Danfoss VMTD MIX IE With Complete Insulation User Guide

VMTD MIX IE With Complete Insulation

Operating Guide

Termix VMTD MIX-IE with complete

termix

Operating Guide Termix VMTD MIX-IE with complete insulation

2.0 Functional description

District heating substation for direct heating and
instantaneous domestic hot water with thermostatic control.
Designed for wall-mounting.

Application
The Termix VMTD MIX-IE is a complete solution with built-in water
heater and heating system with differential pressure control
and mixing loop. The Termix VMTD MIX-IE is applicable for for
single-family houses and for decentralized systems in multi-family
houses.

District heating (DH)
The substation is prefabricated with a differential pressure
controller, fitting piece and sensor pocket for insertion of a
heat meter as well as strainer and ball valves. Furthermore the
substation is delivered with a mixing loop including pump, controls
and non-return valve.

Heating (HE)
The heating circuit is designed for direct connection. The
differential pressure controller sets the optimum operation
conditions for radiator thermostats in order to enable individual
temperature control in each room. The mixing loop creates a
suitable temperature level e.g. for floor heating. In order to enable
a timedependent temperature control program, a zone valve with
actuator and a room thermostat can be included as an option.

Domestic hot water (DHW)
The domestic hot water is prepared in the heat exchanger and
the heat exchanger and the temperature is regulated with a flow
compensated temperature controller with integrated differential
pressure controller. The heat exchanger cools out the DH water
very efficiently, thereby creating an excellent operating economy.
The Danfoss IHPT valve ensures a stable hot water temperature
by varying loads, supply temperatures and by high and varying
differential pressure without the need for readjusting the valve.
This protects the heat exchanger against overheating and lime
scale formation. Furthermore the IHPT valve has an integrated
idle temperature controller, which keeps the house supply line
warm. This shortens the waiting periods during summer when
the heating system is in reduced operation, which is ideal were
high comfort is requested.

3.0 Safety notes
3.1 Safety Notes – general

The following instructions refer to the standard design of
substation. Special versions of substations are available on
request.

This operating manual should be read carefully before installation
and start-up of the substation. The manufacturer accepts no
liability for damage or faults that result from non-compliance with
the operating manual. Please read and follow all the instructions
carefully to prevent accidents, injury and damage to property.
Assembly, start-up and maintenance work must be performed by
qualified and authorized personnel only.
Please comply with the instructions issued by the system
manufacturer or system operator.

Corrosion protection
All pipes and components are made of stainless steel and brass.
The maximum chloride compounds of the flow medium should not
be higher than 150 mg/l.
The risk of equipment corrosion increases considerably if the
recommended level of permissible chloride compounds is
exceeded.

Energy source
The substation is designed for district heating as the primary
source of energy. However, also other energy sources can be used
where the operating conditions allow it and always are comparable
to district heating.

Application
The substation is designed to be connected to the house
installation in a frost-free room, where the temperature does not
exceed 50 °C and the humidity does not exceed 60%. Do not cover
or wall up the substation or in any other way block the entrance
to the station.

Choice of material
Choice of materials always in compliance with local legislation.
Safety valve(s)
We recommend mounting of safety valve(s), however, always in
compliance with local regulations.

Connection
The substation must be equipped with features that ensure that
the substation can be separated from all energy sources (also
power supply).

Emergency
In case of danger or accidents – fire, leaks or other dangerous
circumstances – interrupt all energy sources to the station if
possible, and seek expert help.
In case of discoloured or bad-smelling domestic hot water, close all
shut-off valves on the substation, inform the operating personnel
and call for expert help immediately.

REACH
All Danfoss A/S products fulfill the requirements in REACH.
One of the obligations in REACH is to inform customers about
presence of Candidate list substances if any, we hereby inform
you about one substance on the candidate list: The product
contains brass parts which contains lead (CAS no: 7439-92-1) in a
concentration above 0.1% w/w.

Storage
Any storage of the substation which may be necessary prior to
installation should be in conditions which are dry and heated.

Authorized personnel only
Assembly, start-up and maintenance work must be performed by
qualified and authorized personnel only.

Please observe instructions carefully
To avoid injury to persons and damage to the device, it is absolutely
necessary to read and observe these instructions carefully.

Warning of high pressure and temperature
Be aware of the installation’s permissible system pressure and
temperature.
The maximum temperature of the flow medium in the substation is
110 °C.

The maximum operating pressure of the substation is 10 bar. PN 16
versions are available on enquiry.
The risk of persons being injured and equipment damaged increases
considerably if the recommended permissible operating parameters
are exceeded.

