DKS 9550 Gate Operator User Manual

9550 Gate Operator

Specifications

Model Horsepower Volts Operator and Heater Amps Wire Size / Max Distance in Feet
9210 1 115 VAC 16.3 50 / 80 / 130 / 210 (12 AWG, 10 AWG, 8 AWG, 6 AWG)
9210 1 208 VAC 8.4 180 / 290 / 470 / 750 (12 AWG, 10 AWG, 8 AWG, 6 AWG)

Product Usage Instructions

Power Connection

  1. Shut off the AC input power to the operator from the circuit
    breaker.
  2. Remove clear plastic electronic box cover and the locknuts
    inside to access the electronic box.
  3. Connect the 2 heater power wires according to the operator’s AC
    power type.

Mounting Plate Installation

  1. Bolt the mounting plate to the heater using the supplied bolts
    and nuts.
  2. Slide the heater into the gear reducer bracket and secure it
    with the provided bolts.
  3. Run the power wires as instructed, keeping them away from
    heater vents and ensuring they are not pinched in the electronic
    box’s folding hinge.

FAQ

Q: Do I need to drill holes in the gear reducer bracket for
securing bolts?

A: Older models may require drilling two holes in the gear
reducer bracket for securing the bolts to mount the heater.

“`

-195 / -197 / -198 HEATER KITS
These kits are designed for the 9200 · 9500 · 6300 208 & 230 VAC Input power or 460 VAC Input power · 6550 208 & 230 VAC Input power or 460 VAC Input power · 6555 230 VAC Input power · 9000 208 & 230 VAC Input power or 460 VAC Input power · 9024 AC powered 230 VAC ONLY · 9150 208 & 230 VAC Input power or 460 VAC Input power · 1601/1602/1603 208 & 230 VAC Input power or 460 VAC Input power model gate operators. For cold weather climates where temperatures routinely drop below 10°F (-12°C). A built-in thermostat will automatically control the temperature inside operator housing. Find your “SPECIFIC” operator on the next 15 pages.

DoorKing Part Numbers:
1601-195 Kit
115 VAC Model 6.6 Amp
1601-197 Kit
208/230 VAC Models 3.3 Amp
1601-198 Kit
460 VAC Models 3.3 Amp

9200 Specifications Tables

High Voltage AC Input Power for the 9200 Gate Operator with a Heater
The 9200 draws significant power and should have a “Dedicated” circuit breaker at the power source. If power wiring is greater than the maximum distance shown, it is recommended that a service feeder be installed. When large gauge wire is used, a separate junction box must be installed for the operator connection. Wire run calculations are based on NEC 310.15(B)(16) with a maximum voltage drop of 3%. These wire runs are a general guideline but it is highly suggested that individual calculations are made for your specific installation as these distances may vary. Never run low voltage rated wire insulation in the same conduit as high voltage rated wire insulation.

High voltage AC input wire size and distance limitations for a 9210 – 115 VAC with a heater.

Phase

Model Horsepower Volts

Operator and
Heater Amps

Wire Size / Max Distance in Feet
12 AWG 10 AWG 8 AWG 6 AWG

Heater Kit P/N

9210

1

115 VAC

16.3

50

80

130

210

1601-195

Note: Operator should have a “Dedicated 20 Amp” minimum circuit breaker at the power source.

High voltage AC input wire size and distance limitations for a 9200 – 208/230 VAC OR 460 VAC with a heater.

Phase

Motor Model Horsepower Volts

Operator and
Heater Amps

Wire Size / Max Distance in Feet
12 AWG 10 AWG 8 AWG 6 AWG

Heater Kit P/N

208 VAC

8.4

180

290

470

750

9210

1

230 VAC

8.3

210

330

530

840

208 VAC

15.0

100

160

260

420

9220

2

230 VAC

14.8

110

180

290

470

1601-197 1601-197 1601-197 1601-197

208 VAC

6.7

270

430

680

1090

9210

1

230 VAC

6.6

300

480

770

1220

460 VAC

5

800

1280

2040

3240

208 VAC

10.0

180

290

460

730

9220

2

230 VAC

9.6

210

330

530

840

460 VAC

6.6

610

970

1540

2450

208 VAC

13.2

130

210

340

550

9230/9240

3

230 VAC

13.0

150

240

390

620

460 VAC

8.0

300

800

1100

2000

208 VAC

16.2

110

170

280

450

9235

3

230 VAC

16.0

120

200

310

500

460 VAC

8.0

300

800

1100

2000

1601-197 1601-197 1601-198 1601-197 1601-197 1601-198 1601-197 1601-197 1601-198 1601-197 1601-197 1601-198

1601-167-J-8-25

Installation on next page.
Copyright 2025 DoorKing®, Inc. All rights reserved. 1

ON OFF
ON OFF

9200 Installation of Heater

DoorKing Part Numbers

1601-195 Kit 1601-197 Kit 1601-198 Kit

115 VAC Model 208/230 VAC Models 460 VAC Models

6.6 Amp

3.3 Amp

3.3 Amp

Shut off the AC input power to the Wire run tables on previous page.

operator from the circuit breaker.

