DSEG8660 Intelligent Controller
Product Information
The DSEG8660 module is a versatile device that contains two software applications: Mains Controller and Group Controller. It is designed to monitor the mains (utility) supply and control one or more generator sets equipped with DSEG8600 (Multi Set) controllers based on the status of the mains supply. The module can be configured as a Group Controller, allowing the expansion of a system beyond the 64-module limit imposed by the capacity of a CAN bus.
Control Buttons
Icon | Description |
---|---|
Mode Button | In the G8660, the mode button is used to select Auto Mode, Test Mode, or Manual Mode. Pressing the button cycles through Auto mode > (Test mode) > Manual mode > Auto mode. |
Alarm Mute / Lamp Test | This button silences the audible alarm in the controller, deactivates the Audible Alarm output (if configured), and illuminates all the LEDs on the module’s facia as a lamp test function. |
RHS Breaker Button | Used for navigating the instrumentation, event log, and configuration screens. |
Accessing the Main Configuration Editor
To access the main configuration editor, press the (Stop/Reset) button. Once selected, the page remains on the LCD display until a different page is selected or after an extended period of inactivity (LCD Page Timer), the module reverts to the home display.
Editing a Parameter
To edit a parameter:
- Use the buttons to cycle to the section to view/change.
- Use the buttons to select the parameter to view/change within the currently selected section.
- Press the button to enter edit mode. The parameter will be highlighted to indicate selection.
- Use the buttons or Next Page/Previous Page buttons to change the parameter to the desired value.
- Press the button to save the value. The parameter will stop flashing to indicate that it has been saved.
Note:
If the editor is left inactive for the duration of the LCD Page Timer, it will be automatically exited for security reasons. The PIN number will be reset when the editor is exited manually or automatically.
Comprehensive module configuration can be done using the DSE Configuration Suite PC Software. Refer to DSE publication 057-322 DSE8600 Configuration Suite PC Software Manual available from www.deepseaelectronics.com.
Note:
Depending upon module configuration, some parameters in the Main and Running Editors may not be available. For more information, refer to DSE publication 057-324 DSE8600 Configuration Suite PC Software Manual available from www.deepseaelectronics.com.
This document details the installation and operation requirements of the DSEG8660 module and is part of the DSEGenset® range of products. The DSEG8660 module contains two software applications, Mains Controller and Group Controller. The DSEG8660 module has been designed to monitor the mains (utility) supply and automatically start/stop one or more generator sets equipped with DSEG8600 (Multi Set) controllers depending upon the status of the mains (utility) supply.
Configured as a Group Controller which allows the expansion of a system beyond the 64-module limit that is imposed by the capacity of a CAN bus.
Icon | Description |
![]() |
Mode Button In the G8660 the mode button is used to select Auto Mode, Test Mode, or Manual Mode. Pressing the button cycles through Auto mode > (Test mode) > Manual mode > Auto mode >. |
![]() |
Alarm Mute / Lamp Test This button silences the audible alarm in the controller, de-activates the Audible Alarm output (if configured) and illuminates all the LEDs on the module’s facia as a lamp test function. |
![]() |
RHS Breaker Button
Transfer to generator/bus LHS Breaker Button Transfer to Mains |
![]() |
Stop / Reset Mode
|
![]() |
Start
|
![]() |
Menu Navigation Used for navigating the instrumentation, event log and configuration screens. |
ACCESSING THE MAIN CONFIGURATION EDITOR
- Ensure the generator bus is dead and the module is in STOP mode
by pressing the (Stop/Reset) button.
- Navigate to Editor page:
Once selected, the page remains on the LCD display until the user selects a different page, or after an extended period of inactivity (LCD Page Timer), the module reverts to the home display.
- Press the Tick
button, the first ‘#’ changes to ‘0’. Press the Scroll
buttons to adjust it to the correct value.