The substation installation must be equipped with safety valves,
however, always in accordance with local regulations.

Warning of hot surface
The substation has got hot surfaces, which can cause skin burns.
Please be extremely cautious in close proximity to the substation.
Power failure can result in the motor valves being stuck in open
position. The surfaces of the substation can get hot, which can cause
skin burns. The ball valves on district heating supply and return should
be closed.

Warning of transport damage
Before substation installation, please make sure that the substation
has not been damaged during transport.

IMPORTANT – Tightening of connections
Due to vibrations during transport all flange connections, screw joints
and electrical clamp and screw connections must be checked and
tightened before water is added to the system. After water has been
added to the system and the system has been put into operation,
re-tighten ALL connections.

4.0 Mounting
4.1 Mounting

Installation must be in compliance with local standards and
regulations.
District heating (DH) – In the following sections, DH refers to the
heat source which supplies the substations. A variety of energy
sources, such as oil, gas or solar power, could be used as the
primary supply to Danfoss substations. For the sake of simplicity,
DH can be taken to mean the primary supply.

noteConnections:
1. District heating (DH) supply
2. District heating (DH) return
3. Heating (HE) supply
4. Heating (HE) return
5. Domestic hot water (DHW)
6. Domestic cold water (DCW)

Connection sizes:
DH + HE: G ¾” (int. thread)
DCW + DHW: G ¾” (int. thread)

Dimensions (mm):
Without insulation: H 800 x W 530 x D 375
With cover: H 800 x W 540 x D 430
Weight (approx.): 25 kg

Authorized personnel only
Assembly, start-up and maintenance work must be performed by
qualified and authorized personnel only.

4.1.1 Installation
Mounting:
Adequate space
Please allow adequate space around the substation for mounting
and maintenance purposes.

Orientation
The station must be mounted so that components, keyholes
and labels are placed correctly. If you wish to mount the station
differently please contact your supplier.
Drillings
Where substations are to be wall-mounted, drillings are provided
in the back mounting plate. Floor mounted units have support.

Labelling
Each connection on the substation is labelled.
Before installation:

Clean and rinse
Prior to installation, all substation pipes and connections should be
cleaned and rinsed.

Tightening
Due to vibration during transport, all substation connections must
be checked and tightened before installation.

Unused connections
Unused connections and shut-off valves must be sealed with a
plug. Should the plugs require removal, this must only be done by
an authorized service technician.
Installation:

Strainer
If a strainer is supplied with the station it must be fitted according
to schematic diagram. Please note that the strainer may be
supplied loose.

Connections
Internal installation and district heating pipes connections must be
made using threaded, flanged or welded connections.
Keyhole for mounting.

4.1.2 Dismantle the insulation front
Pull the insulation front using the handle in the top of the cover
whilst keeping the ECL controller in its place.

Keep the ECL controller in its position while removing the insulation
front completely by pulling at the lower end of the insulation front.

4.1.3 Mounting the display of the energy meter
Mark the position of the fixation points of the bracket for the energy
display and screw the two plugs supplied into the insulation front.

Mount the bracket for the display of the energy meter.
Mount the display/calculator of the energy meter onto the bracket.
Pull the wires from the sensors inside the unit through the
duct/cut-out in the insulation plate.

4.2 Start-up

Start-up, Heating with mixing loop
Start-up:

1: Pump speed
Set the pump to highest speed before start-up.

2: Start pump
Start the pump and heat through the system.

3: Open shut-off valves
The shut-off valves should then be opened and the unit observed
as it enters service. Visual checking should confirm temperatures,
pressures, acceptable thermal expansion and absence of leakage.
If the system operates in accordance with design, it can be put
to regular use.

4: Vent system
Switch off the pump and vent the installation after the radiators
have been warmed up.

5: Adjust pump speed
Set the pump to the lowest speed consistent with comfort and
electricity consumption.

Normally the change-over switch is set in the mid position (default).
However for systems with under floor heating or single pipe loop
systems, it may be necessary to turn the change-over switch
upwards.

Higher pump speeds are only used if the heating requirement
increases.

Under floor heating:
Pump stop function
If the substation is used in connection with under floor heating, the
circulation pump must be connected to the pump stop function in
the under floor heating controller. The pump must be stopped if
all under floor heating circuits are closed.

Warranty
If this is not possible, then flow must be continued through the
by-pass. Failing this, the pump will be at risk of seizure and any
remaining warranty will be withdrawn.

