9550 Gate Operator
“
Specifications
Model | Horsepower | Volts | Operator and Heater Amps | Wire Size / Max Distance in Feet |
---|---|---|---|---|
9210 | 1 | 115 VAC | 16.3 | 50 / 80 / 130 / 210 (12 AWG, 10 AWG, 8 AWG, 6 AWG) |
9210 | 1 | 208 VAC | 8.4 | 180 / 290 / 470 / 750 (12 AWG, 10 AWG, 8 AWG, 6 AWG) |
Product Usage Instructions
Power Connection
- Shut off the AC input power to the operator from the circuit
breaker. - Remove clear plastic electronic box cover and the locknuts
inside to access the electronic box. - Connect the 2 heater power wires according to the operator’s AC
power type.
Mounting Plate Installation
- Bolt the mounting plate to the heater using the supplied bolts
and nuts. - Slide the heater into the gear reducer bracket and secure it
with the provided bolts. - Run the power wires as instructed, keeping them away from
heater vents and ensuring they are not pinched in the electronic
box’s folding hinge.
FAQ
Q: Do I need to drill holes in the gear reducer bracket for
securing bolts?
A: Older models may require drilling two holes in the gear
reducer bracket for securing the bolts to mount the heater.
“`
-195 / -197 / -198 HEATER KITS
These kits are designed for the 9200 · 9500 · 6300 208 & 230 VAC Input power or 460 VAC Input power · 6550 208 & 230 VAC Input power or 460 VAC Input power · 6555 230 VAC Input power · 9000 208 & 230 VAC Input power or 460 VAC Input power · 9024 AC powered 230 VAC ONLY · 9150 208 & 230 VAC Input power or 460 VAC Input power · 1601/1602/1603 208 & 230 VAC Input power or 460 VAC Input power model gate operators. For cold weather climates where temperatures routinely drop below 10°F (-12°C). A built-in thermostat will automatically control the temperature inside operator housing. Find your “SPECIFIC” operator on the next 15 pages.
DoorKing Part Numbers:
1601-195 Kit
115 VAC Model 6.6 Amp
1601-197 Kit
208/230 VAC Models 3.3 Amp
1601-198 Kit
460 VAC Models 3.3 Amp
9200 Specifications Tables
High Voltage AC Input Power for the 9200 Gate Operator with a Heater
The 9200 draws significant power and should have a “Dedicated” circuit breaker at the power source. If power wiring is greater than the maximum distance shown, it is recommended that a service feeder be installed. When large gauge wire is used, a separate junction box must be installed for the operator connection. Wire run calculations are based on NEC 310.15(B)(16) with a maximum voltage drop of 3%. These wire runs are a general guideline but it is highly suggested that individual calculations are made for your specific installation as these distances may vary. Never run low voltage rated wire insulation in the same conduit as high voltage rated wire insulation.
High voltage AC input wire size and distance limitations for a 9210 – 115 VAC with a heater.
Phase
Model Horsepower Volts
Operator and
Heater Amps
Wire Size / Max Distance in Feet
12 AWG 10 AWG 8 AWG 6 AWG
Heater Kit P/N
1ø
9210
1
115 VAC
16.3
50
80
130
210
1601-195
Note: Operator should have a “Dedicated 20 Amp” minimum circuit breaker at the power source.
High voltage AC input wire size and distance limitations for a 9200 – 208/230 VAC OR 460 VAC with a heater.
Phase
Motor Model Horsepower Volts
Operator and
Heater Amps
Wire Size / Max Distance in Feet
12 AWG 10 AWG 8 AWG 6 AWG
Heater Kit P/N
208 VAC
8.4
180
290
470
750
9210
1
1ø
230 VAC
8.3
210
330
530
840
208 VAC
15.0
100
160
260
420
9220
2
230 VAC
14.8
110
180
290
470
1601-197 1601-197 1601-197 1601-197
208 VAC
6.7
270
430
680
1090
9210
1
230 VAC
6.6
300
480
770
1220
460 VAC
5
800
1280
2040
3240
208 VAC
10.0
180
290
460
730
9220
2
230 VAC
9.6
210
330
530
840
3ø
460 VAC
6.6
610
970
1540
2450
208 VAC
13.2
130
210
340
550
9230/9240
3
230 VAC
13.0
150
240
390
620
460 VAC
8.0
300
800
1100
2000
208 VAC
16.2
110
170
280
450
9235
3
230 VAC
16.0
120
200
310
500
460 VAC
8.0
300
800
1100
2000
1601-197 1601-197 1601-198 1601-197 1601-197 1601-198 1601-197 1601-197 1601-198 1601-197 1601-197 1601-198
1601-167-J-8-25
Installation on next page.
Copyright 2025 DoorKing®, Inc. All rights reserved. 1
ON OFF
ON OFF
9200 Installation of Heater
DoorKing Part Numbers
1601-195 Kit 1601-197 Kit 1601-198 Kit
115 VAC Model 208/230 VAC Models 460 VAC Models
6.6 Amp
3.3 Amp
3.3 Amp
Shut off the AC input power to the Wire run tables on previous page.
operator from the circuit breaker.