Power Connection

Mounting Plate

Remove clear plastic electronic box cover. Remove the 3 locknuts inside the electronic box to swing box open.

Heater

Connect the 2 heater power wires according to operator AC power type.

Bolt mounting plate to heater with 2 supplied bolts and nuts.

DANGER

Slide heater into the gear reducer bracket as shown below and bolt heater to the bracket with 2 supplied securing bolts.

HIGH VOLTAGE!

Run the 2 power wires as shown below. Keep wires away from the heater vents and make sure wires do not get pinched in the electronic box’s folding hinge.

DAHNOTG! ER

Hot Neu
L1 L2 L3 L4 L5
115 VAC
1601-195 Kit

DANGER
HIGH VOLTAGE!

CCVMSALEEONARHDS/ICCAEICSAOCSLLENNUARSFTLCIOI/A2FUR2IRLEM.-D23GS2NTAT5OOOT.E24O7HPPERAT53O38R2 VOLTS

AMPS

MADXoGoArKTiEngL,OIAncD.,

PHASE 60 Hz
Inglewood, CA

WARNING
SaDRpDoOMnareoopEtdaoehnnORdrpfooawreoetttVIrehweOasaiIgttllnoleeaNUoaefntwggrpedGS’aasecottioeenmhnIpG.iilgNlaslydeanArmwtJuaeeTnhanoUpdlevEtanaiRoontnhgbgpCdYas.loatstAreryaOuwfNaicenraRtteiylgokaCainnDtitsshAes.rtEioaUnruruAescgSaitTghioEhHnt s.

1601-167-J-8-25

Securing Bolts
Power Wires Clear Plastic Electronic Box Cover
Access Door

GRBreeaadcrukceetr

Electronic Box

Power Wires

1
Locknut

2
Locknut
3
Locknut

Note: The gear reducer bracket may need to be spread apart a little to get the heater to slide in. Older 9200s must have 2 holes drilled in the gear reducer bracket for the securing bolts.
2

Hot Hot Hot
L1 L2 L3 L4 L5
208/230/460 VAC
1-Phase and 3-Phase
1601-197 Kit (208/230 VAC) 1601-198 Kit (460 VAC)

Heater Switch for: 115/208/230 VAC

DANGER HOT!

ON
OFF OFF – Turns
the heater off.

ON – Normal setting.
Automatically turns the heater ON when the temperature drops below 40°F (4°C) inside the operator, and turns the heater OFF when the temperature rises above 55°F (13°C) inside the operator.

Note: Model 1601-198 460 VAC does NOT have a On/Off heater switch. Heater must be turned off at the operator’s input power source, circuit breaker, external power disconnect switch, etc.

120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.

9500 Specifications Table

DoorKing Part Numbers:
1601-197 Kit
208/230 VAC Models 3.3 Amp
1601-198 Kit
460 VAC Models 3.3 Amp

High Voltage AC Input Power for the 9500 Gate Operator with a Heater

The 9500 draws significant power and should have a “Dedicated” circuit breaker at the power source.
If power wiring is greater than the maximum distance shown, it is recommended that a service feeder be installed. When large gauge wire is used, a separate junction box must be installed for the operator connection. Wire run calculations are based on NEC 310.15(B)(16) with a maximum voltage drop of 3%. These wire runs are a general guideline but it is highly suggested that individual calculations are made for your specific installation as these distances may vary.
Never run low voltage rated wire insulation in the same conduit as high voltage rated wire insulation.

High voltage AC input wire size and distance limitations for a 9500 – 208/230 VAC OR 460 VAC with a heater.

Motor Model Horsepower Phase

Volts

Operator and
Heater Amps

Wire Size / Max Distance in Feet
12 AWG 10 AWG 8 AWG 6 AWG

Heater Kit P/N

9550/9555

5

208 VAC

16.2

110

175

280

3

230 VAC

16.1

125

195

315

450 1601-197
500

460 VAC

9.7

410

660

1050

1650

1601-198

208 VAC

24.4

n/a

100

160

1

230 VAC

22.4

n/a

120

190

260

1601-197

310

460 VAC

12.5

270

430

700

1100

1601-198

9570/9575

7

208 VAC

25.0

n/a

110

180

3

230 VAC

23.8

n/a

130

210

290

1601-197

340

460 VAC

13.5

290

470

750

1200

1601-198

208 VAC

35.0

n/a

n/a

110

180

1

230 VAC

32.0

n/a

n/a

130

1601-197 210

460 VAC

17.0

200

320

510

820

1601-198

208 VAC

29.3

n/a

90

150

3

230 VAC

26.3

n/a

120

190

250 1601-197
300

9590/9595

10

460 VAC

15.3

260

410

660

1060

1601-198

208 VAC

45.5

n/a

n/a

n/a

130

1

230 VAC

41.4

n/a

n/a

n/a

1601-197 160

460 VAC

21.6

n/a

250

400

640

1601-198

WARNING RpDeoaDaoatrOSdohnnopMdonwopEewotefrhRratrOsniealttaeeeeItalVerlOngogo’sdgaIfawUtaNtmpieetnceeSaiGhoo.sgninpalumdIlltyaGeerNolewapvanAJniahnndttUTedoghno.EsRpobgalrsafaYCetywtrteuyaiAnOaclikrtnNgieRotsaahtntrreCisuosD.acuAirtngEieohUasAnigsST.hEtH