Re-thighten connections
After water has been added to the system and the system has been
put into operation, re-tighten ALL connections.

Pump
The pump must be switched off during system fill.

4.3 Electrical connections

Before making electrical connections, please note the
following:

Safety notes
Please read the relevant parts of the safety notes.
230 V
The substation must be connected to 230 V AC and earth.

Potential bonding
Potential bonding should be carried out according
to 60364-4-41:2007 and IEC 60364-5-54:2011.
Bonding point on the mounting plate below right corner marked
with earth symbol.

Disconnection
The substation must be electrically connected so that it can be
disconnected for repairs.

Outdoor temperature sensor
Outdoor sensors should be mounted so as to avoid exposure to
direct sunlight. They should not be placed close to doors, windows
or ventilation outlets.

The outdoor sensor must be connected to the station on the
terminal block under the electronic control.

Authorized electrician
Electrical connections must be made by an authorized electrician only.

Local standards
Electrical connections must be made in accordance with current
regulations and local standards.

5.0 Design
5.1 Design

design

Your substation might look different than the substation shown.

Design description
B Heat exchanger, DHW 27 Actuator, HE
F Electronic controller 31 Differential pressure controller
9 Strainer 41 Fitting piece, energy meter
10 Circulator pump, HE 63 Sieve
14 Sensor pocket, energy meter 74 IHPT controller, DHW

5.2 Schematic diagram

diagram

Your substation might look different than the schematic diagram shown.
Schematic description
B Heat exchanger, DHW 14 Sensor pocket, energy meter 31 Differential pressure controller
F Electronic controller 16 Outdoor sensor 39 Connection closed
1 Ball valve 18 Thermometer 41 Fitting piece, energy meter
2 Single check valve 19 Surface sensor 63 Sieve
9 Strainer 27 Actuator 74 IHPT controller
10 Circulator pump 29 2-way motorized valve

DHW: Domestic Hot Water
DCW: Domestic Cold Water
DH Supply: District Heating Supply
DH Return: District Heating Return
HE Supply: Heating Supply
HE Return: Heating Return

5.2.1 Technical parameters

Technical parameters
Nominal pressure: PN 10 (PN 16 versions are available on enquiry)
Max. DH supply temperature: 110 °C
Min. DCW static pressure: 1.0 bar
Brazing material (HEX): Copper
Heat exchangers test pressure: 30 bar
Sound level: P 55 dB

6.0 Controls
6.1 Heating circuit
6.1.1 Differential pressure controller

The differential pressure controller smooths out the fluctuations in
pressure arriving from the district heating network. The operating
pressure in the substation is thus held steady.

6.1.2 HE temperature control

The HE flow temperature in the heating circuit is controlled by the
HE temperature controller.

6.1.3 RAVK controller

RAVK controller (25-65 °C). The temperature setting is as follows: 1 = 25 °C

2 = 35 °C

3 = 45 °C

4 = 55 °C

5 = 65 °C

The values are intended as a guide.

Thermostatic control

The temperature of the HE flow line is adjusted as follows: To increase temperature, turn the handle on the thermostatic controller to select a higher number.

To decrease temperature, turn the handle on the thermostatic controller to select a lower number.

12 | © Danfoss | 2019.05 VI.JV.P3.02 / LUK40283

Operating Guide Termix VMTD MIX-IE with complete insulation6.1.4 Electronic control

Substations with electronic control must be set in accordance with manufacturer´s instructions.

Where the room temperature is controlled by radiator thermostats, it is recommended that thermostats be set for minimum temperature in each room.

6.1.5 Outside temperature sensor

Outdoor sensors should be mounted so as to avoid exposure to direct sunlight. They should not be placed close to doors, windows or ventilation outlets.

6.1.6 Circulator pump UPM3

UPM3 Pumps can be controlled in constant pressure, proportional pressure or constant speed mode defined by the means of a smart user interface.

The variable speed modulating modes allow the pump to match its performance to the system requirements, helping to reduce noise when thermostatic valves are closing down.

Energy labelling class A

VI.JV.P3.02 / LUK40283 © Danfoss | 2019.05 | 13

Operating Guide Termix VMTD MIX-IE with complete insulation

6.1.7 Grundfos UPM3 AUTO L instructions

Control mode

You can switch from the performance view to the settings view by pressing the push button. The settings view shows which mode controls the circulator. After 2 seconds, the display switches back to performance view.

