FP9000P Power Supply Panel
“
Product Information
Specifications
- Input voltage: Not specified
- Maximum current consumption: Not specified
- Output voltage: Not specified
- Output current: Not specified
- Maximum output current: Not specified
- Average charging current: Not specified
- Overcharging protection: Not specified
- Output for fault condition: Not specified
- Maximum section of the connecting wires: Not specified
- Back up battery: Not specified
- Degree of protection: Not specified
- Operational temperature range: Not specified
- Relative humidity resistance: Not specified
- Dimensions: Not specified
- Weight of the feeder: Not specified
Product Usage Instructions
Installation
- Dismantle the cover by unscrewing the fixings on the front
panel. - Drill the holes for the connecting wires. Observe the marked
places. - Install the required connecting wires to the module.
- It is recommended to install the multi-core connecting wires
with cable shoes. - Put the indicating PC board cable wires in the respective
terminals. Then install the cover by means of the fixings.
Service Schedule
No specific service schedule provided. Regular maintenance
checks are recommended.
Warranty
The manufacturer guarantees compliance with EN 54-4 standards.
The warranty period is 36 months from the date of sale, subject to
specific conditions. Contact your supplier for warranty
repairs.
FAQ
Q: What should I do if the yellow LED indicates a fault
condition?
A: If the yellow LED indicates a fault condition, check for low
battery, back up battery issues, interrupted fuses, or mains
voltage failure. Contact an authorized technician if needed.
Q: Where can I find replacement parts for the power
supply?
A: Replacement parts can be obtained through authorized
suppliers or directly from DMTech Ltd. Ensure to use genuine parts
for optimal performance.
“`
“DMTech” Ltd, Pleven
POWER SUPPLY TYPE FP9000P
GENERAL DESCRIPTION
Power supply type FP9000P is an independent feeding device of combined type back up battery and batterycharger. Its function is to ensure continuous power supply for devices in fire-alarming and fire-detecting installations and automation of the fire protection equipment. The feeder complies with the provisions set in the European Standard EN 54-4. FP9000 P consists of: – feeding module; – two back up batteries; thee back up batteries are not included in the content of the delivery. – Connecting terminals and a fuser 220V The power supply front panel provides indication for the following conditions: – Duty Mode (green LED) – Fault condition (yellow LED). The fault condition could mean voltage failure 220V or interrupted fuse AC;
faultor missing back up battery; interrupted fuse ACU; interrupted fuse User ; – Low battery, back up battery or interrupted fuse ACU (yellow LED); – mains voltage failure 220V AC or interrupted fuse AC (yellow LED); – interrupted fuse User (yellow LED). Upon fault condition the relay output is switched, too. On the supply module the following terminals are located for connection to: – the relay contacts for fault condition; – voltage terminal 28V / 2.0A.
Page 1 of 3
1. TECHNICAL DATA
Input voltage Maximum current consumption Output voltage Output current Maximum output current Average charging current Overcharging protection Output for fault condition Maximum section of the connecting wires Back up battery Degree of protection Operational temperature range Relative humidity resistance Dimensions Weight of the feeder
(187-253)V AC, 50/60 Hz 110V (17-27.6)V DC 4.0 4.5 for 15 minutes 0.8 A at voltage < 17V relay, potential free switching, 1 / 30V DC 2,5 mm2 212V / 9 Ah IP 40 -5º up to +40º (92±3)% at 40º 305250100 mm 1.0 kg
2. CONTENT OF DELIVERY
Power supply FP9000P Instruction Manual Fuse 4A Connecting bridge for the back up batteries Package
1 pc. 1 pc. 1 pcs. 1 pc. 1 pc.
Page 2 of 3
3. INSTALLATION
To install the power supply please follow the sequence: 1. Dismantle the cover by unscrewing the fixings on the front panel. 2. Drill the holes for the connecting wires. Observe the marked places. 3. Install the required connecting wires to the module. 4. It is recommended to install the multi-core connecting wires with cable shoes.
5. Put the indicating PC board cable wires in the respective terminals . Then install the cover by means of the fixings.
4. SERVICE SCHEDULE
1. Inspection for visible physical damages – monthly 2. Satisfactory operation test monthly
5. WARRANTY
The manufacturer guarantees that the product complies with EN 54-4. The warranty period is 36 months from the date of sale, provided that:
– storage and transport conditions are met; – the commissioning is carried out by authorized persons; – the operating requirements set out in this manual are observed; – the defects are not caused by natural phenomena and failures of the power supply network. If a warranty repair is required, please contact your supplier.
DMTech wishes you pleasant work!
Page 3 of 3