data FLOW logodata FLOW Apl Switch Field - logodata FLOW Apl Switch Field

AplSwitch Field

16 port Ethernet-APL Field Switch for use in Zone 2

  • Transparent connection of intrinsically safe Ethernet-APL field devices to Industrial Ethernet networks
  • Supplies the field devices with intrinsically safe power
  • Installable in Ex Zone 2
  • Easy integration into automation systems

data FLOW Apl Switch Field - overviewEthernet-APL for seamless and reliable integration into DCS and AMS systems

  • 16 Ethernet APL spur „2-WISE“ ports
  • PROFINET enabled switch with support for PROFINET MRP ring topology
  • Supports all major DCS and AMS systems like
  • Emerson, Siemens, ABB and others
  • Ensures stable networks via ingress/egress support

Extensive diagnostics

  • Integrated PROFINET diagnostic functions for easy commission, maintaining and trouble shooting
  • Local display for instant commissioning diagnostics
  • Enhanced FDI support for easy device integration and parametrization

Allows installation in hazardous areas

  • All product variants can be installed in Ex zone 2
  • Field Devices located in Ex zone 0 and 1 can be connected to the switch
  • Ruggedized and robust housing for field installation IP30

PowerClass A and B support for APL Field devices

  • Allows usage of more complex/power intensive field devices
  • APL power class B supports up to 1,17 W per device on 4 ports
  • Futureproof since no limitation to power class A with 0,54 W