Power Connection
Mounting Plate
Remove clear plastic electronic box cover. Remove the 3 locknuts inside the electronic box to swing box open.
Heater
Connect the 2 heater power wires according to operator AC power type.
Bolt mounting plate to heater with 2 supplied bolts and nuts.
DANGER
Slide heater into the gear reducer bracket as shown below and bolt heater to the bracket with 2 supplied securing bolts.
HIGH VOLTAGE!
Run the 2 power wires as shown below. Keep wires away from the heater vents and make sure wires do not get pinched in the electronic box’s folding hinge.
DAHNOTG! ER
Hot Neu
L1 L2 L3 L4 L5
115 VAC
1601-195 Kit
DANGER
HIGH VOLTAGE!
CCVMSALEEONARHDS/ICCAEICSAOCSLLENNUARSFTLCIOI/A2FUR2IRLEM.-D23GS2NTAT5OOOT.E24O7HPPERAT53O38R2 VOLTS
AMPS
MADXoGoArKTiEngL,OIAncD.,
PHASE 60 Hz
Inglewood, CA
WARNING
SaDRpDoOMnareoopEtdaoehnnORdrpfooawreoetttVIrehweOasaiIgttllnoleeaNUoaefntwggrpedGS’aasecottioeenmhnIpG.iilgNlaslydeanArmwtJuaeeTnhanoUpdlevEtanaiRoontnhgbgpCdYas.loatstAreryaOuwfNaicenraRtteiylgokaCainnDtitsshAes.rtEioaUnruruAescgSaitTghioEhHnt s.
1601-167-J-8-25
Securing Bolts
Power Wires Clear Plastic Electronic Box Cover
Access Door
GRBreeaadcrukceetr
Electronic Box
Power Wires
1
Locknut
2
Locknut
3
Locknut
Note: The gear reducer bracket may need to be spread apart a little to get the heater to slide in. Older 9200s must have 2 holes drilled in the gear reducer bracket for the securing bolts.
2
Hot Hot Hot
L1 L2 L3 L4 L5
208/230/460 VAC
1-Phase and 3-Phase
1601-197 Kit (208/230 VAC) 1601-198 Kit (460 VAC)
Heater Switch for: 115/208/230 VAC
DANGER HOT!
ON
OFF OFF – Turns
the heater off.
ON – Normal setting.
Automatically turns the heater ON when the temperature drops below 40°F (4°C) inside the operator, and turns the heater OFF when the temperature rises above 55°F (13°C) inside the operator.
Note: Model 1601-198 460 VAC does NOT have a On/Off heater switch. Heater must be turned off at the operator’s input power source, circuit breaker, external power disconnect switch, etc.
120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.
9500 Specifications Table
DoorKing Part Numbers:
1601-197 Kit
208/230 VAC Models 3.3 Amp
1601-198 Kit
460 VAC Models 3.3 Amp
High Voltage AC Input Power for the 9500 Gate Operator with a Heater
The 9500 draws significant power and should have a “Dedicated” circuit breaker at the power source.
If power wiring is greater than the maximum distance shown, it is recommended that a service feeder be installed. When large gauge wire is used, a separate junction box must be installed for the operator connection. Wire run calculations are based on NEC 310.15(B)(16) with a maximum voltage drop of 3%. These wire runs are a general guideline but it is highly suggested that individual calculations are made for your specific installation as these distances may vary.
Never run low voltage rated wire insulation in the same conduit as high voltage rated wire insulation.
High voltage AC input wire size and distance limitations for a 9500 – 208/230 VAC OR 460 VAC with a heater.
Motor Model Horsepower Phase
Volts
Operator and
Heater Amps
Wire Size / Max Distance in Feet
12 AWG 10 AWG 8 AWG 6 AWG
Heater Kit P/N
9550/9555
5
208 VAC
16.2
110
175
280
3
230 VAC
16.1
125
195
315
450 1601-197
500
460 VAC
9.7
410
660
1050
1650
1601-198
208 VAC
24.4
n/a
100
160
1
230 VAC
22.4
n/a
120
190
260
1601-197
310
460 VAC
12.5
270
430
700
1100
1601-198
9570/9575
7
208 VAC
25.0
n/a
110
180
3
230 VAC
23.8
n/a
130
210
290
1601-197
340
460 VAC
13.5
290
470
750
1200
1601-198
208 VAC
35.0
n/a
n/a
110
180
1
230 VAC
32.0
n/a
n/a
130
1601-197 210
460 VAC
17.0
200
320
510
820
1601-198
208 VAC
29.3
n/a
90
150
3
230 VAC
26.3
n/a
120
190
250 1601-197
300
9590/9595
10
460 VAC
15.3
260
410
660
1060
1601-198
208 VAC
45.5
n/a
n/a
n/a
130
1
230 VAC
41.4
n/a
n/a
n/a
1601-197 160
460 VAC
21.6
n/a
250
400
640
1601-198
WARNING RpDeoaDaoatrOSdohnnopMdonwopEewotefrhRratrOsniealttaeeeeItalVerlOngogo’sdgaIfawUtaNtmpieetnceeSaiGhoo.sgninpalumdIlltyaGeerNolewapvanAJniahnndttUTedoghno.EsRpobgalrsafaYCetywtrteuyaiAnOaclikrtnNgieRotsaahtntrreCisuosD.acuAirtngEieohUasAnigsST.hEtH