- Press the Next Page
button when the first digit is correctly entered. The digit previously entered now shows as ‘#’ for security.
- Repeat this process for the other digits of the PIN number. Press the Previous Page
button to move back to adjust one of the previous digits.
- When the Tick
button is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not correct, the PIN must be re-entered.
- If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is displayed:
EDITING A PARAMETER
- Enter the editor as described above.
- Press the Next Page or Previous Page
buttons to cycle to the section to view/change.
- Press the Scroll
buttons to select the parameter to view/change within the currently selected section.
- To edit the parameter, press the Tick
button to enter edit mode. The parameter is highlighted to indicate editing.
- Press the Scroll
buttons or Next Page or Previous Page
buttons to change the parameter to the required value.
- Press the Tick
button to save the value. The parameter ceases flashing to indicate that it has been saved.
NOTE:
If the editor is left inactive for the duration of the LCD Page Timer, it is automatically exited to ensure security. The PIN number is automatically reset when the editor is exited (manually or automatically) to ensure security. Comprehensive module configuration is possible using the DSE Configuration Suite PC Software, refer to DSEpublication 057-322 DSE8600 Configuration Suite PC Software Manual available from www.deepseaelectronics.com.
NOTE:
Depending upon module configuration, some parameters in the Main and Running Editors may not be available. For more information refer to DSE publication 057-324 DSE8600 Configuration Suite PC Software Manual available from www.deepseaelectronics.com.
MAIN CONFIGURATION EDITOR PARAMETERS
Section | Parameter As Shown On Display | Values |
Display | Contrast | 0% |
Language | English, Other. | |
Current Date and Time | DD:MM:YY, hh:mm:ss | |
Alt Config | Default Config | Default Config / Alternative Config |
Bus | Start Delay On Load | 0 h 0 m 0 s |
Battery Under Voltage Warning | Active / Inactive | |
Battery Under Voltage Warning Delay | 0 h 0 m 0 s | |
Battery Under Voltage Warning | 0.0 V | |
Battery Over Voltage Warning | Active / Inactive | |
Battery Over Voltage Warning Delay | 0 h 0 m 0 s | |
Battery Over Voltage Warning | 0.0 V | |
Load Level For More Sets | 0 % | |
Load Level For Less Sets | 0 % | |
Ramp Up Rate | 0.0 % | |
Ramp Down Rate | 0.0 % | |
Bus Over Zero Seq Volts | Active / Inactive | |
Bus Over Zero Seq Volts | 0.0 V | |
Bus Under Pos Seq Volts | Active / Inactive | |
Bus Under Pos Seq Volts | 0.0 V | |
Bus Over Neg Seq Volts | Active / Inactive | |
Bus Over Neg Seq Volts | 0.0 V | |
Bus Asymmetry High | Active / Inactive | |
Bus Asymmetry High | 0.0 V | |
Enable MSC Compatibility | Active / Inactive | |
Mains | Under Voltage Trip | 0 V |
Over Voltage Trip | 0 V | |
Under Frequency Trip | 0 Hz | |
Over Frequency Trip | 0 Hz | |
Transient Delay | 0.0 s | |
CT Primary | 0 A Power Cycle After Exit | |
CT Secondary | 0 A Power Cycle After Exit | |
Full kW Rating | 0 kW | |
Full kVar Rating | 0 kvar | |
Mains Over Zero Seq Volt | Active / Inactive | |
Mains Over Zero Seq Volt | 0 V | |
Mains Under Pos Seq Volt | Active / Inactive | |
Mains Under Pos Seq Volt | 0 V | |
Mains Over Neg Seq Volt | Active / Inactive | |