Technical Data

Explosion Protection Installation (zones)
Ex interface zone
IECEx certificate
IECEx gas explosion protection
IECEx dust explosion protection
ATEX certificate
ATEX gas explosion protection
ATEX dust explosion protection
Notes
2
0, 1, 2, 20, 21, 22
in preparation
Ex ec ia [ia Ga] IIC T4 Gc (in preparation)
[Ex ia Da] IIIC (in preparation)
in preparation
data FLOW Apl Switch Field - symbolII3(1)GExecia[iaGa]IICT4Gc(inpreparation)
data FLOW Apl Switch Field - symbol II(1)D[ExiaDa]IIIC(inpreparation)
Certificates in preparation
Safety Data Max. voltage U0
Max. current I0 (Ex ia)
Max. power P0 (Ex ia)
Max. permissible external capacity C0 for IIC
Max. permissible external inductance L0 for IIC
Max. external capac. C0 (IIB/IIIC)
Max. external induc. L0 (IIB/IIIC)
Internal inductance Lᵢ (coil)
Internal capacitance Cᵢ (coil)
AC rated insulation voltage Um
Intrinsic safety concept
17.5 V
380 mA
1.67 W
0.25 μF
0.15 mH
1.5 μF
0.5 mH
negligible
negligible
60 V
2-WISE (CLC IEC/TS 60079-47)
Electrical Data Interface 1 version
Transfer rate interface 1
Number of ports interface 1
Connection type interface 1
Cable shield earthing inter. 1
Interface 2 version
Transfer rate interface 2
Number of ports interface 2
Connection type interface 2
Link network 1 LED
Link network 2 LED
Link network 3 LED
Link network 4 LED
100BASE-TX
100 MBit/s
2 (XT1, XT2)
RJ45 (EIA/TIA 568B)
direct
100BASE-FX
100 MBit/s
2 (XT3, XT4)
SFP (optional)
“XT1” LED, yellow
“XT2” LED, yellow
“XT3” LED, yellow
“XT4” LED, yellow
Auxiliary Power Auxiliary power nominal voltage
Auxiliary power voltage range
Auxiliary power 1 LED
Auxiliary power 2 LED
Max. current consumpt. 24 V DC
Max. current consumpt. 48 V DC
Max. power consumption 24 V DC
Max. power consumption 48 V DC
Max. power dissipation at 24 V
Max. power dissipation 48 V
Auxiliary power connection
Auxil. power connection type
Conductor cross-section rigid min. auxiliary power
Conductor cross-section rigid max. auxiliary power
Conductor cross-section flexible min. auxiliary power
Conductor cross-section flexible max. auxiliary power
24 V DC, 48 V DC
19.2…..57.6 V DC
“PWR1” LED, green
“PWR2” LED, green
1.3 A
0.65 A
31.2 W
31.2 W
19 W
19 W
2 (PWR1, PWR2)
Plugable spring clamp terminal 4-pin BK
Plugable screw terminal 4-pin BK
0.5 mm²
2.5 mm²
0.5 mm²
2.5 mm²
Galvanic Isolation Test voltage for galvanic separation
Auxiliary power/spurs
Auxiliary power/100BASE-TX
Auxiliary power/SFP
100BASE-TX/SFP
Spurs/100BASE-TX
Between spurs
According to standard EN 60079-11
≥ 1500 V AC
≥ 1500 V AC
≥ 1500 V AC
≥ 1500 V AC
≥ 1500 V AC
none
Field Device Interface
Spursversion
Numberofportsspurs
Characteristicspurs
Transferratespurs
LinkspursLED
PowerClass
Max.numberofspurspowerclassA
Max.numberofspurspowerclassB
Max.numberofspursPROFIBUSPA
Open-circuitvoltagepwrcl.A
Open-circuitvoltagepwrcl.BUA
OutputnominalcurrentpowerclassA
OutputnominalcurrentpowerclassB
OutputpowerpowerclassA
OutputpowerpowerclassB
Cableshieldearthingspurs
Spursconnections
Spursconnectiontype
Conductorcross-sectionflexiblemin.spurs
Conductorcross-sectionflexiblemax.spurs
Conductorcross-sectionrigidmin.spurs
Conductor cross-section rigid max. spurs
Ethernet-APL (10BASE-T1L)
16
2-WISE power supply
10 MBit/s vollduplex
S01 … S16 LED, yellow
A
B
16
4
0
13.65 V
12.80 V
55.56 mA
115.00 mA
0.54 W
1.17 W
capacitive
16
Plugable spring-clamp terminal 3-pin BU
Plugable screw terminal 3-pin BU
0.50 mm²
2.50 mm²
0.50 mm²
2.50 mm²
Device Specific Data
Protocols 1
Characteristic protocol 1
Availability protoco l1
Functions protocol 1
Configuration protocol 1
Protocols 2
Characteristic protocol 2
Availability protocol 2
Functions protocol 2
Configuration protocol 2
User interface
Device integration
Ethernet functions
Security
Real-time clock
PROFINET
Device, conformity class B
System redundancy S2, MRP
Dynamic reconfiguration, Network load class I Pruning
Rate limiter
GSDML
EtherNet/IP
Adaptor
DLR
in progress
EDS
Web server
Display
LEDs
FDI
OPC UA
SNMP
DHCP
HTTPS
Password management
Port lock
Yes
Diagnostics Physical layer 10BASE-T1L
Communication
Ambient condition
Diagnostics connections
Maintenance required LED
Start-up process LED
LED group error
Diagnostics connection type
Conductor cross-section flexible min. diagnostics
Conductor cross-section flexible max. diagnostics
Conductor cross-section rigid min. diagnostics
Conductor cross-section rigid max. diagnostics
SNR
TDR
Shield unbalance
Lost packets
LLDP
Temperature, humidity
1 x Pt100, 2-wire (SPT)
“M/S” LED, blue
“BOOT” LED, green
„ERR“ LED, red
Spring clamp terminal 2-pin BU
0.25 mm²
1.5 mm²
0.25 mm²
1.5 mm²
Display Display resolution
Display
Display size in inches
Display operation
Retrievable information
Device reset
256 x 64 pixels
OLED WH/BK
2.00
4 operating keys, capacitive
Device data
Ethernet diagnostics
Physical layer diagnostics
Operating keys
Ambient Conditions Ambient temperature
Storage temperature
Max. operating altitude
Max. relative humidity
Degr. of pollution (IEC 60664)
-40 °C … +70 °C
-40 °C … +65 °C when using SFP module
-40 °C … +60 °C when using Power Class B ports
-40 °C … +80 °C
< 2000 m
95% non-condensing
1
2
Mechanical Data Degree of protection (IP) (IEC 60529)
Fire resistance (UL 94)
Pollutant class
Enclosure material
Dimensions (L x W x H)
Length
Width
Height
Weight
Weight
IP30
V0
corresponds to G3 (ISA-71-04-2013)
Aluminium, painted
260,000 x 292,000 x 52,600 mm
260 mm
292 mm
52.6 mm
2.9 kg
6.39 lb
Mounting / Installation Mounting type
Mounting orientation
On mounting plate
Horizontal
Vertical
Components SFP module 2 x 100BASE-FX

Scope of Delivery

Hardware aplSwitch Field
Documentation On website

Order Numbers

GSL-XX-020102 aplSwitch Field with spring clamp terminals
GSL-XX-020103 aplSwitch Field with screw terminals

Additional Products and Services

ACA-XX-020203 Screw terminals, Contents: 16 x 3-pin, blue; 2 x 4-pin, black
ACA-XX-020202 Spring clamp terminals, Contents: 16 x 3-pin, blue; 2 x 4-pin, black
AAA-XX-020301 Multi-Mode Duplex SFP Transceiver
on request Mounting plate for din rail including 4 screws

Your local Softing contact:

data FLOW logodata FLOW Apl Switch Field - logohttps://industrial.softing.com
Technical changes reserved
©Softing Industrial Automation GmbH, aplFieldS
witch_D_EN_250429_110, April 2025

Documents / Resources

data FLOW Apl Switch Field [pdf] User Guide
apISwitch Field, Apl Switch Field, Switch Field, Field

References

Leave a comment

Your email address will not be published. Required fields are marked *