DOP-B Series HMI Touchscreen
“
Product Information
Specifications:
- Model: DOP-B10S615 / DOP-B10E615
- Screen Type: High Color Wide Screen
- Manufacturer: DELTA
- Address: No.18, Xinglong Rd., Taoyuan City 33068, Taiwan
Product Usage Instructions
1. Installation:
Before installing the DELTA’s DOP-B series HMI product, ensure
the following precautions:
- Install the product in a clean and dry location free from
corrosive and inflammable gases or liquids. - Ensure all wiring instructions and recommendations are
followed. - Correctly connect the HMI to a ground following the electrical
standard of the country. - Do not disassemble, modify, or remove wiring when power is
applied to the HMI.
2. Safety Precautions:
Observe the following safety precautions during installation,
operation, and maintenance:
- Comply with the quick start guide for installation to avoid
equipment damage. - Avoid installing the product outside the stated specifications
to prevent electric shock, fire, or explosion. - Avoid exceeding specified temperatures during installation to
prevent abnormal operation or damage.
3. Wiring:
When wiring the HMI product, remember the following:
- Connect the ground terminals to a class-3 ground with a ground
resistance not exceeding 100 ohms. - Improper grounding may lead to communication errors, electric
shock, or fire.
4. Operation:
During operation:
- Use Delta Screen Editor software for editing in Delta’s HMI
product to prevent abnormal operation. - Design HMI programs carefully to avoid personal injury and
equipment damage.
FAQ (Frequently Asked Questions)
Q: Where can I send quote requests for this product?
A: You can send quote requests to info@automatedpt.com.
Q: What should I do if I have questions during operation?
A: If you have any questions during operation, please contact
our local distributors or Delta sales representatives for
assistance.
“`
Send Quote Requests to info@automatedpt.com
DOP-B1 0
High ColorWide Screen User-Friendly HMI Products
No.18, Xinglong Rd., Taoyuan City 33068, Taiwan
B10S615 / B10E615 Instrunction Sheet
(1) Preface
Thank you for purchasing DELTA’s DOP-B series. This instruction sheet will be helpful in the installation, wiring and inspection of Delta HMI. Before using the product, please read this instruction sheet to ensure correct use. You should thoroughly understand all safety precautions before proceeding with the installation, wiring and operation. Place this instruction sheet in a safe location for future reference. Please observe the following precautions:
Install the product in a clean and dry location free from corrosive and inflammable gases or liquids. Ensure that all wiring instructions and recommendations are followed. Ensure that HMI is correctly connected to a ground. The grounding method must comply with the electrical standard of
the country (Please refer to NFPA 70: National Electrical Code, 2005 Ed.). Do not disassemble HMI, modify or remove wiring when power is applied to HMI. Do not touch the power supply during operation. Otherwise, it may cause electric shock.
If you have any questions during operation, please contact our local distributors or Delta sales representatives.
The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the most updated version at http://www.delta.com.tw/ia
(2) Safety Precautions
Carefully note and observe the following safety precautions when receiving, inspecting, installing, operating, maintaining and troubleshooting. The following words, DANGER, WARNING and STOP are used to mark safety precautions when using the Delta’s HMI product. Failure to observe these precautions may void the warranty!
Installation
Comply with quick start for installation. Otherwise it may cause equipment damage. Do not install the product in a location that is outside the stated specification for the HMI. Failure to
observe this caution may result in electric shock, fire, or explosion.
Do not install the product in a location where temperatures will exceed specification for the HMI.
Failure to observe this caution may result in abnormal operation or damage the product.
Please note that this equipment has obtained EMC registration for commercial use. In the event
that it has been mistakenly sold or purchased, please exchange it for equipment certified for home use.
Do not use this product as an alarm device for disaster early warning that may result in personal
injury, equipment damage, or system emergency stop.
Wiring
Connect the ground terminals to a class-3 ground (Ground resistance should not exceed 100).
Improper grounding may result in communication error, electric shock or fire.
Operation
The users should use Delta Screen Editor software to perform editing in Delta’s HMI product. To
perform editing and confirming HMI programs without using Delta Screen Editor software in Delta’s
HMI product may result in abnormal operation.
To prevent the personal injury and equipment damage, when designing HMI programs, please
ensure that a communication error occurred between Delta’s HMI product and the connecting
controller or equipment will not result in system failure or malfunction.
Please be sure to backup the screen data and HMI programs in case they are lost, accidentally
deleted or worse.