CAUTION PTCEBBAyheetooteervfleots-emsCBorreMoonpIvnlstAatieesntDyrtlgeAiRAIsmrnTecnejoposduFtnurLiOoynlnitrfpegAtIeLcnnOTrtidefaopMtdtieWoLnirnFrigaif.orlttolC.romRorTveofrOesoMrupmlOeotrdnTIanelhtyroeD.arsatBeeFmerEaaSymgueere-eTo
WARNING
DTPFShMisEeORntIVraOnIcNUe GSis foIGNr AvJehTUicERlesCYoAnOlyN.RPCedDAesEUtrAiaSnTsEH Pbgmseptiameamreuofoitreneeposestrrtegtrloyasognc,unromytoaliessionnetotaoeeosdsanl.vtep.aro,raeteuparsdscecetneehotwrnptiiaaoolskaiduttnoerohrrtasereroeot.panmoeuudrtscoeailpstntpnehiirtceagmeirorracTa!iornlltyaowewcTprsenhateid.hnereeDnergv’gisgniedacagnmteeet.tv)eraiiacsnsopehurcmaa(aplsllpeluaannacnyobthdtlienabostehfae
53382
CAONNSFIO/URLM-3S2T5O E OPERATOR CAN/CCSEARTCI2F2IE.D2 NTOO. 247 VEHICULAR GAT HP
CLASS
MODEL
PHASE
SERIAL
60 Hz
VOLTS
AMPS
MAX
GATE LOAD DoorKing, Inc.,
Inglewood,
CA
Installation on next page.
1601-167-J-8-25
120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.
3
9500 Installation of Heater
Mounting Plate Heater ON OFF
Mount heater to heater bracket with two screws and locknuts.
Wire run tables on previous page.
DoorKing Part Numbers:
1601-197 Kit
208/230 VAC Models 3.3 Amp
1601-198 Kit
460 VAC Models 3.3 Amp
he(aCtHeaernastmeifronBueranccetkstewstaory)
DAHNOGT!ER
Keep wires away from the heater vents.
25 A 23 20
TEST PUteScHhnTiOciaOnPuEsRe AoTnEly
OPEN CLOSE STOP
Shut off the AC input power to the operator from the circuit breaker.
Mount heater bracket to existing holes in base of operator with two nuts and bolts.
ON OFF
BHreaactkeert
Operator Base
Power Connection
Connect the 2 heater power wires according to operator AC power type.
DANGER
HIGH VOLTAGE!
Hot Hot Hot
L1 L2 L3 L4 L5
208/230/460 VAC
1-Phase and 3-Phase
1601-197 Kit (208/230 VAC) 1601-198 Kit (460 VAC)
Run the 2 power wires as shown. Make sure wires do not get pinched in the electronic box’s folding hinge.
25 A 23
20
TEST
PUteScHhnTiOciaOnPuEsRe AoTnEly
OPEN CLOSE
STOP
1601-167-J-8-25
Power Wires
1 Remove the
3 locknuts inside the electronic box to swing box open.
2
Heater Switch for: 208/230 VAC
DANGER HOT!
ON
OFF OFF – Turns
the heater off.
ON – Normal setting.
Automatically turns the heater ON when the temperature drops below 40°F (4°C) inside the operator, and turns the heater OFF when the temperature rises above 55°F (13°C) inside the operator.
Note: Model 1601-198 460 VAC does NOT have a On/Off heater switch. Heater must be turned off at the operator’s input power source, circuit breaker, external power disconnect switch, etc.
Electronic Box
3
4
120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.
6300 – 208/230 VAC Input Power ONLY Install
IMPORTANT: Your gate operator MUST have the optional high voltage kit installed on it.
DoorKing Part Number:
1601-197 Kit
208/230 VAC Models 3.3 Amp
High voltage AC input wire size and distance limitations for a 6300 208/230 VAC Input Power with a heater.
Model
Horsepower
Volts
Operator and
Heater Amps
12 AWG
Wire Size / Max Distance in Feet
10 AWG
8 AWG
6 AWG
Heater Kit P/N
1/2 HP
208/230
6.0
260
410
660
1050
1601-197
6300
1 HP
208/230
8.2
190
300
480
770
1601-197
Wire run distances are shown for a single 6300 operator with heater. In bi-parting (dual) gate applications, reduce the distance by one-half.
DAHNOGT!ER
Heater Locknut
Step-Down Transformer
Shut off the AC input power wire from the main circuit breaker.
MounPtilnagte Instatlhl roenadeexdistsitnugds
Heater MUST be installed on mounting plate.
To gate operator power terminal
DANGER
HIGH VOLTAGE!
High Voltage Kit Configured for
208 VAC
OR
230 VAC
3rd Leg 2nd Leg
208 VAC Input Power
Wire
OR
230 VAC Input Power
Wire
OFF ON
Step-Down Transformer
OFF ON
HDOATN! GER
Heater Switch
a1n6d0F1a-1n9A7sHseematbelry
ON ON – Normal setting. Automatically
turns the heater ON when the temperature
drops below 40°F (4°C) inside the
operator, and turns the heater OFF when
the temperature rises above 55°F (13°C)
OFF
inside the operator.