If you press the button for 2 to 10 seconds, the user interface switches to “setting selection” if the user interface is unlocked. You can change the settings as they appear. The selection of the control mode depends on the system type and the allocation of pressure losses. If you press the key lock for more than 10 seconds, you can toggle between enabling/disabling the key lock function.

Function

Recommended for

Green

Yellow

 Yellow

 Yellow

 Yellow

Proportional pressure 1

 �

Proportional pressure 2

2-pipe systems

 �

 �

Proportional pressure 3

 �

 �

 �

Constant pressure 1

1-pipe systems

 �

Constant pressure 2

Under floor heating

 �

 �

Constant pressure 3

 �

 �

 �

Constant Curve 1

 �

 �

Constant Curve 2

 �

 �

 �

Constant Curve 3

 �

 �

 �

 �

Constant Curve Max.

 �

 �

 �

Operation status

Function

Green

Yellow

 Yellow

 Yellow

 Yellow

Standby*

 * Only PWM controlled

0% ≤ P1 ≤ 25%

 �

25% ≤ P1 ≤ 50%

 �

 �

50% ≤ P1 ≤ 75%

 �

 �

 �

75% ≤ P1 ≤ 100%

 �

 �

 �

 �

Alarm status

Function

Red

 Yellow

 Yellow

 Yellow

 Yellow

Blocked

 �

Supply voltage low

 �

Electrical error

 �

14 | © Danfoss | 2019.05 VI.JV.P3.02 / LUK40283

Operating Guide Termix VMTD MIX-IE with complete insulation

6.2 DHW temperature control

DHW temperature control

There are various types of DHW temperature control used in Danfoss substations.

DHW temperature should be adjusted to 45-50 °C, as this provides

optimal utilisation of DH water. At DHW temperatures above 55 °C,

the possibility of lime scale deposits increases significantly.

6.2.1 IHPT 90 controller (45–65 °)

IHPT is a self-acting flow-compensated temperature controller with integrated differential pressure controller.

The IHPT operates at its best at DH supply temperatures of up to 100 °C.

By turning the handle for temperature setting in (+) direction the setting is increased, by turning it in (-) direction the setting is decreased.

Turns*

Scale

DHW Temperature Setting [°C]

0

7

64

1

6

 61

2

5

58

3

4

 55

4

3

 52

5

2

 48

6

1

 44

7

0

 43

*Start position: Handle turned fully in (+) direction.

The values are intended as a guide.

VI.JV.P3.02 / LUK40283 © Danfoss | 2019.05 | 15

Operating Guide Termix VMTD MIX-IE with complete insulation

6.3 Other
6.3.1 Safety valve

The purpose of the safety valve is to protect the substation from excessive pressure.

The blow-off pipe from the safety valve must not be closed. The blow-off pipe outlet should be placed so that it discharges freely and it is possible to observe any dripping from the safety valve. It is recommended to check the operation of safety valves at intervals of 6 months. This is done by turning the valve head in direction indicated.

6.3.2 Strainer

Strainers should be cleaned regularly by authorized personnel. The frequency of cleaning would depend on operating conditions and the manufacturer’s instructions.

6.3.3 GTU Pressure Equalizer

The GTU Pressure Equalizer absorbs the expansion on the secondary side of the Termix water heaters and can be used as a substitute to the safety valve.

Furthermore the pressure equalizer absorbs a possible increase in pressure, so a discharge outlet is omitted.

The GTU Pressure Equalizer may not be applied in systems with hot water circulation.

16 | © Danfoss | 2019.05 VI.JV.P3.02 / LUK40283

Operating Guide Termix VMTD MIX-IE with complete insulation6.3.4 Fitting piece

The substation is equipped with a fitting piece for energy meter. Assembly of energy meters:

1: Close ball valves

Close the ball valves on DH Supply and DH Return, if there is water on the system.

2: Loosen nuts

Loosen the nuts on the fitting piece.

3: Remove fitting piece

Remove the fitting piece and replace it with the energy meter. Do not forget the gaskets.

4: Tighten connections

After mounting of the energy meter remember to check and tighten all threaded connections.

Sensor pocket, energy meter

The sensors of the energy meter is mounted in the sensor pockets.

VI.JV.P3.02 / LUK40283 © Danfoss | 2019.05 | 17

Operating Guide Termix VMTD MIX-IE with complete insulation

6.4 Extras
6.4.1 Circulation pipe

The circulation pipe set is mounted directly on the controller. The set includes circulation pipe, single check valve and fitting. When mounting the hot water circulation directly on the controller the hot water circulation temperature will be equal to the idle temperature. The idle temperature is a few degrees lower than the set domestic hot water temperature.