Do not modify wiring during operation. Otherwise it may result in electric shock or personal injury. Never use a hard or pointed object to hit or strike the screen as doing this may damage the screen
and let the screen has not respond at all, and then cause HMI to work abnormally.
Maintenance and Inspection
Do not touch any internal or exposed parts of the HMI as electrical shock may result. Do not remove operation panel while power is on. Otherwise electrical shock may result. Wait at least 10 minutes after power has been removed before touching any HMI terminals or
performing any wiring and/or inspection as an electrical charge may still remain in the HMI with hazardous voltages even after power has been removed.
Turn the power off before changing backup battery and check system settings after finishing
change. (all data will be cleared after changing battery).
Be sure the ventilation holes are not obstructed during operation. Otherwise malfunction may result
due to bad ventilation or overheating troubles.
Wiring Method
Do not use a voltage that will exceed specification for the HMI. Failure to observe this caution may
result in electric shock or fire.
Remove the terminal block from the HMI before wiring. Insert only one wire into one terminal on the terminal block. If the wiring is in error, perform the wiring again with proper tools. Never use force to remove the
terminals or wires. Otherwise, it may result in malfunction or damage.
For the power line that forced to take out, ensure to check wiring again and restart.
Communication Wiring
Comply with communication wiring specification for wiring. Wiring length should comply with the stated specification for the HMI. Proper grounding to avoid bad communication quality. To avoid noise and interference, the communication cable, all power cables, and motor power
cable should be placed in separate conduits.
(3) Pin Definition of Serial Communication
DOP-B10S615 / DOP-B10E615 COM1 Port (Supports Flow Control)
COM Port
PIN
PIN1
1 2
3
4
5
6
7
8
9
Note: Blank = No Connection.
Contact RS-232
RXD TXD
GND
RTS CTS
Cal(l4+)1P(8a0r0ts)9N8a5m-6e9s29 To Order or Order Online At Deltaacdrives.com
DOP-B10S615 DOP-B10E615 (Front View)
C
DOP-B10S615 / DOP-B10E615 COM2 Port (Supports Flow Control)
COM Port
PIN
1
PIN1
2
3
4
5
6
7
8
9
MODE1 RS-232
RXD TXD
GND
RTS CTS
MODE2 RS-422 TXD+
RXD+ GND TXD-
RXD-
MODE3 RS-485
D+
GND D-
Note1: Blank = No Connection.
Note2: When COM2 port is used for RS-232 flow control, i.e. RTS and CTS signals are used for flow control, COM3 port will become
incapable of being used. Note3: When COM2 port is used for RS-422 flow control, please refer to the following COM3 Port signals table for pin assignments. The
signals, RTS+, CTS+, RTS- and CTS- shown in brackets are the signals used for flow control.
DOP-B10S615 / DOP-B10E615 COM3 Port
COM Port
PIN
1
PIN1
2
3
4
5
6
7
8
9
MODE1 RS-232
RXD TXD
GND
MODE2 RS-422 TXD+(RTS+)
RXD+(CTS+) GND
TXD-(RTS-)
RXD-(CTS-)
MODE3 RS-485
D+
GND D-
Note1: Blank = No Connection. Note2: When COM2 port is used for RS-422 flow control, please refer to the COM3 Port signals table above for pin assignments. The signals,
RTS+, CTS+, RTS- and CTS- shown in brackets are the signals used for flow control.
DOP-B10E615 Ethernet Interface (LAN)
Ethernet Interface (LAN)
PIN
1 2 3 4 5 6 7 8
Note: Blank = No Connection.
Contact Ethernet
TX+ TXRX+
RX-
Send Quote Requests to info@automatedpt.com Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
A B
: Power LED Indicator A
Lights in green when HMI works normally.
: Operation LED Indicator (Blue) (Note1) The operation LED indicator blinks in blue when either the communication is carried out or the B data is accessing (please refer to the “Note1″ below for explanation).
: Alarm LED Indicator (Red) The alarm LED indicator blinks in red when one of the alarms is on.
C Touch Screen / Display
NOTE 1. The definition of the operation LED indicator (Blue) can be determined by the users freely.
DOP-B10S615DOP-B10E615 (Rear View)
G
H I J
A
B
C
D
A Power Input Terminal
COM2
(It is provided with two LED indicators to indicate B
that HMI is in Read or Write status during the
communication process.)
COM3
(It is provided with two LED indicators to indicate C
that HMI is in Read or Write status during the
communication process.)