OFF – Turns the heater off.
1601-167-J-8-25
Keep wires away from the heater vents.
High Voltage Kit P/N 2600-266 (Sold sepatately) See instruction sheet for more information.
1st Leg
Use only two legs of the incoming 3-phase power and terminate the 3rd leg.
To secondary operator heater if installed.
Wire heater(s) DIRECTLY from input power wire.
DO NOT wire heater to gate operator power terminal or damage will occur.
Note for Bi-Parting Dual Gate Operators: Run two (AWG 16-600 volt insulation) power wires from the input power wire through the interconnection cable conduit to power the secondary operator’s heater.
DO NOT wire secondary heater directly to the secondary gate operator’s terminal or damage will occur.
RESET
AC
Note: Heater will NOT turn off
POWER
when using the gate operator
OFF
ON/OFF power switch.
5
120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.
6300 – 460 VAC Input Power ONLY Installation
IMPORTANT: Your gate operator MUST have the optional high voltage kit installed on it.
DoorKing Part Number:
1601-198 Kit
460 VAC Models 3.3 Amp
High voltage AC input wire size and distance limitations for a 6300 208/230 VAC Input Power with a heater.
Model
Horsepower
Volts
Operator and
Heater Amps
12 AWG
Wire Size / Max Distance in Feet
10 AWG
8 AWG
6 AWG
Heater Kit P/N
1/2 HP
460
4.7
740
1180
1870
2980
1601-198
6300
1 HP
460
5.7
610
970
1540
2460
1601-198
Wire run distances are shown for a single 6300 operator with heater. In bi-parting (dual) gate applications, reduce the distance by one-half.
DAHNOGT!ER
Heater Locknut
Step-Down Transformer
Shut off the AC input power wire from the main circuit breaker.
MounPtilnagte Instatlhl roenadeexdistsitnugds
DANGER
HIGH VOLTAGE!
3rd Leg
Heater MUST be installed on mounting plate.
To gate operator power terminal
High Voltage Kit Configured for 460 VAC ONLY
2nd Leg
460 VAC Input Power
Wire
Step-Down Transformer
OFF ON
HDOATN! GER
a1n6d0F1a-1n9A8sHseematbelry
Turning Heater On/Off
Model 1601-198 460 VAC does NOT have a On/Off heater switch. Heater must be turned off at the operator’s input power source, circuit breaker, external power disconnect switch, etc.
1601-167-J-8-25
Keep wires away from the heater vents.
High Voltage Kit P/N 2600-266 (Sold sepatately) See instruction sheet for more information.
1st Leg
Use only two legs of the incoming 3-phase power and terminate the 3rd leg.
To secondary operator heater if installed.
Wire heater(s) DIRECTLY from input power wire.
DO NOT wire heater to gate operator power terminal or damage will occur.
Note for Bi-Parting Dual Gate Operators: Run two (AWG 16-600 volt insulation) power wires from the input power wire through the interconnection cable conduit to power the secondary operator’s heater.
DO NOT wire secondary heater directly to the secondary gate operator’s terminal or damage will occur.
RESET
AC
Note: Heater will NOT turn off
POWER
when using the gate operator
OFF
ON/OFF power switch.
6
120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.
6550 – 208/230 VAC Input Power ONLY Install
IMPORTANT: Your gate operator MUST have the optional high voltage kit installed on it.
DoorKing Part Number:
1601-197 Kit
208/230 VAC Models 3.3 Amp
High voltage AC input wire size and distance limitations for a 6550 208/230 VAC Input Power with a heater.
Model
Horsepower
Volts
Operator and
Heater Amps
12 AWG
Wire Size / Max Distance in Feet
10 AWG 8 AWG
6 AWG
Heater Kit P/N
1 HP
208/230
8.2
190
300
480
770
1601-197
66550500
Wire run distances are shown for a single 6550 operator with heater. In bi-parting (dual) gate applications, reduce the distance by one-half.
Shut off the AC input power wire from the main circuit breaker.
To gate operator power terminal
Step-Down Transformer
DANGER
HIGH VOLTAGE!
High Voltage Kit Configured for
208 VAC
OR
230 VAC
3rd Leg 2nd Leg
208 VAC Input Power
Wire
OR
230 VAC Input Power
Wire
OFF ON
Step-Down Transformer
OFF ON
a1n6dD0F1Aa-1Hn9NAO7sGHTsee!maEtbeRlry
MounPtilnagte
Heater MUST
Heater Switch
Use Existing 2 Bolts and Nuts
be installed on mounting plate.
ON ON – Normal setting. Automatically
turns the heater ON when the temperature
drops below 40°F (4°C) inside the
operator, and turns the heater OFF when
the temperature rises above 55°F (13°C)
RESET
OFF
inside the operator.
OFF – Turns the heater off.
AC POWER
OFF
Keep wires away from the heater vents.
High Voltage Kit P/N 2600-266 (Sold sepatately) See instruction sheet for more information.
1st Leg
Use only two legs of the incoming 3-phase power and terminate the 3rd leg.