CAUTION PTCEBBAyheetooteervfleots-emsCBorreMoonpIvnlstAatieesntDyrtlgeAiRAIsmrnTecnejoposduFtnurLiOoynlnitrfpegAtIeLcnnOTrtidefaopMtdtieWoLnirnFrigaif.orlttolC.romRorTveofrOesoMrupmlOeotrdnTIanelhtyroeD.arsatBeeFmerEaaSymgueere-eTo

WARNING

DTPFShMisEeORntIVraOnIcNUe GSis foIGNr AvJehTUicERlesCYoAnOlyN.RPCedDAesEUtrAiaSnTsEH Pbgmseptiameamreuofoitreneeposestrrtegtrloyasognc,unromytoaliessionnetotaoeeosdsanl.vtep.aro,raeteuparsdscecetneehotwrnptiiaaoolskaiduttnoerohrrtasereroeot.panmoeuudrtscoeailpstntpnehiirtceagmeirorracTa!iornlltyaowewcTprsenhateid.hnereeDnergv’gisgniedacagnmteeet.tv)eraiiacsnsopehurcmaa(aplsllpeluaannacnyobthdtlienabostehfae

53382

CAONNSFIO/URLM-3S2T5O E OPERATOR CAN/CCSEARTCI2F2IE.D2 NTOO. 247 VEHICULAR GAT HP

CLASS

MODEL

PHASE

SERIAL

60 Hz

VOLTS

AMPS

MAX

GATE LOAD DoorKing, Inc.,

Inglewood,

CA

Installation on next page.

1601-167-J-8-25

120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.
3

9500 Installation of Heater

Mounting Plate Heater ON OFF

Mount heater to heater bracket with two screws and locknuts.

Wire run tables on previous page.

DoorKing Part Numbers:
1601-197 Kit
208/230 VAC Models 3.3 Amp
1601-198 Kit
460 VAC Models 3.3 Amp

he(aCtHeaernastmeifronBueranccetkstewstaory)

DAHNOGT!ER

Keep wires away from the heater vents.

25 A 23 20
TEST PUteScHhnTiOciaOnPuEsRe AoTnEly
OPEN CLOSE STOP

Shut off the AC input power to the operator from the circuit breaker.

Mount heater bracket to existing holes in base of operator with two nuts and bolts.

ON OFF
BHreaactkeert

Operator Base

Power Connection
Connect the 2 heater power wires according to operator AC power type.
DANGER
HIGH VOLTAGE!

Hot Hot Hot
L1 L2 L3 L4 L5
208/230/460 VAC
1-Phase and 3-Phase
1601-197 Kit (208/230 VAC) 1601-198 Kit (460 VAC)

Run the 2 power wires as shown. Make sure wires do not get pinched in the electronic box’s folding hinge.

25 A 23

20

TEST

PUteScHhnTiOciaOnPuEsRe AoTnEly

OPEN CLOSE
STOP

1601-167-J-8-25

Power Wires
1 Remove the
3 locknuts inside the electronic box to swing box open.
2

Heater Switch for: 208/230 VAC

DANGER HOT!

ON
OFF OFF – Turns
the heater off.

ON – Normal setting.
Automatically turns the heater ON when the temperature drops below 40°F (4°C) inside the operator, and turns the heater OFF when the temperature rises above 55°F (13°C) inside the operator.

Note: Model 1601-198 460 VAC does NOT have a On/Off heater switch. Heater must be turned off at the operator’s input power source, circuit breaker, external power disconnect switch, etc.

Electronic Box

3
4

120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.

6300 – 208/230 VAC Input Power ONLY Install
IMPORTANT: Your gate operator MUST have the optional high voltage kit installed on it.

DoorKing Part Number:
1601-197 Kit
208/230 VAC Models 3.3 Amp

High voltage AC input wire size and distance limitations for a 6300 208/230 VAC Input Power with a heater.

Model

Horsepower

Volts

Operator and
Heater Amps

12 AWG

Wire Size / Max Distance in Feet

10 AWG

8 AWG

6 AWG

Heater Kit P/N

1/2 HP

208/230

6.0

260

410

660

1050

1601-197

6300

1 HP

208/230

8.2

190

300

480

770

1601-197

Wire run distances are shown for a single 6300 operator with heater. In bi-parting (dual) gate applications, reduce the distance by one-half.

DAHNOGT!ER

Heater Locknut

Step-Down Transformer

Shut off the AC input power wire from the main circuit breaker.

MounPtilnagte Instatlhl roenadeexdistsitnugds
Heater MUST be installed on mounting plate.

To gate operator power terminal

DANGER
HIGH VOLTAGE!

High Voltage Kit Configured for
208 VAC
OR
230 VAC

3rd Leg 2nd Leg

208 VAC Input Power
Wire
OR
230 VAC Input Power
Wire

OFF ON
Step-Down Transformer
OFF ON

HDOATN! GER

Heater Switch

a1n6d0F1a-1n9A7sHseematbelry

ON ON – Normal setting. Automatically
turns the heater ON when the temperature

drops below 40°F (4°C) inside the

operator, and turns the heater OFF when

the temperature rises above 55°F (13°C)

OFF

inside the operator.
OFF – Turns the heater off.

