DUCO-logo

DUCO L2003592-F Modbus TCP

Product Specifications

  • Product Name: Duco Connectivity Board
  • Supported Models: DucoBox Silent Connect, DucoBox Focus, DucoBox Energy
  • Modbus Subset Support: HEX 0x03, 0x04, 0x06, 0x10
  • Modbus Component Interface: TCP on port 502

Product Usage Instructions

Working with Registers/Parameters
The DucoBox Silent Connect, Focus, and Energy support the following Modbus subset functions:

  • Read multiple HOLDING registers (HEX 0x03)
  • Read multiple INPUT registers (HEX 0x04)
  • Write a single HOLDING register (HEX 0x06)
  • Write multiple HOLDING registers (HEX 0x10)
    Input registers are read-only 16-bit variables, while holding registers are read/write 16-bit variables. The Modbus address can be set via the Display menu, Duco Installation App, or Duco Network Tool.

Communication with Control Unit
The external control unit communicates with each component through read parameters (INPUT) and write parameters (HOLDING).

  • Read Parameters (INPUT): Ventilation system type, ventilation status, indoor air quality based on relative humidity, indoor air quality based on CO2 value, etc.
  • Write Parameters (HOLDING): Ventilation status, component identification, etc.
    It is recommended to read the current value before performing a write action to adjust the value. There are limits on write actions to prevent excessive writing.

Overview of Parameters
Below is an overview of the INPUT and HOLDING parameters for the ventilation system and its components:

Register INPUT (Read Parameter) Data Conversion Application Recommended Survey Frequency
0020 Temperature ODA Displays the temperature of the supply air from outside to the
unit (Outdoor Air).
DucoBox Energy 1/min

Introduction

  • The Modbus interface on DUCO systems (via the Duco Connectivity Board option on a DucoBox)1 allows an external controller or building management system to communicate with the DUCO ventilation system.
  • That way, you can retrieve info about the ventilation network via read parameters or input registers, or read or adjust settings via write parameters or holding registers.
  • The supported protocol is Modbus TCP over Ethernet or Wi-Fi via the Duco Connectivity Board. The information in this document is valid from API version v2.5 onwards.

Working registers/parameters

  • The DucoBox Silent Connect, Focus, and Energy support the following Modbus subset:
    HEX DEC SUPPORT FUNCTION
    0x03 3 Read multiple HOLDING registers
    0x04 4 Read multiple INPUT registers
    0x06 6 Write a single HOLDING register
    0x10 16 Write multiple HOLDING registers
  • Here, input registers are 16-bit read-only variables, and holding registers are 16-bit read/write variables. Combined consecutive registers are not used. The Duco Connectivity Board functions as a Modbus component via TCP on port 502. The Modbus address can be set via the Display menu (see information sheet L8000002), the Duco Installation App, or the Duco Network Tool.
  • The external control unit communicates with each component (node) through read parameters (INPUT) and write parameters (HOLDING).
    • Read parameters (INPUT): ventilation system type, ventilation status, indoor air quality based on relative humidity, indoor air quality based on CO2 value, …
    • Write parameters (HOLDING): ventilation status, identification (of components), …
      Note: Read parameters can be read without restriction. There are, however, two important limits to writing actions:
      1. A daily limit of 200 write actions. From a second supply or extraction zone, 100 write actions are added per additional zone.
      2. A periodic limit of one write action every 2 seconds.
  • It is recommended to use a logic that first reads the current value before determining whether a new write action is needed to adjust the value.
  • Each node and its parameters are assigned a code: XXyy (XX=node number, yy=parameter number).DUCO-L2003592-F-Modbus-TCP-fig-1
  • This allows all values to be read and controlled from the external control unit. There are specific parameters for each component.
    Note
    • Due to a difference in some Modbus implementations compared to the official specification (on which our implementation is based), an address shift of ‘1’ may occur for the read and write parameters.
      E.g.: read address ‘20’ will become ‘19’.
    • For any box type (Silent Connect, Focus, Energy), this can be resolved via the Duco Installation App or the Duco Network Tool under tab > Tree view-Settings-external settings. With the DucoBox Focus, moreover, this can be solved by setting ‘ > ‘RegOffs’ to ‘1’ under > CONFIG > Modbus in the Display menu. With the DucoBox Energy also possible via ‘Register Offset’ under > Setting > Modbus in the advanced menu.