Wire heater(s) DIRECTLY from input power wire. DO NOT wire heater to gate operator power terminal or damage will occur.
Note: Heater will NOT turn off when using the gate operator ON/OFF power switch.
To secondary operator heater
if installed.
Note for Bi-Parting Dual Gate Operators: Run two (AWG 16-600 volt insulation) power wires from the input power wire through the interconnection cable conduit to power the secondary operator’s heater. DO NOT wire secondary heater directly to the secondary gate operator’s terminal or damage will occur.
1601-167-J-8-25
120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.
7
6550 – 460 VAC Input Power ONLY Installation
IMPORTANT: Your gate operator MUST have the optional high voltage kit installed on it.
DoorKing Part Number:
1601-198 Kit
460 VAC Models 3.3 Amp
High voltage AC input wire size and distance limitations for a 6550 460 VAC Input Power with a heater.
Model
Horsepower
Volts
Operator and
Heater Amps
12 AWG
Wire Size / Max Distance in Feet
10 AWG 8 AWG
6 AWG
Heater Kit P/N
1 HP
460
5.7
850
1350
2150
3420
1601-198
66550500
Wire run distances are shown for a single 6550 operator with heater. In bi-parting (dual) gate applications, reduce the distance by one-half.
Shut off the AC input power wire from the main circuit breaker.
DANGER
HIGH VOLTAGE!
3rd Leg
To gate operator power terminal
Step-Down Transformer
High Voltage Kit Configured for 460 VAC ONLY
2nd Leg
460 VAC Input Power
Wire
Step-Down Transformer
OFF ON
a1n6dD0F1Aa-1Hn9NAO7sGHTsee!maEtbeRlry
MounPtilnagte
Use Existing 2 Bolts and Nuts
Heater MUST be installed on mounting plate.
Turning Heater On/Off
Model 1601-198 460 VAC does NOT have a On/Off heater switch. Heater must be turned off at the operator’s input power source, circuit breaker, external power disconnect switch, etc.
AC POWER
OFF
RESET
Keep wires away from the heater vents.
High Voltage Kit P/N 2600-266 (Sold sepatately) See instruction sheet for more information.
1st Leg
Use only two legs of the incoming 3-phase power and terminate the 3rd leg.
Wire heater(s) DIRECTLY from input power wire. DO NOT wire heater to gate operator power terminal or damage will occur.
Note: Heater will NOT turn off when using the gate operator ON/OFF power switch.
To secondary operator heater
if installed.
Note for Bi-Parting Dual Gate Operators: Run two (AWG 16-600 volt insulation) power wires from the input power wire through the interconnection cable conduit to power the secondary operator’s heater. DO NOT wire secondary heater directly to the secondary gate operator’s terminal or damage will occur.
1601-167-J-8-25
120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.
8
6555 Installation of Heater
DoorKing Part Number:
1601-197 Kit
208/230 VAC Models 3.3 Amp
If power wiring is greater than the maximum distance shown, it is recommended that a service feeder be installed. When large gauge wire is used, a separate junction box must be installed for the operator connection. The wire table is based on stranded copper wire. Wire run calculations are based on an AC power source with a 3% voltage drop on the power line, plus an additional 10% reduction in distance to allow for other losses in the system.
High voltage AC input wire size and distance limitations for a 6555 230 VAC with a heater.
Model
Horsepower
Volts
Operator and
Heater Amps
12 AWG
Wire Size / Max Distance in Feet
10 AWG
8 AWG
6 AWG
Heater Kit P/N
P6o56w5A5e5C2r4ed
2
230
14.8
110
180
290
470
1601-197
Shut off the AC input power to the operator from the circuit breaker.
Operator Power Connection
Power Wires
Hot Hot
Run power wires through chassis.
230 VAC
1601-197 Kit (208/230 VAC)
DANGER
HIGH VOLTAGE!
Heater Switch
ON OFF
ON – Normal setting. Automatically turns the
heater and fan ON when the temperature drops below 40°F (4°C) inside the operator, and turns the heater and fan OFF when the temperature rises above 55°F (13°C) inside the operator.
OFF – Turns the heater and fan off.
OFF ON
DAHNOGT!ER
MounPtilnagte
Keep wires away from the heater vents.
Use Existing 2 Bolts and Nuts
1601-167-J-8-25
Copyright 2020 DoorKing®, Inc. All rights reserved. 9
120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.
9000 – 208/230 VAC Input Power ONLY Install
IMPORTANT: Your gate operator MUST have the optional high voltage kit installed on it.
DoorKing Part Number:
1601-197 Kit
208/230 VAC Models 3.3 Amp
High voltage AC input wire size and distance limitations for 9000 208/230 VAC Input Power with a heater.
Model
Horsepower
Volts
Operator and
Heater Amps
12 AWG
Wire Size / Max Distance in Feet
10 AWG
8 AWG
6 AWG
Heater Kit P/N
1/2 HP
208/230
6.0
260
410
660
1050
1601-197
9000
1 HP
208/230
8.2
190
300
480
770
1601-197
Wire run distances are shown for a single 9000 operator with heater. In bi-parting (dual) gate applications, reduce the distance by one-half.