1601-167-J-8-25

Keep wires away from the heater vents.

High Voltage Kit P/N 2600-266 (Sold sepatately) See instruction sheet for more information.

1st Leg

Use only two legs of the incoming 3-phase power and terminate the 3rd leg.

To secondary operator heater if installed.

Wire heater(s) DIRECTLY from input power wire.
DO NOT wire heater to gate operator power terminal or damage will occur.

Note for Bi-Parting Dual Gate Operators: Run two (AWG 16-600 volt insulation) power wires from the input power wire through the interconnection cable conduit to power the secondary operator’s heater.
DO NOT wire secondary heater directly to the secondary gate operator’s terminal or damage will occur.

RESET

AC

Note: Heater will NOT turn off

POWER

when using the gate operator

OFF

ON/OFF power switch.

5

120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.

6300 – 460 VAC Input Power ONLY Installation
IMPORTANT: Your gate operator MUST have the optional high voltage kit installed on it.

DoorKing Part Number:
1601-198 Kit
460 VAC Models 3.3 Amp

High voltage AC input wire size and distance limitations for a 6300 208/230 VAC Input Power with a heater.

Model

Horsepower

Volts

Operator and
Heater Amps

12 AWG

Wire Size / Max Distance in Feet

10 AWG

8 AWG

6 AWG

Heater Kit P/N

1/2 HP

460

4.7

740

1180

1870

2980

1601-198

6300

1 HP

460

5.7

610

970

1540

2460

1601-198

Wire run distances are shown for a single 6300 operator with heater. In bi-parting (dual) gate applications, reduce the distance by one-half.

DAHNOGT!ER

Heater Locknut

Step-Down Transformer

Shut off the AC input power wire from the main circuit breaker.

MounPtilnagte Instatlhl roenadeexdistsitnugds

DANGER
HIGH VOLTAGE!
3rd Leg

Heater MUST be installed on mounting plate.

To gate operator power terminal

High Voltage Kit Configured for 460 VAC ONLY

2nd Leg

460 VAC Input Power
Wire

Step-Down Transformer
OFF ON

HDOATN! GER
a1n6d0F1a-1n9A8sHseematbelry
Turning Heater On/Off
Model 1601-198 460 VAC does NOT have a On/Off heater switch. Heater must be turned off at the operator’s input power source, circuit breaker, external power disconnect switch, etc.
1601-167-J-8-25

Keep wires away from the heater vents.

High Voltage Kit P/N 2600-266 (Sold sepatately) See instruction sheet for more information.

1st Leg

Use only two legs of the incoming 3-phase power and terminate the 3rd leg.

To secondary operator heater if installed.

Wire heater(s) DIRECTLY from input power wire.
DO NOT wire heater to gate operator power terminal or damage will occur.

Note for Bi-Parting Dual Gate Operators: Run two (AWG 16-600 volt insulation) power wires from the input power wire through the interconnection cable conduit to power the secondary operator’s heater.
DO NOT wire secondary heater directly to the secondary gate operator’s terminal or damage will occur.

RESET

AC

Note: Heater will NOT turn off

POWER

when using the gate operator

OFF

ON/OFF power switch.

6

120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.

6550 – 208/230 VAC Input Power ONLY Install
IMPORTANT: Your gate operator MUST have the optional high voltage kit installed on it.

DoorKing Part Number:
1601-197 Kit
208/230 VAC Models 3.3 Amp

High voltage AC input wire size and distance limitations for a 6550 208/230 VAC Input Power with a heater.

Model

Horsepower

Volts

Operator and
Heater Amps

12 AWG

Wire Size / Max Distance in Feet

10 AWG 8 AWG

6 AWG

Heater Kit P/N

1 HP

208/230

8.2

190

300

480

770

1601-197

66550500

Wire run distances are shown for a single 6550 operator with heater. In bi-parting (dual) gate applications, reduce the distance by one-half.

Shut off the AC input power wire from the main circuit breaker.

To gate operator power terminal
Step-Down Transformer

DANGER
HIGH VOLTAGE!

High Voltage Kit Configured for
208 VAC
OR
230 VAC

3rd Leg 2nd Leg

208 VAC Input Power
Wire
OR
230 VAC Input Power
Wire

OFF ON
Step-Down Transformer
OFF ON

a1n6dD0F1Aa-1Hn9NAO7sGHTsee!maEtbeRlry
MounPtilnagte

Heater MUST

Heater Switch

Use Existing 2 Bolts and Nuts

be installed on mounting plate.

ON ON – Normal setting. Automatically
turns the heater ON when the temperature

drops below 40°F (4°C) inside the

operator, and turns the heater OFF when

the temperature rises above 55°F (13°C)

RESET

OFF

inside the operator.
OFF – Turns the heater off.

AC POWER

OFF

Keep wires away from the heater vents.

High Voltage Kit P/N 2600-266 (Sold sepatately) See instruction sheet for more information.