Mains Over Neg Seq Volt | 0 V | |
Mains Asymmetry High | Active / Inactive | |
Mains Asymmetry High | 0 V | |
Timers | LCD Page Delay | 0 h 0 m 1 s |
LCD Sleep Timer | 0 h 0 m 0 s | |
Remote Start On Load | 0 h 0 m 0 s | |
Remote Start Off Load | 0 h 0 m 0 s | |
Telemetry Start | 0 h 0 m 0 s | |
Parallel Run Time | 0 h 0 m 0 s | |
Start form AMSC Master | 0 h 0 m 0 s | |
Transfer Time/ Load Delay | 0 h 0 m 0 s | |
Breaker Close Pulse | 0 h 0 m 0 s | |
Breaker Trip Pulse | 0 h 0 m 0 s | |
Bus Close Delay | 0 h 0 m 0 s |
Battery Under Voltage Warning Delay | 0 h 0 m 0 s | |
Battery Over Voltage Warning Delay | 0 h 0 m 0 s | |
Return Delay | 0 h 0 m 0 s | |
Generator Transient Delay | 0 s | |
Mains Fail | 0 s | |
Mains Transient Delay | 0 s | |
Mains Transfer Time | 0 s | |
Mains Over Zero Seq Volt Delay | 0.0 s | |
Mains Under Pos Seq Volt Delay | 0.0 s | |
Mains Over Neg Seq Volts Delay | 0.0 s | |
Mains Asymmetry High Delay | 0.0 s | |
Gen Over Zero Seq Volt Delay | 0.0 s | |
Gen Under Pos Seq Volt Delay | 0.0 s | |
Gen Over Neg Seq Volts Delay | 0.0 s | |
Gen Asymmetry High Delay | 0.0 s | |
Schedule | Schedule | Active / Inactive |
Schedule Bank 1 Period | Weekly / Monthly, | |
Island / Parallel / Off Load / Auto Start Inhibit, Week, Start Time, Run Time and Day. Selection (1 to 8) | Press the Tick![]() |
|
Schedule Bank 2 Period | Weekly / Monthly, | |
Island / Parallel / Off Load / Auto Start Inhibit, Week, Start Time, Run Time and Day. Selection (1 to 8) | Press the Tick![]() |
ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
- Press the Next Page
button to access the Main Menu page.
- Press the Previous Page
button followed by either the Scroll
buttons or the
Next Page or Previous Page buttons to locate the ‘Running’ Configuration Editor.
RUNNING CONFIGURATION EDITOR PARAMETERS
Section | Parameter As Shown On Display | Values |
Display | Contrast | 75 % |
Units Pressure | kPa, bar, psi | |
Units Temperature | °C, ° F | |
Units Volume | Litres. Imp gal. Us gal | |
Language | English, Other | |
Synchronising | Commissioning Screen | Active / Inactive |
Override Starting Alarms | Active / Inactive | |
Voltage Adjust
(Manual Mode Only With Gen Open) |
0% | |
Frequency Adjust
(Manual Mode Only With Gen Open) |
0% | |
Load Control | Injection Port | Active / Inactive |
Mains Decoupling Test Mode | Active / Inactive | |
Power Control Mode | Constant Power / Frequency-Power / Voltage- Power | |
Load Parallel Power | 0 % | |
Load Parallel kVArs | 0 % | |
Load Parallel PF | 0.00 pf | |
Governor Droop Offset | 0% | |
Governor Ramp Rate | 0% | |
AVR Droop Offset | 0% | |
AVR Ramp Rate | 0% | |
Load Priority | 1-64 |
ELECTRICAL SPECIFICATIONS
Parameter | Specification |
DC Supply Voltage | 8 VDC to 35 VDC |
Maximum Operating Current | 530 mA at 12 V
280 mA at 24 V |
Maximum Standby Current | 320 mA at 12 V
120 mA at 24 V |
Typical Power
(Controller On, Heater Off) |
3.8 W to 4.1 W |
Typical Power
(Controller On, Heater On) |
6.8 W to 7.1 W |
Mains Phase to Neutral Voltage Sensing | 15 VAC to 345 VAC |
Mains Phase to Phase Voltage Sensing | 26 VAC to 720 VAC |
Mains Voltage Sensing Offset from Earth | 100 VAC |
Volt-Free Output Rating | 8 A at 250 VAC, 5 A at 30 VDC |
REQUIREMENTS FOR UL CERTIFICATION
WARNING!:
More than one live circuit exists, see the diagram overleaf for further information.