Overview of parameters

The overview is grouped into three sections:

  • Parameters that are only supported at the system level.
  • Parameters that are only supported by the DucoBox.
  • Parameters that are supported by the nodes (components).
    Below is an overview of the INPUT and HOLDING parameters for both the ventilation system and the components.

System parameters:

INPUT

(read parameter)

Register Data Conversion Application Recommended survey frequency
0020 Temperature ODA Displays the temperature of the supply air from outside to the unit (Outdoor Air). °C / 10 DucoBox Energy 1 / min
0021 SUP temperature displays the temperature of the supply air from the unit to the home (Supply Air). °C / 10 DucoBox Energy 1 / min
0022 Temperature ETA Displays the temperature of the exhaust air from the home to the unit (Extract Air). °C / 10 DucoBox Energy 1 / min
0023 Temperature EHA Displays the temperature of the exhaust air from the unit to the outside (Exhaust Air). °C / 10 DucoBox Energy 1 / min
0024 Outdoor temperature measured via the weather station. °C / 10 DucoBox with weather station 1 / min
0025 Wind speed
Measured via the weather station.
Decimetre/second DucoBox with weather station 1 / min
0026 Rain
Measured via the weather station.
0 = No (False) 1 = Yes (True) DucoBox with weather station 1 / min
0027 Light intensity south was measured via the weather station. Kilolux DucoBox with weather station 1 / min
0028 Light intensity east was measured via the weather station. Kilolux DucoBox with weather station 1 / min
0029 Light intensity west was measured via the weather station. Kilolux DucoBox with weather station 1 / min
0030 Local API Version Displays the local API version. Whole number Example: 2.4 becomes 204.

Public API version ‘X.Y’ becomes Modbus = X · 100 + Y

DucoBox Silent Connect DucoBox Focus DucoBox Energy 1 / day
0031 Remaining write actions: Displays the number of corrective commands until midnight. Whole number DucoBox Silent Connect DucoBox Focus DucoBox Energy 1 / min
  • Negative temperatures are displayed as a number greater than 32767.
  • To display this value correctly, you need to implement some logic to convert the value.
  • The formula is: (value-65536)/ 10
  • Example:
    • If(ModBusInputRegisterValue >= 32768)
    • Temp = (ModbusInputRegisterValue – 65536)/10
      Else
    • Temp = ModbusInputRegisterValue/10
      End

DucoBox parameters:

INPUT

(read parameter)

Register Data Conversion Application Recommended survey frequency
0100 System type
Indicates the type of ventilation system
17 = DucoBox DucoBox Silent Connect DucoBox Focus DucoBox Energy one-time
0102 Remaining time Current Ventilation mode
Indicates the remaining time the DucoBox will ventilate in this mode
Seconds DucoBox Silent Connect DucoBox Focus DucoBox Energy 1 / min
0103 Flow rate versus target level
Displays the actual ventilation mode for the zone in which the component is located
Percentage DucoBox Silent Connect DucoBox Focus DucoBox Energy 1 / min
0104 Indoor air quality based on RH
Average indoor air quality based on measured relative humidity
100 %

95 %

Very good indoor air quality Box sensor DucoBox Silent Connect

Box sensor DucoBox Energy

1 / min
90 %

80 %

65 %

Good indoor air quality
50 %

35 %

Temporarily acceptable indoor air quality
20 %

5 %

Poor indoor air quality
0105 Indoor air quality based on CO2
Average indoor air quality based on measured CO2 value
100 % Very good indoor air 95 %   quality

90 %

Box sensor DucoBox Silent Connect

Box sensor DucoBox Energy

1 / min
85 %

80 %   Good indoor air quality 75 %

70 %

65 %   Temporarily acceptable 60 %   indoor air quality

55 %

50 %

45 %

40 %   Poor indoor air quality 35 %

35 %

0106 Ventilation status
Indicates the status of ventilation
 

0 = OK

1 = Error

2 = Inactive

DucoBox Silent Connect DucoBox Focus DucoBox Energy 1 / min
0107  Filter Time Remaining
Indicates remaining filter life
Days DucoBox Energy 1 / day
0108  

Filter status
Indicates the status of the filter

0 = OK

1 = Filter is dirty 2 = Inactive

DucoBox Energy 1 / min
0109 Humidity
Indicates the measured humidity value.
RH (%) (relative humidity) DucoBox Silent Connect DucoBox Focus DucoBox Energy