1st Leg

Use only two legs of the incoming 3-phase power and terminate the 3rd leg.

Wire heater(s) DIRECTLY from input power wire. DO NOT wire heater to gate operator power terminal or damage will occur.
Note: Heater will NOT turn off when using the gate operator ON/OFF power switch.

To secondary operator heater
if installed.
Note for Bi-Parting Dual Gate Operators: Run two (AWG 16-600 volt insulation) power wires from the input power wire through the interconnection cable conduit to power the secondary operator’s heater. DO NOT wire secondary heater directly to the secondary gate operator’s terminal or damage will occur.

1601-167-J-8-25

120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.
7

6550 – 460 VAC Input Power ONLY Installation
IMPORTANT: Your gate operator MUST have the optional high voltage kit installed on it.

DoorKing Part Number:
1601-198 Kit
460 VAC Models 3.3 Amp

High voltage AC input wire size and distance limitations for a 6550 460 VAC Input Power with a heater.

Model

Horsepower

Volts

Operator and
Heater Amps

12 AWG

Wire Size / Max Distance in Feet

10 AWG 8 AWG

6 AWG

Heater Kit P/N

1 HP

460

5.7

850

1350

2150

3420

1601-198

66550500

Wire run distances are shown for a single 6550 operator with heater. In bi-parting (dual) gate applications, reduce the distance by one-half.

Shut off the AC input power wire from the main circuit breaker.

DANGER
HIGH VOLTAGE!
3rd Leg

To gate operator power terminal
Step-Down Transformer

High Voltage Kit Configured for 460 VAC ONLY

2nd Leg

460 VAC Input Power
Wire

Step-Down Transformer
OFF ON

a1n6dD0F1Aa-1Hn9NAO7sGHTsee!maEtbeRlry
MounPtilnagte

Use Existing 2 Bolts and Nuts

Heater MUST be installed on mounting plate.

Turning Heater On/Off
Model 1601-198 460 VAC does NOT have a On/Off heater switch. Heater must be turned off at the operator’s input power source, circuit breaker, external power disconnect switch, etc.
AC POWER
OFF

RESET

Keep wires away from the heater vents.

High Voltage Kit P/N 2600-266 (Sold sepatately) See instruction sheet for more information.

1st Leg

Use only two legs of the incoming 3-phase power and terminate the 3rd leg.

Wire heater(s) DIRECTLY from input power wire. DO NOT wire heater to gate operator power terminal or damage will occur.
Note: Heater will NOT turn off when using the gate operator ON/OFF power switch.

To secondary operator heater
if installed.
Note for Bi-Parting Dual Gate Operators: Run two (AWG 16-600 volt insulation) power wires from the input power wire through the interconnection cable conduit to power the secondary operator’s heater. DO NOT wire secondary heater directly to the secondary gate operator’s terminal or damage will occur.

1601-167-J-8-25

120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.
8

6555 Installation of Heater

DoorKing Part Number:
1601-197 Kit
208/230 VAC Models 3.3 Amp

If power wiring is greater than the maximum distance shown, it is recommended that a service feeder be installed. When large gauge wire is used, a separate junction box must be installed for the operator connection. The wire table is based on stranded copper wire. Wire run calculations are based on an AC power source with a 3% voltage drop on the power line, plus an additional 10% reduction in distance to allow for other losses in the system.
High voltage AC input wire size and distance limitations for a 6555 230 VAC with a heater.

Model

Horsepower

Volts

Operator and
Heater Amps

12 AWG

Wire Size / Max Distance in Feet

10 AWG

8 AWG

6 AWG

Heater Kit P/N

P6o56w5A5e5C2r4ed

2

230

14.8

110

180

290

470

1601-197

Shut off the AC input power to the operator from the circuit breaker.
Operator Power Connection

Power Wires

Hot Hot

Run power wires through chassis.

230 VAC
1601-197 Kit (208/230 VAC)
DANGER
HIGH VOLTAGE!

Heater Switch

ON OFF

ON – Normal setting. Automatically turns the
heater and fan ON when the temperature drops below 40°F (4°C) inside the operator, and turns the heater and fan OFF when the temperature rises above 55°F (13°C) inside the operator.
OFF – Turns the heater and fan off.

OFF ON

DAHNOGT!ER
MounPtilnagte

Keep wires away from the heater vents.

Use Existing 2 Bolts and Nuts

1601-167-J-8-25

Copyright 2020 DoorKing®, Inc. All rights reserved. 9

120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.

9000 – 208/230 VAC Input Power ONLY Install
IMPORTANT: Your gate operator MUST have the optional high voltage kit installed on it.

DoorKing Part Number:
1601-197 Kit
208/230 VAC Models 3.3 Amp

High voltage AC input wire size and distance limitations for 9000 208/230 VAC Input Power with a heater.

Model

Horsepower

Volts

Operator and
Heater Amps

12 AWG

Wire Size / Max Distance in Feet

10 AWG

8 AWG

6 AWG

Heater Kit P/N

1/2 HP

208/230

6.0

260

410

660

1050

1601-197

9000

1 HP

208/230

8.2

190

300

480

770

1601-197

Wire run distances are shown for a single 9000 operator with heater. In bi-parting (dual) gate applications, reduce the distance by one-half.