Specification | Description |
Screw Terminal Tightening
Torque |
· 4.5 lb-in (0.5 Nm) |
Conductors | · Terminals suitable for connection of conductor size 13 AWG to 20 AWG (0.5 mm² to
2.5 mm²). · Conductor protection must be provided in accordance with NFPA 70, Article 240 · Low voltage circuits (35 V or less) must be supplied from the engine starting battery or an isolated secondary circuit. · The communication, sensor, and/or battery derived circuit conductors shall be separated and secured to maintain at least ¼” (6 mm) separation from the generator and mains connected circuit conductors unless all conductors are rated 600 V or greater. |
Current Inputs | · Must be connected through UL Listed or recognized isolating current transformers with the secondary rating of 5 A max. |
Communication Circuits | · Must be connected to communication circuits of UL Listed equipment |
DC Output Pilot Duty | · 0.5 A |
Mounting | · Suitable for flat surface mounting in Type 1 Enclosure Type rating with surrounding air temperature -22 ºF to +122 ºF (-30 ºC to +50 ºC)
· Suitable for pollution degree 3 environments when voltage sensing inputs do not exceed 300 V. When used to monitor voltages over 300 V device to be installed in an unventilated or filtered ventilation enclosure to maintain a pollution degree 2 environment. |
Maximum Operating Temperature | · 122 ºF (50 ºC) |
DIMENSIONS AND MOUNTING
Parameter | Specification |
Dimensions | 248 mm x 182.6 mm x 45.2 mm (9.76 ” x 7.18 ” x 1.77 ”) |
Panel Cutout | 220 mm X 160 mm (8.7” X 6.3”) |
Weight | 0.76 kg (1.67 lb) |
Operating Temperature with Standard Display | -30 ºC to +70 ºC (-22 ºF to +158 ºF) |
Operating Temperature with Heated Display | -40 ºC to +70 ºC (-40 ºF to +158 ºF) |
Storage Temperature | -40 ºC to +80 ºC (-40 ºF to +176 ºF) |
FIXING CLIPS
NOTE:
In conditions of excessive vibration, mount the control panel on suitable anti-vibration mountings.
The module is held into the control panel fascia using the supplied fixing clips.
- Withdraw the fixing clip screw (turn anticlockwise) until only the pointed end is protruding from the clip.
- Insert the three ‘prongs’ of the fixing clip into the slots in the side of the DSE module’s case.
- Pull the fixing clip backward (towards the back of the module) ensuring all three prongs of the clip are inside their allotted slots.
- Turn the fixing clip screws clockwise until they make contact with the panel fascia.
- Turn the screws a quarter of a turn to secure the module into the control panel’s fascia. Care must be taken not to over-tighten the fixing clip screws.
TYPICAL WIRING DIAGRAMS
NOTE:
A larger version of the Typical Wiring Diagram is available in the product’s operator manual, refer to DSE Publication: 057-323 DSE8660 Operator Manual available from www.deepseaelectronics.com for more information.
Mains Parallel Controller
Group Controller
Deep Sea Electronics Ltd.
- Tel: +44 (0)1723 890099
- Email: support@deepseaelectronics.com
- Web: www.deepseaelectronics.com.
Deep Sea Electronics Inc.
- Tel: +1 (815) 316 8706
- Email: usasupport@deepseaelectronics.com.
- Web: www.deepseaelectronics.com.
Documents / Resources
![]() |
DSE DSEG8660 Intelligent Controller [pdf] Instruction Manual DSEG8660 Intelligent Controller, DSEG8660, Intelligent Controller, Controller |