DELTA-logo

DELTA Solar System Software

DELTA-Solar-System-Software-product

Home Screen

DELTA-Solar-System-Software-fig- (1)

  1. Monitor Mode:
    Choose the corresponding model.DELTA-Solar-System-Software-fig- (2)
  2. Communication:
    Select the USB COM port that connects to the RS485 box. Press the”DELTA-Solar-System-Software-fig- (4) ” button.DELTA-Solar-System-Software-fig- (3)
  3. ID set up:
    Check inverter ID and key in Start ID & End ID.
    Press the”DELTA-Solar-System-Software-fig- (5) ” button.
  4. Send Command:
    Choose “Single” can send a command to the current set inverter. Choose “Broadcast” can send a command to all inverters detected.
  5. Auto ID Function:
    Click this icon for inverters’ first-time commission, please refer to Chapter 2 for more details.

Auto ID function (first commission)

DELTA-Solar-System-Software-fig- (6)

  1. Select the corresponding model
  2. Click “RS485“
  3. Select the communication port (automatic detection by the system)
  4. ClickDELTA-Solar-System-Software-fig- (7)
  5. Click “Auto IDDELTA-Solar-System-Software-fig- (8)
  6. Enter the numbers of inverters, and click “Scan”DELTA-Solar-System-Software-fig- (9)
  7. The serial number of the successfully scanned device will be displayed, the default ID can be changed.
  8. After the ID setting is completed, click “Set ID”.DELTA-Solar-System-Software-fig- (10)
  9. Select the country of the inverter, and click “Set ”.
    Time will also be synced from a laptop or PC at this stepDELTA-Solar-System-Software-fig- (11)

Main Page

DELTA-Solar-System-Software-fig- (12)

  • Version: Showing all FW versions, Serial Numbers, and Model Names.
  • Status: Showing inverter status and maximum power.
    Warning Display: Showing warning of the inverter.
  • Output: Showing Output Voltage, Current, Power, and Freq readings. Input: Showing input voltage, Current, and Power readings.
  • Inverter Time: Showing inverter time.
  • Temperature: Showing temperature for internal ambient and module.
  • Output Energy: Showing energy generated and runtime for today / Life.
  • Bus Voltage: Showing bus voltage of internal bus capacitor.
  • Max. Input Value: Showing maximum input voltage ever occurs.
  • Max. Output Value: Showing maximum output voltage ever occurs.
  • String Current: Showing each string current.
  • Total Power: Showing total output information, including current and power.DELTA-Solar-System-Software-fig- (13)
  • Derating Records: Showing derating records of the inverter.
  • Test Value: Showing some internal DSP value. This tab is for engineers when doing on-site checking.DELTA-Solar-System-Software-fig- (14)
  • Error Event: Log error events up to 30 pcs.
  • Energy Day / Month: Showing Day / Month energy of the inverter.

Config Page

Please contact local service team to get the password first.DELTA-Solar-System-Software-fig- (15)

DELTA-Solar-System-Software-fig- (16)

  1. Country Set:
    • Country:
      allowed to choose a different country setting.
    • Reclosure time:
      allowed to change the reclosure time.DELTA-Solar-System-Software-fig- (17)
  2. Insulation: Allowed to enable/disable Insulation detection.
  3. DC Injection: Allowed to enable/disable DC injection detection.
  4. Uac/Freq. Protection: Allowed to change UAC/Freq. protection setting. The key value in the blank, if the value is out of the range, it will not be modified in the inverter side.
  5. Comm Protection: Allow to set the communication protection with another device, if disconnected over a specific value, the inverter will shut down.
  6. AC Terminal: Allowed to change AC terminal setting. if there has an N wire on the AC side please chose 3P4W.
  7. Islanding: On/Off selection for anti-islanding function.
  8. EPO: Emergency power-off function, user can set the port to Normal open /close depending on different applications.
  9. Wi-Fi Function: Allowed to reset the Wi-fi module or reset password.
    Only for Wifi supported inverters.