Note: Operator illustrated without
some components to better show
heater mounting location.
BacIkntshotrfaeElalldeocentdMreosxontiiuusctndiBntsiognxg Plate
Heater MUST be installed on mounting plate.
DANGHOETR!
DAHNOGT!ER
1601-197 Heater and Fan Assembly
Heater Locknut
Shut off the AC input power wire from the main circuit breaker.
ON OFF
STrtaenps-Dfoorwmner
ON OFF
Heater Switch
ON – Normal setting. Automatically
turns the heater ON when the temperature drops below 40°F (4°C) inside the operator, and turns the heater OFF when the temperature rises above 55°F (13°C) inside the operator.
OFF – Turns the heater off.
1601-167-J-8-25
Power
PUSHteTcOhnOicPiEanRAusTeEonly
Keep wires away from the heater vents.
To gate operator power terminal
DANGER
HIGH VOLTAGE!
High Voltage Kit Configured for
208 VAC
OR
230 VAC
3rd Leg 2nd Leg
208 VAC Input Power
Wire
OR
230 VAC Input Power
Wire
Step-Down Transformer
High Voltage Kit P/N 2600-266 (Sold sepatately) See instruction sheet for more information.
1st Leg
Use only two legs of the incoming 3-phase power and terminate the 3rd leg.
To secondary operator heater if installed.
Wire heater(s) DIRECTLY from input power wire. DO NOT wire heater to gate operator power terminal or damage will occur.
Note: Heater will NOT turn off when using the gate operator ON/OFF power switch.
ON OFF
Note for Bi-Parting Dual Gate Operators: Run two (AWG 16-600 volt insulation) power wires from the input power wire through the interconnection cable conduit to power the secondary operator’s heater.
DO NOT wire secondary heater directly to the secondary gate operator’s terminal or damage will occur.
120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.
10
9000 – 460 VAC Input Power ONLY Installation
IMPORTANT: Your gate operator MUST have the optional high voltage kit installed on it.
DoorKing Part Number:
1601-198 Kit
460 VAC Models 3.3 Amp
High voltage AC input wire size and distance limitations for 9000 460 VAC Input Power with a heater.
Model
Horsepower
Volts
Operator and
Heater Amps
12 AWG
Wire Size / Max Distance in Feet
10 AWG
8 AWG
6 AWG
Heater Kit P/N
1/2 HP
460
4.7
1160
1850
2940
4670
1601-198
9000
1 HP
460
5.7
850
1350
2150
3420
1601-198
Wire run distances are shown for a single 9000 operator with heater. In bi-parting (dual) gate applications, reduce the distance by one-half.
Note: Operator illustrated without
some components to better show
heater mounting location.
BacIkntshotrfaeElalldeocentdMreosxontiiuusctndiBntsiognxg Plate
Heater MUST be installed on mounting plate.
DANGHOETR!
DAHNOGT!ER
1601-198 Heater and Fan Assembly
Heater Locknut
Shut off the AC input power wire from the main circuit breaker.
Keep wires away from the heater vents.
DANGER
HIGH VOLTAGE!
STrtaenps-Dfoorwmner
Turning Heater On/Off
Model 1601-198 460 VAC does NOT have a On/Off heater switch. Heater must be turned off at the operator’s input power source, circuit breaker, external power disconnect switch, etc.
1601-167-J-8-25
Power
PUSHteTcOhnOicPiEanRAusTeEonly
To gate operator power terminal
High Voltage Kit Configured for 460 VAC ONLY
3rd Leg
2nd Leg
460 VAC Input Power
Wire
Step-Down Transformer
High Voltage Kit P/N 2600-266 (Sold sepatately) See instruction sheet for more information.
1st Leg
Use only two legs of the incoming 3-phase power and terminate the 3rd leg.
To secondary operator heater if installed.
Wire heater(s) DIRECTLY from input power wire. DO NOT wire heater to gate operator power terminal or damage will occur.
Note: Heater will NOT turn off when using the gate operator ON/OFF power switch.
ON OFF
Note for Bi-Parting Dual Gate Operators: Run two (AWG 16-600 volt insulation) power wires from the input power wire through the interconnection cable conduit to power the secondary operator’s heater.
DO NOT wire secondary heater directly to the secondary gate operator’s terminal or damage will occur.
120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.
11
9024 AC Powered – 230 VAC Installation
DoorKing Part Number:
1601-197 Kit
208/230 VAC Models 3.3 Amp
If power wiring is greater than the maximum distance shown, it is recommended that a service feeder be installed. When large gauge wire is used, a separate junction box must be installed for the operator connection. The wire table is based on stranded copper wire. Wire run calculations are based on an AC power source with a 3% voltage drop on the power line, plus an additional 10% reduction in distance to allow for other losses in the system.
High voltage AC input wire size and distance limitations for a 9024 AC Powered 230 VAC with a heater.
Model
Horsepower
Volts
Operator and
Heater Amps
12 AWG
Wire Size / Max Distance in Feet
10 AWG
8 AWG
6 AWG
Heater Kit P/N
Po9wA0eC2r4ed
Quadra Drive
230
4.2
410
DC Motor
ONLY
660
1050
1670
1601-197
In bi-parting (dual) gate applications, high voltage AC power is required for EACH 9024 AC Powered 230 VAC operator with heater.
