DAUDIN GFGW-RM01N Remote I-O Module System User Manual

1. Remote I/O Module System Configuration List
Part No. | Specification | Description |
GFGW-RM01N | Modbus TCP-to-Modbus RTU/ASCII, 4 Ports | Gateway |
GFMS-RM01S | Master Modbus RTU, 1 Port | Main Controller |
GFDI-RM01N | Digital Input 16 Channel | Digital Input |
GFDO-RM01N | Digital Output 16 Channel / 0.5A | Digital Output |
GFPS-0202 | Power 24V / 48W | Power Supply |
GFPS-0303 | Power 5V / 20W | Power Supply |
0170-0101 | 8 pin RJ45 female connector/RS-485 Interface | Interface Module |
Product Description
- The interface module can convert the gateway’s RS485 port into a RJ45
- The main controller is in charge of the management and dynamic configuration of I/O parameters and so on.
- The power module and interface module are standard for remote I/O’s and users can choose the model or brand they prefer.
Siemens S7-200 Smart Connection Setup
This section details how to connect a gateway to Siemens S7-200 Smart. For detailed information regarding , please refer to the -Series Product Manual
i-Designer Program Setup
- Make sure that the module is powered and connected to the gateway module using an Ethernet cable
- Click to launch the software
- Select “M Series Module Configuration”
- Click on the “Setting Module” icon
- Enter the “Setting Module” page for M-series
- Select the mode type based on the connected module
- Click on “Connect”
- Gateway Module IP Settings
Note: The IP address must be in the same domain as the controller equipment - Gateway Module Operational Modes
Note:
Set Group 1 as Slave and set the gateway to use the first set of RS485 port to connect to the main controller (GFMS-RM01N)
Siemens S7-200 Smart Hardware Connections
This chapter explains how to use the Step7-MicroWINSMART program to connect S7-200 Smart to . The software must be V2.4 or above for Modbus TCP support. For detailed information, please refer to the S7-200 SmartSeries Manual
- Modbus TCP connects with the gateway via the Ethernet cable going through the Ethernet port on the S7-200 Smart\
Siemens S7-200 Smart Connection Setup
- Launch Step7-MicroWINSMART and click on “Commands” on the right side of the program
A. Click on the “Commands” menu B. Click on the “Bases” menu
C. Click on the “Modbus TCP Client” menu
D. Click to add a new “MBUS_CLIENT”
Communication protocol settings
ames & Definitions
Names | Function | |
A | EN | Enable bits |
B | Req | When it is “1”, it means to send Modbus requests to the server |
C |
Connec t |
When it is “1”, it will attempt to connect to the assigned IP address;
When it is “0”, it will disconnect and ignore any requests from the “Req” command |
D |
IP Add 1~4 |
Gateway IP address |
E | IP Port | The gateway’s port number, which is 502 |
F | RW | Operating modes. “0” is “Read” and “1” is “Write” |
G | Addr | Read/Write Modbus’ starting address |
H | Count | Length of the data to be read/written |
I | DataPtr | Address where the data is stored |
J | Done | Completed bits |
K | Error | Error Code |
Command Memory Configurations
![]() |
A. Click on the “Memory” menu
B. Set up a command’s starting address and once finished, click on “Confirm” |
Notes:
※ ’s first GFDI-RM01N has the register address at 1000(HEX) converted to 4096(DEC)+1 and the starting address at 44097
※ ’s first GFDO-RM01N has the register address at 2000(HEX) converted to 8192(DEC)+1 and the starting address at 48193
Sample Program
Control with one GFDI-RM01N and one GFDO-RM01N
When the first point of DI has received a signal and is triggered, the first point of DO will output a signal as it is connected
Read More About This Manual & Download PDF:
Documents / Resources
![]() |
DAUDIN GFGW-RM01N Remote I-O Module System [pdf] User Manual GFGW-RM01N, GFMS-RM01S, GFDI-RM01N, GFDO-RM01N, GFPS-0202, GFPS-0303, 0170-0101, GFGW-RM01N Remote I-O Module System, GFGW-RM01N, Remote I-O Module System, I-O Module System, Module System |