D COM1
E USB Slave
E F G
H I J
F Ethernet Interface (LAN) Memory Card Slot / Battery Cover
USB Host Audio Output Interface System Key
(5S)eDnidmQeunostieonRsequests to info@automatedpt.com
DOP-B10S615 / DOP-B106515
261.3+10.0 (10.29″+00.04″ )
)
272(10.71″)
+0.04″ 0
Note: T=1.6mm(0.063″)~6mm(0.24″)
51.9(2.04″) T
189.3+10.0(7.45″
188.3(7.41″)
200(7.88″)
Units: mm (inches)
(6) Specifications
LCD MODULE
Model Display Type
Resolution Backlight
DOP-B10S615
DOP-B106515
10.1” Widescreen TFT LCD (65536 colors)
1024 x 600 pixels LED Back Light (less than 10,000 hours half-life at 25oC) (Note 1)
Display Size
226 x 128.7mm
Operation System
Delta Real Time OS
MCU NOR Flash ROM
SDRAM
32-bit RISC Micro-controller Flash ROM 128 MB
(OS System: 30MB / Backup: 16MB / User Application: 82MB) 64Mbytes
Backup Memory
Sound Effect Output
Buzzer AUX
Ethernet Interface
USB
16Mbytes
Multi-Tone Frequency2K ~ 4K Hz85dB
N/A
Stereo output
IEEE 802.3, IEEE 802.3u
10/100 Mbps
N/A
auto-sensing
(has built-in isolated power circuit (Note 3)
1 USB Host (Note 2) Ver 1.1 / 1 USB Slave Ver 2.0
Memory Card
SD Card (supports SDHC)
Serial COM Port
COM1 COM2 COM3
RS-232 (supports hardware flow control)
RS-232RS-422RS-485 RS-232RS-422RS-485
RS-232 / RS-422 / RS-485 (has built-in isolated power circuit (Note 3))
RS-232 / RS-422 / RS-485 (has built-in isolated power circuit (Note 3))
Function Key
N/A
Perpetual Calendar (RTC)
Built-in
Cooling Method
Natural air circulation
Safety Approval
CEUL (Note 4) KCC (Note 4)
Waterproof Degree
IP65NEMA4
Operation Voltage (Note 5)
DC +24V (-10% ~ +15%) (has built-in isolated power circuit (Note 3))
Voltage Endurance AC500V for 1 minute (between charging (DC24V terminal) and FG terminals)
Power Consumption (Note 5)
12W
Backup Battery
3V lithium battery CR2032 x 1
Backup Battery Life
It depends on the temperature used and the conditions of usage, about 3 years or more at 25oC.
Operation Temp.
o
o
0 C ~ 50 C
Storage Temp.
-20oC ~ +60oC
Ambient Humidity
10% ~ 90% RH [0 ~ 40oC], 10% ~ 55% RH [41 ~ 50oC] Pollution Degree 2
Vibration
IEC 61131-2 compliant 5Hzf8.3Hz = Continuous: 3.5mm, 8.3Hzf150Hz = Continuous: 1.0g
Shock
IEC 60068-2-27 compliant 15g peak for 11 ms duration, X, Y, Z directions for 6 times
Dimensions (W) x (H) x (D) mm
272 x 200 x 61
Panel Cutout (W) x (H) mm
261.3 X 189.3
Weight
Approx.1520g
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
NOTE
1) The half-life of backlight is defined as original luminance being reduced by 50% when the maximum driving current is supplied to HMI. The life of LED backlight shown here is an estimated value under 25oC normal temperature and humidity conditions.
2) USB Host port can provide up to 5V/ 500mA of power. 3) The withstand voltage of the isolated power circuit is 1500V peak for 1 minute. 4) Some models are in the process of application to UL and KCC certification. For more information, please consult our distributors. 5) The value of the power consumption indicates the electrical power consumed by HMI only without connecting to any peripheral
devices. In order to ensure the normal operation, it is recommended to use a power supply which the capacity is 1.5 ~2 times the value of the power consumption. 6) The content of this quick start may be revised without prior notice. Please consult our distributors or download the most updated version at http://www.delta.com.tw/ia/.
Send Quote Requests to info@automatedpt.com Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Documents / Resources
![]() |
DELTA DOP-B Series HMI Touchscreen [pdf] Instruction Manual B10S615, B10E615, DOP-B Series HMI Touchscreen, DOP-B Series, HMI Touchscreen, Touchscreen |