Shut off the AC input
power to the operator
Mounting Heater Existing Operator Threaded Stud
from the circuit breaker
Locate existing threaded studs in operator. Heater
and DC power switch on
MUST be on mounted
operator
on mounting plate with 2 supplied locknuts.
Note: Operator illustrated without some components
Mounting
Plate
1601H-1ea9an7tAedsrFsaenmbly
to better show heater
Back
of
Electronic Box
Heater
mounting location.
Existing Operator Threaded
Stud
ON OFF
DAHNOTG! ER
ON
OFF
Power Wires
Keep wires away from the heater vents.
Heater Switch
Operator Power Connection
ON OFF
DANGER
HOT!
ON – Normal setting. Automatically turns
HOT Hot
the heater ON when the temperature
drops below 40°F (4°C) inside the operator, and turns the heater OFF when
230 VAC
the temperature rises above 55°F (13°C) 1601-197 Kit (208/230 VAC)
inside the operator.
OFF – Turns the heater off.
DANGER
HIGH VOLTAGE!
9024 AC Powered 230 VAC ONLY
1601-167-J-8-25 12
120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.
9150 – 208/230 VAC Input Power ONLY Install
IMPORTANT: Your gate operator MUST have the optional high voltage kit installed on it.
DoorKing Part Number:
1601-197 Kit
208/230 VAC Models 3.3 Amp
High voltage AC input wire size and distance limitations for a 9150 208/230 VAC Input Power with a heater.
Model
Horsepower
Volts
Operator and
Heater Amps
12 AWG
Wire Size / Max Distance in Feet
10 AWG
8 AWG
6 AWG
Heater Kit P/N
1/2 HP
208/230
6.0
260
410
660
1050
1601-197
9150
1 HP
208/230
8.2
190
300
480
77
1601-197
In bi-parting (dual) gate applications, high voltage AC power is required for EACH 9150 operator with heater.
OFF ON
Heater
Note: Operators illustrated without some components to better show heater mounting location.
Shut off the AC input power wire from the main circuit breaker.
DANGER HOT!
RESET
Install on existing threaded studs
Heater Location
MPloatuenting
LHoecaktneurt
OFF ON
TSratenps-fDoromwenr
Heater MUST be installed on mounting plate. Keep wires away from the heater vents.
1601-197 Heater and Fan Assembly
Heater
DAHNOGT!ER
Switch
ON
ON – Normal setting. Automatically
turns the heater ON when the temperature
drops below 40°F (4°C) inside the
operator, and turns the heater OFF when
the temperature rises above 55°F (13°C)
OFF
inside the operator.
OFF – Turns the heater off.
1601-167-J-8-25
To gate operator power terminal
Step-Down Transformer
DANGER
HIGH VOLTAGE!
High Voltage Kit Configured for
208 VAC
OR
230 VAC
3rd Leg 2nd Leg
208 VAC Input Power
Wire
OR
230 VAC Input Power
Wire
High Voltage Kit P/N 2600-266 (Sold sepatately) See instruction sheet for more information.
1st Leg
Use only two legs of the incoming 3-phase power and terminate the 3rd leg.
Wire heater DIRECTLY from input power wire.
DO NOT wire heater to gate operator power terminal or damage will occur.
AC
Note: Heater will NOT turn off
POWER
when using the gate operator
OFF
ON/OFF power switch.
13
120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.
9015000–446600VVAACCIInnppuuttPPoowweerrOONNLLYYIInnssttaallllaattiioonn
IMPORTANT: Your gate operator MUST have the optional high voltage kit installed on it.
DoorKing Part Number:
1601-198 Kit
460 VAC Models 3.3 Amp
High voltage AC input wire size and distance limitations for a 9150 208/230 VAC Input Power with a heater.
Model
Horsepower
Volts
Operator and
Heater Amps
12 AWG
Wire Size / Max Distance in Feet
10 AWG
8 AWG
6 AWG
Heater Kit P/N
1/2 HP
460
4.7
1160
1850
2940
4670
1601-198
9150
1 HP
460
5.7
850
1350
2150
3420
1601-198
In bi-parting (dual) gate applications, high voltage AC power is required for EACH 9150 operator with heater.
OFF ON
Heater
Note: Operators illustrated without some components to better show heater mounting location.
Shut off the AC input power wire from the main circuit breaker.
DANGER HOT!
RESET
Install on existing threaded studs
Heater Location
MPloatuenting
LHoecaktneurt
TSratenps-fDoromwenr
Heater MUST be installed on mounting plate. Keep wires away from the heater vents.
1601-198 Heater and Fan Assembly
DAHNOGT!ER
Turning Heater On/Off
Model 1601-198 460 VAC does NOT have a On/Off heater switch. Heater must be turned off at the operator’s input power source, circuit breaker, external power disconnect switch, etc.
1601-167-J-8-25
To gate operator power terminal
Step-Down Transformer
DANGER
HIGH VOLTAGE!
3rd Leg
High Voltage Kit Configured for 460 VAC ONLY
High Voltage Kit P/N 2600-266 (Sold sepatately) See instruction sheet for more information.