+ minimum

1 humidity sensor

1 / min
10 % Poor indoor air quality
15 %
20 %   Temporarily acceptable
25 %   indoor air quality
30 % Good indoor air quality
35 %
40 %
Very good indoor air quality
45 %

50 %

55 %

60 % Good indoor air quality
65 %
70 %
75 %   Temporarily acceptable
80 %   indoor air quality
85 % Poor indoor air quality
0110 CO2
Indicates the measured CO2  value.
CO2 (ppm) DucoBox Silent Connect DucoBox Focus DucoBox Energy

+ minimum 1 CO2 Sensor

1 / min
< 800

800

900

Very good indoor air quality
1000

1100

1200

Good indoor air quality
1250

1300

1350

1400

1450

Temporarily acceptable indoor air quality
1500

1550

1600

> 1600

Poor indoor air quality
HOLDING

(read/write parameter)

Register Data Conversion Application Recommended survey frequency
0100 Ventilation mode

Here, the ventilation mode can be adjusted.

Conversions 11 through 16 are used to maintain manual modes longer.

For example, Manual 1 (conversion 4) is set to duration t by default. For Manual 1 x 2 (conversion 11), the mode t x 2 (= 2 x standard duration) will be maintained and for Manual

1 x 3 (conversion 14), the mode t x 3 (= 3 x standard duration) will be maintained.

0 = AUTO

4 = Manual 1

5 = Manual 2

6 = Manual 3 7 = Not at home

8 = Permanent 1

9 = Permanent 2

10 = Permanent 3

11 = Manual 1 x 2

12 = Manual 2 x 2

13 = Manual 3 x 2

14 = Manual 1 x 3

15 = Manual 2 x 3

16 = Manual 3 x 3

DucoBox Silent Connect DucoBox Focus DucoBox Energy 1 / min
xx01 Identification: Here, a component can be identified. This will light up blue. 0 = Node Visualisation OFF 1= Node Visualisation ON DucoBox Silent Connect DucoBox Focus DucoBox Energy One-time, read before write. (Read and check before writing)
0102 Supply temperature target zone 1
Here, the comfort temperature of the SUP zone 1 can be adjusted
°C / 10 DucoBox Energy One-time, read before write. (Read and check before writing)
0103 Supply temperature target zone 2
Here, the comfort temperature of the SUP zone 2 can be adjusted
°C / 10 DucoBox Energy One-time, read before write. (Read and check before writing)
0104 Supply temperature target zone 3
Here, the comfort temperature of the SUP zone 3 can be adjusted
°C / 10 DucoBox Energy One-time, read before write. (Read and check before writing)
0105 Supply temperature target zone 4
Here, the comfort temperature of the SUP zone 4 can be adjusted
°C / 10 DucoBox Energy One-time, read before write. (Read and check before writing)

Node parameters:

INPUT

(read parameter)

Register Data Conversion Application Recommended survey frequency
xx00 System type
Indicates the type of ventilation system
0 = Unknown

7 = DucoTronic window ventilator 8 = User controller RF/BAT

9 = User controller RF/Wired 10 = Humidity Room sensor 12 =CO2 Room sensor

13 = Sensorless Control Valve

14 = Humidity Control Valve 16 = CO2 Control Valve

18 = Switch Sensor

22 = iAV Control valve 23 = iAV Humidity

25 = iAV CO2

27 = Control unit

28 =CO2/RH control valve

29 = User Controller ‘Sun Control’

30 = User Controller ‘Ventilative Cooling’

31 = External multi-zone valve 35 = Humidity box sensor

37 = CO2 Box Sensor 38 = Motor relay

39 = Duco Weather Station or Outdoor Temperature Sensor 40 = Modbus motor

41 = Digital input 42 = Digital output 44 = Modbus relay 45 = Perilex

46 = Relay output

User controller Room sensor Box sensor Control valve Switch sensor

Electronic window ventilator

one-time
xx02 Remaining time Current Ventilation mode
Indicates the remaining time the DucoBox will ventilate in this mode
Seconds User controller Room sensor Control valve Switch sensor 1 / min
xx03 Flow rate versus target level
Displays the actual ventilation mode for the zone in which the component is located
Percentage Control valve, Electronic window ventilator 1 / min
xx04 Indoor air quality based on RH
Average indoor air quality based on measured relative humidity
100 %