Note: Operator illustrated without

some components to better show

heater mounting location.

BacIkntshotrfaeElalldeocentdMreosxontiiuusctndiBntsiognxg Plate

Heater MUST be installed on mounting plate.

DANGHOETR!

DAHNOGT!ER

1601-197 Heater and Fan Assembly
Heater Locknut

Shut off the AC input power wire from the main circuit breaker.

ON OFF

STrtaenps-Dfoorwmner

ON OFF

Heater Switch
ON – Normal setting. Automatically
turns the heater ON when the temperature drops below 40°F (4°C) inside the operator, and turns the heater OFF when the temperature rises above 55°F (13°C) inside the operator.
OFF – Turns the heater off.

1601-167-J-8-25

Power
PUSHteTcOhnOicPiEanRAusTeEonly

Keep wires away from the heater vents.
To gate operator power terminal

DANGER
HIGH VOLTAGE!

High Voltage Kit Configured for
208 VAC
OR
230 VAC

3rd Leg 2nd Leg

208 VAC Input Power
Wire
OR
230 VAC Input Power
Wire

Step-Down Transformer

High Voltage Kit P/N 2600-266 (Sold sepatately) See instruction sheet for more information.

1st Leg

Use only two legs of the incoming 3-phase power and terminate the 3rd leg.

To secondary operator heater if installed.

Wire heater(s) DIRECTLY from input power wire. DO NOT wire heater to gate operator power terminal or damage will occur.
Note: Heater will NOT turn off when using the gate operator ON/OFF power switch.

ON OFF
Note for Bi-Parting Dual Gate Operators: Run two (AWG 16-600 volt insulation) power wires from the input power wire through the interconnection cable conduit to power the secondary operator’s heater.
DO NOT wire secondary heater directly to the secondary gate operator’s terminal or damage will occur.

120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.
10

9000 – 460 VAC Input Power ONLY Installation
IMPORTANT: Your gate operator MUST have the optional high voltage kit installed on it.

DoorKing Part Number:
1601-198 Kit
460 VAC Models 3.3 Amp

High voltage AC input wire size and distance limitations for 9000 460 VAC Input Power with a heater.

Model

Horsepower

Volts

Operator and
Heater Amps

12 AWG

Wire Size / Max Distance in Feet

10 AWG

8 AWG

6 AWG

Heater Kit P/N

1/2 HP

460

4.7

1160

1850

2940

4670

1601-198

9000

1 HP

460

5.7

850

1350

2150

3420

1601-198

Wire run distances are shown for a single 9000 operator with heater. In bi-parting (dual) gate applications, reduce the distance by one-half.

Note: Operator illustrated without

some components to better show

heater mounting location.

BacIkntshotrfaeElalldeocentdMreosxontiiuusctndiBntsiognxg Plate

Heater MUST be installed on mounting plate.

DANGHOETR!

DAHNOGT!ER

1601-198 Heater and Fan Assembly
Heater Locknut

Shut off the AC input power wire from the main circuit breaker.

Keep wires away from the heater vents.

DANGER
HIGH VOLTAGE!

STrtaenps-Dfoorwmner

Turning Heater On/Off
Model 1601-198 460 VAC does NOT have a On/Off heater switch. Heater must be turned off at the operator’s input power source, circuit breaker, external power disconnect switch, etc.

1601-167-J-8-25

Power
PUSHteTcOhnOicPiEanRAusTeEonly

To gate operator power terminal

High Voltage Kit Configured for 460 VAC ONLY

3rd Leg

2nd Leg

460 VAC Input Power
Wire

Step-Down Transformer

High Voltage Kit P/N 2600-266 (Sold sepatately) See instruction sheet for more information.

1st Leg

Use only two legs of the incoming 3-phase power and terminate the 3rd leg.

To secondary operator heater if installed.

Wire heater(s) DIRECTLY from input power wire. DO NOT wire heater to gate operator power terminal or damage will occur.
Note: Heater will NOT turn off when using the gate operator ON/OFF power switch.

ON OFF
Note for Bi-Parting Dual Gate Operators: Run two (AWG 16-600 volt insulation) power wires from the input power wire through the interconnection cable conduit to power the secondary operator’s heater.
DO NOT wire secondary heater directly to the secondary gate operator’s terminal or damage will occur.

120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.
11

9024 AC Powered – 230 VAC Installation

DoorKing Part Number:
1601-197 Kit
208/230 VAC Models 3.3 Amp

If power wiring is greater than the maximum distance shown, it is recommended that a service feeder be installed. When large gauge wire is used, a separate junction box must be installed for the operator connection. The wire table is based on stranded copper wire. Wire run calculations are based on an AC power source with a 3% voltage drop on the power line, plus an additional 10% reduction in distance to allow for other losses in the system.
High voltage AC input wire size and distance limitations for a 9024 AC Powered 230 VAC with a heater.

Model

Horsepower

Volts

Operator and
Heater Amps

12 AWG

Wire Size / Max Distance in Feet

10 AWG

8 AWG

6 AWG

Heater Kit P/N

Po9wA0eC2r4ed

Quadra Drive

230

4.2

410

DC Motor

ONLY

660

1050

1670

1601-197

In bi-parting (dual) gate applications, high voltage AC power is required for EACH 9024 AC Powered 230 VAC operator with heater.

