1. Einleitung
This manual provides essential information for the safe installation, operation, and maintenance of the Murray MP120AFC 20-Amp 1 Pole 120-Volt Combination Type Arc Fault Circuit Interrupter (AFCI). Please read this manual thoroughly before installation or use to ensure proper function and safety. This device is designed to detect and mitigate the effects of arc faults, which can be a cause of electrical fires.
2. Sicherheitshinweise
WARNING: Risk of Electric Shock or Fire
- Installation und Wartung dürfen nur von qualifiziertem Elektropersonal durchgeführt werden.
- Always turn off power at the main service panel before working on electrical circuits or installing this device.
- Geeignete persönliche Schutzausrüstung (PSA) verwenden.
- Ensure all wiring connections are secure and meet local and national electrical codes.
- Verwenden Sie dieses Gerät nicht, wenn es beschädigt erscheint.
3. Produktüberschreitungview
The Murray MP120AFC is a single-pole, 20-Amp, 120-Volt Combination Type Arc Fault Circuit Interrupter designed for use in Murray load centers or meter combinations. It provides protection against both parallel and series arc faults, as well as overcurrent protection. The breaker features a test button for verifying proper operation.

Abbildung 1: Illustrative image of a Murray Arc Fault Circuit Interrupter. Note: This image displays a 15-Amp version for visual reference; the product covered by this manual is a 20-Amp model (MP120AFC). The image shows the main body of the circuit breaker, including the toggle switch, the blue 'TEST' button, and various labels indicating specifications like 'MURRAY', 'ARC FAULT', 'AFCI', 'Interrupting Rating 22kA 120V~', and wiring instructions. A coiled white pigtail wire is visible at the bottom.
4. Einrichtung und Installation
Befolgen Sie diese Schritte für eine ordnungsgemäße Installation:
- Stromabschaltung: Turn off the main power to the electrical panel at the service entrance. Verify power is off using a voltage Tester.
- Steckplatz identifizieren: Locate an available slot in the Murray load center.
- Anschlusskabel: Connect the white pigtail wire from the AFCI to the neutral bar in the load center. Ensure a secure connection.
- Sicherungsautomat installieren: Hook the rear of the breaker onto the bus bar stab and firmly push the front of the breaker down until it is fully seated in the panel.
- Connect Circuit Wire: Connect the circuit's hot (black) wire to the terminal screw on the AFCI. Tighten the screw to the torque specified on the breaker label (e.g., 25 lb-in for 60/75°C wire, AWG CU #14-8 / AL #12-8).
- Connect Circuit Neutral: Connect the circuit's neutral (white) wire to the designated terminal on the AFCI, not the neutral bar.
- Strom wiederherstellen: Once all connections are secure and verified, close the panel cover and restore power at the main service entrance.
5. Bedienungsanleitung
The AFCI operates automatically to protect against arc faults and overcurrents. It has a toggle switch for manual operation and a test button.
5.1 Ein-/Ausschalten
- To turn the circuit ON, push the toggle switch firmly to the 'ON' position.
- To turn the circuit OFF, push the toggle switch firmly to the 'OFF' position.
5.2 Testing the AFCI
It is recommended to test the AFCI monthly to ensure proper operation.
- Stellen Sie sicher, dass sich der Leitungsschutzschalter in der Position „EIN“ befindet.
- Press the 'TEST' button (typically blue) located on the front of the breaker.
- The breaker should immediately trip to the 'TRIPPED' (center) position. This indicates the AFCI is functioning correctly.
- To reset the breaker, push the toggle switch firmly to the 'OFF' position, then back to the 'ON' position.
- If the breaker does not trip when the 'TEST' button is pressed, or if it does not reset, contact a qualified electrician for inspection and replacement if necessary.
6. Wartung
The Murray MP120AFC is designed for maintenance-free operation. Regular testing as described in Section 5.2 is the primary maintenance requirement. Keep the area around the electrical panel clean and free from obstructions. Do not attempt to open or repair the circuit breaker.
7. Fehlerbehebung
| Problem | Mögliche Ursache | Lösung |
|---|---|---|
| Unterbrecher löst häufig aus | Arc fault detected, Overload, Short circuit, Ground fault | Unplug appliances from the circuit. If it still trips, contact a qualified electrician to inspect wiring for arc faults, overloads, or short circuits. |
| Der Schutzschalter wird nicht zurückgesetzt. | Persistent fault, Internal breaker failure | Ensure all loads are disconnected. If it still won't reset, contact a qualified electrician. |
| Test button does not trip breaker | AFCI malfunction | The AFCI may be faulty. Contact a qualified electrician for replacement. |
8. Spezifikationen
- Marke: Murray
- Modell: MP120AFC
- Aktuelle Bewertung: 20 Amps
- Bandtage: 120 Volt
- Anzahl der Pole: 1
- Leistungsschaltertyp: Combination Type AFCI (Arc Fault Circuit Interrupter)
- Montageart: Steckhalterung
- Unterbrechungsbewertung: 22 kA
- Frequenz: 50/60 Hz
- Kabelkompatibilität: CU #14-8 / AL #12-8
- Drehmomentbewertung: 25 lb-in (for wire terminals)
- Abmessungen: Ungefähr 1 x 4 x 3 Zoll
- Gewicht: Ungefähr 1.6 Unzen
- Zertifizierungen: UL-zertifiziert
9. Garantie und Support
Specific warranty details for the Murray MP120AFC are typically provided at the point of purchase or on the product packaging. For warranty claims or technical support, please contact Murray customer service or refer to the official Murray website. Always ensure that any servicing or inspection is carried out by a qualified professional.