2nd Leg
460 VAC Input Power
Wire
1st Leg
Use only two legs of the incoming 3-phase power and terminate the 3rd leg.
Wire heater DIRECTLY from input power wire.
DO NOT wire heater to gate operator power terminal or damage will occur.
AC
Note: Heater will NOT turn off
POWER
when using the gate operator
OFF
ON/OFF power switch.
14
120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.
1600 – 208/230 VAC Input Power ONLY Install
IMPORTANT: Your gate operator MUST have the optional high voltage kit installed on it.
DoorKing Part Number:
1601-197 Kit
208/230 VAC Models 3.3 Amp
High voltage AC input wire size and distance limitations for a 1600 208/230 VAC Input Power with a heater.
Model
Horsepower
Volts
Operator and
Heater Amps
12 AWG
Wire Size / Max Distance in Feet
10 AWG
8 AWG
6 AWG
Heater Kit P/N
1601 / 1603 1602
1/2 HP
208/230
6.0
260
410
660
1050
1 HP
208/230
8.2
190
300
480
770
In bi-parting (dual) gate applications, high voltage AC power is required for EACH 1601 or 1602 operator with heater.
1601-197 1601-197
Shut off the AC input power wire from the main circuit breaker.
To gate operator power terminal
TSratenps-fDoromwenr
ON OFF
MoPulantteing
160P1/-N197
DAHNOTG! ER
Install with existing carriage bolts OR existing threaded studs
Heater MUST be mounted on mounting plate.
Step-Down Transformer
DANGER
HIGH VOLTAGE!
High Voltage Kit Configured for
208 VAC
OR
230 VAC
3rd Leg 2nd Leg
208 VAC Input Power
Wire
OR
230 VAC Input Power
Wire
High Voltage Kit P/N 2600-266 (Sold sepatately) See instruction sheet for more information.
1st Leg
Use only two legs of the incoming 3-phase power and terminate the 3rd leg.
Wire heater DIRECTLY from input power wire.
DO NOT wire heater to gate operator power terminal or damage will occur.
Heater Switch
ON
ON – Normal setting. Automatically
turns the heater ON when the temperature
drops below 40°F (4°C) inside the
operator, and turns the heater OFF when
the temperature rises above 55°F (13°C)
OFF
inside the operator.
OFF – Turns the heater off. DOWN LOOP
C NC NO
NC
1 2 3 4 5 6 7 8 9 10 11 12 13 14
ON
ON
UP
AUTO
OFF
OFF
DOWN
AC POWER DC POWER
1601-167-J-8-25
Use supplied wire stays and existing wire restrainers to run wires. Keep wires clear of all moving parts and the heater vents.
15
Note: Heater will NOT turn off when using the gate operator ON/OFF power switch(s).
120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.
91600000–446600VVAACCIInnppuuttPPoowweerrOONNLLYYIInnssttaallllaattiioonn
IMPORTANT: Your gate operator MUST have the optional high voltage kit installed on it.
DoorKing Part Number:
1601-198 Kit
460 VAC Models 3.3 Amp
High voltage AC input wire size and distance limitations for a 1600 460 VAC Input Power with a heater.
Model
Horsepower
Volts
Operator and
Heater Amps
12 AWG
Wire Size / Max Distance in Feet
10 AWG
8 AWG
6 AWG
Heater Kit P/N
1601 / 1603 1602
1/2 HP
460
4.7
1160
1850
2940
4670
1 HP
460
5.7
850
1350
2150
3420
In bi-parting (dual) gate applications, high voltage AC power is required for EACH 1601 or 1602 operator with heater.
1601-198 1601-198
Shut off the AC input power wire from the main circuit breaker.
To gate operator power terminal
TSratenps-fDoromwenr
MoPulantteing
160P1/-N198
DAHNOTG! ER
Install with existing carriage bolts OR existing threaded studs
Heater MUST be mounted on mounting plate.
Step-Down Transformer
DANGER
HIGH VOLTAGE!
3rd Leg
High Voltage Kit Configured for 460 VAC ONLY
High Voltage Kit P/N 2600-266 (Sold sepatately) See instruction sheet for more information.
2nd Leg
460 VAC Input Power
Wire
1st Leg
Use only two legs of the incoming 3-phase power and terminate the 3rd leg.
Wire heater DIRECTLY from input power wire.
DO NOT wire heater to gate operator power terminal or damage will occur.
Turning Heater On/Off
Model 1601-198 460 VAC does NOT have a
On/Off heater switch. Heater must be turned off
at the operator’s input power source, circuit
breaker,
external
powerDOWN LOOP
disconnect
switch,
etc.
C NC NO
NC
1 2 3 4 5 6 7 8 9 10 11 12 13 14
ON
ON
UP
AUTO
OFF
OFF
DOWN
AC POWER DC POWER
1601-167-J-8-25
Use supplied wire stays and existing wire restrainers to run wires. Keep wires clear of all moving parts and the heater vents.
16
Note: Heater will NOT turn off when using the gate operator ON/OFF power switch(s).
120 S. Glasgow Avenue Inglewood, California 90301 U.S.A.