Shut off the AC input

power to the operator

Mounting Heater Existing Operator Threaded Stud

from the circuit breaker

Locate existing threaded studs in operator. Heater

and DC power switch on

MUST be on mounted

operator

on mounting plate with 2 supplied locknuts.

Note: Operator illustrated without some components

Mounting

Plate
1601H-1ea9an7tAedsrFsaenmbly

to better show heater

Back

of

Electronic Box
Heater

mounting location.

Existing Operator Threaded
Stud

ON OFF

DAHNOTG! ER

ON
OFF
Power Wires

Keep wires away from the heater vents.

Heater Switch

Operator Power Connection

ON OFF

DANGER

HOT!

ON – Normal setting. Automatically turns

HOT Hot

the heater ON when the temperature

drops below 40°F (4°C) inside the operator, and turns the heater OFF when

230 VAC

the temperature rises above 55°F (13°C) 1601-197 Kit (208/230 VAC)
inside the operator.

OFF – Turns the heater off.

DANGER

HIGH VOLTAGE!

9024 AC Powered 230 VAC ONLY
1601-167-J-8-25 12

120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.

9150 – 208/230 VAC Input Power ONLY Install
IMPORTANT: Your gate operator MUST have the optional high voltage kit installed on it.

DoorKing Part Number:
1601-197 Kit
208/230 VAC Models 3.3 Amp

High voltage AC input wire size and distance limitations for a 9150 208/230 VAC Input Power with a heater.

Model

Horsepower

Volts

Operator and
Heater Amps

12 AWG

Wire Size / Max Distance in Feet

10 AWG

8 AWG

6 AWG

Heater Kit P/N

1/2 HP

208/230

6.0

260

410

660

1050

1601-197

9150

1 HP

208/230

8.2

190

300

480

77

1601-197

In bi-parting (dual) gate applications, high voltage AC power is required for EACH 9150 operator with heater.

OFF ON
Heater

Note: Operators illustrated without some components to better show heater mounting location.

Shut off the AC input power wire from the main circuit breaker.

DANGER HOT!

RESET
Install on existing threaded studs

Heater Location

MPloatuenting

LHoecaktneurt
OFF ON

TSratenps-fDoromwenr
Heater MUST be installed on mounting plate. Keep wires away from the heater vents.

1601-197 Heater and Fan Assembly

Heater

DAHNOGT!ER

Switch

ON

ON – Normal setting. Automatically
turns the heater ON when the temperature

drops below 40°F (4°C) inside the

operator, and turns the heater OFF when

the temperature rises above 55°F (13°C)

OFF

inside the operator.
OFF – Turns the heater off.

1601-167-J-8-25

To gate operator power terminal

Step-Down Transformer

DANGER
HIGH VOLTAGE!

High Voltage Kit Configured for
208 VAC
OR
230 VAC

3rd Leg 2nd Leg

208 VAC Input Power
Wire
OR
230 VAC Input Power
Wire

High Voltage Kit P/N 2600-266 (Sold sepatately) See instruction sheet for more information.

1st Leg

Use only two legs of the incoming 3-phase power and terminate the 3rd leg.

Wire heater DIRECTLY from input power wire.
DO NOT wire heater to gate operator power terminal or damage will occur.

AC

Note: Heater will NOT turn off

POWER

when using the gate operator

OFF

ON/OFF power switch.

13

120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.

9015000–446600VVAACCIInnppuuttPPoowweerrOONNLLYYIInnssttaallllaattiioonn
IMPORTANT: Your gate operator MUST have the optional high voltage kit installed on it.

DoorKing Part Number:
1601-198 Kit
460 VAC Models 3.3 Amp

High voltage AC input wire size and distance limitations for a 9150 208/230 VAC Input Power with a heater.

Model

Horsepower

Volts

Operator and
Heater Amps

12 AWG

Wire Size / Max Distance in Feet

10 AWG

8 AWG

6 AWG

Heater Kit P/N

1/2 HP

460

4.7

1160

1850

2940

4670

1601-198

9150

1 HP

460

5.7

850

1350

2150

3420

1601-198

In bi-parting (dual) gate applications, high voltage AC power is required for EACH 9150 operator with heater.

OFF ON
Heater

Note: Operators illustrated without some components to better show heater mounting location.

Shut off the AC input power wire from the main circuit breaker.

DANGER HOT!

RESET
Install on existing threaded studs

Heater Location

MPloatuenting

LHoecaktneurt

TSratenps-fDoromwenr
Heater MUST be installed on mounting plate. Keep wires away from the heater vents.

1601-198 Heater and Fan Assembly

DAHNOGT!ER
Turning Heater On/Off
Model 1601-198 460 VAC does NOT have a On/Off heater switch. Heater must be turned off at the operator’s input power source, circuit breaker, external power disconnect switch, etc.
1601-167-J-8-25

To gate operator power terminal

Step-Down Transformer

DANGER
HIGH VOLTAGE!
3rd Leg

High Voltage Kit Configured for 460 VAC ONLY
High Voltage Kit P/N 2600-266 (Sold sepatately) See instruction sheet for more information.