95 %

Very good indoor air quality Room sensor Control valve 1 / min
90 %

80 %

65 %

Good indoor air quality
50 %

35 %

Temporarily acceptable indoor air quality
20 % Poor indoor air quality
xx05 Indoor air quality based on CO2
Average indoor air quality based on measured CO2 value
100 % Very good indoor air 95 %   quality

90 %

Room sensor Control valve 1 / min
85 %

80 %   Good indoor air quality 75 %

70 %

65 %   Temporarily acceptable 60 %   indoor air quality

55 %

50 %

45 %

40 %   Poor indoor air quality 35 %

30 %

xx09 Humidity
Indicates the measured humidity value.
RH (%) (relative humidity) Humidity Room Sensor Humidity Box Sensor

Humidity Control Valve

Electronic window ventilator

1 / min
10 %

15 %

Poor indoor air quality
20 %

25 %

Temporarily acceptable indoor air quality
30 %

35 %

40 %

Good indoor air quality
45 %

50 %

55 %

Very good indoor air quality
60 %

65 %

70 %

Good indoor air quality
75 %

80 %

Temporarily acceptable indoor air quality
 

85 %

Poor indoor air quality
xx10 CO2
Indicates the measured CO2  value.
CO2 (ppm) CO2 Room Sensor CO2 Box Sensor CO2 Control Valve 1 / min
< 800 Very good indoor air quality 800

900

1000
1100   Good indoor air quality
1200
1250
1300   Temporarily acceptable

1350   indoor air quality

1400
1450
1500

1550

1600

> 1600

 

Poor indoor air quality

HOLDING

(read/write parameter)

Register Data Conversion Application Recommended survey frequency
xx00 Ventilation mode

Here, the ventilation mode can be adjusted.

Conversions 11 through 16 are used to maintain manual modes longer.

For example, Manual 1 (conversion 4) is set to duration t by default. For Manual 1 x 2 (conversion 11), the mode t x 2 (= 2 x standard duration) will be maintained and for Manual

1 x 3 (conversion 14), the mode t x 3 (= 3 x standard duration) will be maintained.

0 = AUTO

4 = Manual 1

5 = Manual 2

6 = Manual 3 7 = Not at home

8 = Permanent 1

9 = Permanent 2

10 = Permanent 3

11 = Manual 1 x 2

12 = Manual 2 x 2

13 = Manual 3 x 2

14 = Manual 1 x 3

15 = Manual 2 x 3

16 = Manual 3 x 3

User controller Room sensor Box sensor Control valve

Electronic window ventilator

1 / min
xx01 Identification
Here, a component can be identified. This will light up blue.
0 = Node Visualisation OFF 1= Node Visualisation ON User controller, Room sensor, Control valve,e Switch sens, or Electronic window ventilator One-time, read before write. (Read and check before writing it)

General data

To find out which nodes are present in the network, you can (optionally) use the INPUT registers below. Alternatively, you can scan all registers.
Example:

DUCO-L2003592-F-Modbus-TCP-fig-2

 

REGISTER

 

DATA

RECOMMENDED SURVEY FREQUENCY
0000 Bit field indicating which node numbers between 1 and 15 are occupied in the network  

 

 

 

one-time

0001 Bit field indicating which node numbers between 16 and 31 are occupied in the network
0002 Bit field indicating which node numbers between 16 and 31 are occupied in the network
0003 Bit field indicating which node numbers between 48 and 63 are occupied in the network
0004 Bit field indicating which node numbers between 64 and 79 are occupied in the network
0005 Bit field indicating which node numbers between 80 and 95 are occupied in the network
0006 Bit field indicating which node numbers between 96 and 111 are occupied in the network
0007 Bit field indicating which node numbers between 112 and 127 are occupied in the network
0008 Bit field indicating which node numbers between 128 and 143 are occupied in the network

Frequently Asked Questions

How can I set the Modbus address for the Duco Connectivity Board?

The Modbus address can be set via the Display menu, Duco Installation App, or Duco Network Tool.

What are the limits on write actions for the Duco Connectivity Board?

There is a daily limit of 200 write actions, with additional actions allowed based on the number of supply or extraction zones. Additionally, there is a periodic limit of one write action every 2 seconds.

Documents / Resources

DUCO L2003592-F Modbus TCP [pdf] Instruction Manual
Silent Connect, Focus, Energy, L2003592-F Modbus TCP, L2003592-F, Modbus TCP, TCP

References

Leave a comment

Your email address will not be published. Required fields are marked *