Ctrl Page

Please contact local service team to get the password first.DELTA-Solar-System-Software-fig- (18) DELTA-Solar-System-Software-fig- (19)

  1. Active Power:
    • Enable/Disable this function
    • PM(%):
      control the max output power percentage (0~100%)
    • Ramp up power (%):
      ramp up rate per minute (max 6000)DELTA-Solar-System-Software-fig- (20)
  2. Reactive Power:
    • Mode:
      Select reactive power mode
    • Fixed cosΦ:
      when in “Constant cosΦ “mode, the value can be controlled here Fixed Q:
      when in “Constant Q “mode, the value can be controlled hereDELTA-Solar-System-Software-fig- (21)
    • Response time:
      decide the response time for all reactive power function
  3. Q(U) Ctrl:
    • Q(U) function will be controlled in the “Reactive Power ”page
    • Lock-in Power: when active power is higher than this value, this function starts working
    • Lock-out Power: when active power is lower than this value, this function stopped workingDELTA-Solar-System-Software-fig- (22)
  4. P(U) Function:DELTA-Solar-System-Software-fig- (23)
  5. Q by Night:
    • Mode:
      1. Select reactive mode to “Fixed kvar 24/7”
      2. Set specific percentage for reactive power.
    • Q setting 24/7 allows inverter to generate fixed reactive power at night.
    • Range of ConstQ_Percent: -100%~+100%DELTA-Solar-System-Software-fig- (24)
  6. Q(P) Function Setting:
    This function is only applied for VDE4110, customer can set different (P,Q) points to determine the behavior of inverter.DELTA-Solar-System-Software-fig- (25)
  7. P-F Control:DELTA-Solar-System-Software-fig- (26)
  8. Cos(Φ) of P Ctrl: It will be controlled in “Reactive Power ”page.DELTA-Solar-System-Software-fig- (27)
  9. FRT: Some grid code required FRT function, different behavior can be made by this part.(Only a person with permission from Delta can modify the value).
  10. Fan Test: You can use fan test function to test the fan.
    • Fan Fail: Showing the defective fan during the fan test.DELTA-Solar-System-Software-fig- (28)
  11. Anti-PID:
    When Trip time is ‘0’ means this function is disabled, if the value has been set, the anti-PID function will start after 30 mins when the inverter status shows “No DC”.
    Set specific value for anti-PID function active time. Range of Trip Time value: 0~11 (hour)
  12. ARC: When Arc is detected, the inverter will be locked, the user can use “un-lock” to unlock the inverter.
  13. Dry Contact: The user can set different trigger conditions for the dry contact relay to make the external alarm device work.
  14. Multi-function Relay: Same as dry contact function, but includes more application combinations.

Other Functions

DELTA-Solar-System-Software-fig- (29)

  1. Sync Clock: synchronize the inverter’s time with your laptop’s
  2. Firmware: for FW upgradeDELTA-Solar-System-Software-fig- (30)
    After first connection, press”DELTA-Solar-System-Software-fig- (31) ”to load FW file.DELTA-Solar-System-Software-fig- (32)
    After the file is loaded, the current FW version will shown in yellow, you can know whether the FW needs to be upgraded or not.
    If yes, press “DELTA-Solar-System-Software-fig- (33) ”.
    When the upgrade is finished, “FIRMWARE UPGRADE COMPLETED” will be shown.DELTA-Solar-System-Software-fig- (34)
  3. Language: Three languages available(English /German/French)by clicking the national flag.
  4. Protocol: Switch between Sunspec & Delta protocol.
    Notice:
    If switched to Sunspec, there will be no readings in DSS because DSS is for Delta protocol
  5. Grid Load:
    Enter the password you got.DELTA-Solar-System-Software-fig- (35) DELTA-Solar-System-Software-fig- (36)
    “Config_ID1” can be found in the “ConfigLog” folder, and settings can be implemented to other inverters.
  6. Grid save: save the Grid setting as “Config_ID1” in the “ConfigLog” folder
  7. Datalog: log data on Main pageDELTA-Solar-System-Software-fig- (37)
    • Time intervals can be chosen.
    • Data will be in the “Datalog” folder.