2nd Leg

460 VAC Input Power
Wire

1st Leg

Use only two legs of the incoming 3-phase power and terminate the 3rd leg.

Wire heater DIRECTLY from input power wire.
DO NOT wire heater to gate operator power terminal or damage will occur.

AC

Note: Heater will NOT turn off

POWER

when using the gate operator

OFF

ON/OFF power switch.

14

120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.

1600 – 208/230 VAC Input Power ONLY Install
IMPORTANT: Your gate operator MUST have the optional high voltage kit installed on it.

DoorKing Part Number:
1601-197 Kit
208/230 VAC Models 3.3 Amp

High voltage AC input wire size and distance limitations for a 1600 208/230 VAC Input Power with a heater.

Model

Horsepower

Volts

Operator and
Heater Amps

12 AWG

Wire Size / Max Distance in Feet

10 AWG

8 AWG

6 AWG

Heater Kit P/N

1601 / 1603 1602

1/2 HP

208/230

6.0

260

410

660

1050

1 HP

208/230

8.2

190

300

480

770

In bi-parting (dual) gate applications, high voltage AC power is required for EACH 1601 or 1602 operator with heater.

1601-197 1601-197

Shut off the AC input power wire from the main circuit breaker.

To gate operator power terminal

TSratenps-fDoromwenr

ON OFF

MoPulantteing
160P1/-N197
DAHNOTG! ER

Install with existing carriage bolts OR existing threaded studs
Heater MUST be mounted on mounting plate.

Step-Down Transformer

DANGER
HIGH VOLTAGE!

High Voltage Kit Configured for
208 VAC
OR
230 VAC

3rd Leg 2nd Leg

208 VAC Input Power
Wire
OR
230 VAC Input Power
Wire

High Voltage Kit P/N 2600-266 (Sold sepatately) See instruction sheet for more information.

1st Leg

Use only two legs of the incoming 3-phase power and terminate the 3rd leg.

Wire heater DIRECTLY from input power wire.
DO NOT wire heater to gate operator power terminal or damage will occur.

Heater Switch

ON

ON – Normal setting. Automatically
turns the heater ON when the temperature

drops below 40°F (4°C) inside the

operator, and turns the heater OFF when

the temperature rises above 55°F (13°C)

OFF

inside the operator.
OFF – Turns the heater off. DOWN LOOP

C NC NO
NC
1 2 3 4 5 6 7 8 9 10 11 12 13 14

ON

ON

UP

AUTO

OFF

OFF

DOWN

AC POWER DC POWER

1601-167-J-8-25

Use supplied wire stays and existing wire restrainers to run wires. Keep wires clear of all moving parts and the heater vents.
15

Note: Heater will NOT turn off when using the gate operator ON/OFF power switch(s).
120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.

91600000–446600VVAACCIInnppuuttPPoowweerrOONNLLYYIInnssttaallllaattiioonn
IMPORTANT: Your gate operator MUST have the optional high voltage kit installed on it.

DoorKing Part Number:
1601-198 Kit
460 VAC Models 3.3 Amp

High voltage AC input wire size and distance limitations for a 1600 460 VAC Input Power with a heater.

Model

Horsepower

Volts

Operator and
Heater Amps

12 AWG

Wire Size / Max Distance in Feet

10 AWG

8 AWG

6 AWG

Heater Kit P/N

1601 / 1603 1602

1/2 HP

460

4.7

1160

1850

2940

4670

1 HP

460

5.7

850

1350

2150

3420

In bi-parting (dual) gate applications, high voltage AC power is required for EACH 1601 or 1602 operator with heater.

1601-198 1601-198

Shut off the AC input power wire from the main circuit breaker.

To gate operator power terminal

TSratenps-fDoromwenr

MoPulantteing
160P1/-N198
DAHNOTG! ER

Install with existing carriage bolts OR existing threaded studs
Heater MUST be mounted on mounting plate.

Step-Down Transformer

DANGER
HIGH VOLTAGE!
3rd Leg

High Voltage Kit Configured for 460 VAC ONLY
High Voltage Kit P/N 2600-266 (Sold sepatately) See instruction sheet for more information.

2nd Leg

460 VAC Input Power
Wire

1st Leg

Use only two legs of the incoming 3-phase power and terminate the 3rd leg.

Wire heater DIRECTLY from input power wire.
DO NOT wire heater to gate operator power terminal or damage will occur.

Turning Heater On/Off

Model 1601-198 460 VAC does NOT have a

On/Off heater switch. Heater must be turned off

at the operator’s input power source, circuit

breaker,

external

powerDOWN LOOP

disconnect

switch,

etc.

C NC NO
NC

1 2 3 4 5 6 7 8 9 10 11 12 13 14

ON

ON

UP

AUTO

OFF

OFF

DOWN

AC POWER DC POWER

1601-167-J-8-25

Use supplied wire stays and existing wire restrainers to run wires. Keep wires clear of all moving parts and the heater vents.
16

Note: Heater will NOT turn off when using the gate operator ON/OFF power switch(s).
120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.