Relay #1 Common | 13 | Grey |
Relay #1 N/C | 14 | White |
Relay #2 N/O | 15 | Dark Blue |
Relay #2
Common |
10 | Dark
Green |
Relay #2 N/C | 5 | Orange |
RS-485 B(+) | 4 | Tan |
RS-485 A(-) | 3 | Pink |
RS-485
Common |
9 | Light Blue |
- Printed in U.S.A. 6/22 FR# 444695-00
- ©Copyright 2022 Dwyer Instruments, LLC