18 | © Danfoss | 2019.05 VI.JV.P3.02 / LUK40283

Operating Guide Termix VMTD MIX-IE with complete insulation6.5 Maintenance

The substation requires little monitoring, apart from routine checks. It is recommended to read the energy meter at regular intervals, and to write down the meter readings.

Regular inspections of the substation according to this Instruction are recommended, which should include:

Strainers

Cleaning of strainers.

Meters

Checking of all operating parameters such as meter readings.

Temperatures

Checking of all temperatures, such as DH supply temperature and DHW temperature.

Connections

Checking all connections for leakages.

Safety valves

The operation of the safety valves should be checked by turning the valve head in the indicated direction.

Venting

Checking that the system is thoroughly vented.

Inspections should be carried out minimum every two years.

Spare parts can be ordered from Danfoss. Please ensure that any enquiry includes the substation serial number.

Authorized personnel only

Assembly, start-up and maintenance work must be performed by qualified and authorized personnel only.

VI.JV.P3.02 / LUK40283 © Danfoss | 2019.05 | 19

Operating Guide Termix VMTD MIX-IE with complete insulation

7.0 Troubleshooting
7.1 Troubleshooting in general

In the event of operating disturbances, the following basic features should be checked before carrying out actual troubleshooting:

• the substation is connected to electricity,

• the strainer on the DH supply pipe is clean,

• the supply temperature of the DH is at the normal level (summer, at least 60 °C – winter, at least 70 °C),

• the differential pressure is equal to or higher than the normal (local) differential pressure in the DH network – if in doubt, ask the DH plant supervisor,

• pressure on the system – check the HE pressure gauge.

Authorized personnel only

Assembly, start-up and maintenance work must be performed by qualified and authorized personnel only.

20 | © Danfoss | 2019.05 VI.JV.P3.02 / LUK40283

Operating Guide Termix VMTD MIX-IE with complete insulation

7.2 Troubleshooting DHW

Problem

 Possible cause

 Solution

Too little or no DHW.

Strainer in supply or return line clogged.

 Clean strainer(s).

DHW circulation pump out of order or with too low setting.

Check circulation pump.

Defective or clogged non-return valve.

Replace – clean.

No electricity.

 Check.

Wrong setting of automatic controls, if any.

 To adjust an electronic controller for DHW, pls. note enclosed instructions for electronic controller.

Scaling of the plate heat exchanger.

Replace – rinse out.

Defective motorized valve.

 Check (use manual function) – replace.

Defective temperature sensors.

Check – replace.

Defective controller.

Check – replace.

Hot water in some taps but not in all.

DCW is being mixed with the DHW, e.g. in a defective thermostatic mixing valve.

Check – replace.

Defective or clogged non-return valve on circulation valve.

Replace – clean.

Tap temperature too high; DHW tap load too high.

Thermostatic valve adjusted to a too high level.

Check – set.

Temperature drop during tapping.

Scaling of the plate heat exchanger.

Replace – rinse out.

Larger DHW flow than the substation has been designed for.

Reduce DHW flow.

Thermostatic control valve does not close

Temperature difference between DH supply and DHW set point too low.

Lower the set point temperature or increase the DH supply temperature.

Idle temperature too low (for stations equipped with IHPT).

Set point too low.

 Turn thermostat in (+) direction.

VI.JV.P3.02 / LUK40283 © Danfoss | 2019.05 | 21

Operating Guide Termix VMTD MIX-IE with complete insulation

7.3 Troubleshooting HE

Problem

 Possible cause

 Solution

Too little or no heat.

 Strainer clogged in DH or HE circuit (radiator circuit).

Clean gate/strainer(s).

The filter in the energy meter on DH circuit clogged.

Clean the filter (after consulting the DH plant operator).

Defective or wrongly adjusted differential pressure controller.

Check the operation of the differential pressure controller – clean the valve seat if required.

Sensor defective – or possibly dirt in the valve housing.

Check the operation of the thermostat – clean the valve seat if required.

Automatic controls, if any, wrongly set or defective – possibly power failure.

Check if the setting of the controller is correct – see separate instructions. Check the power supply. Temporary setting of motor to “manual” control – see

instructions on automatic controls.

Pump out of operation.

 Check if the pump is receiving power and that it turns. Check if there is air trapped in the pump housing – see pump manual.

The pump is set at too low speed of rotation.

Set the pump at higher speed of rotation.

Pressure drop – the pressure drop on the radiator circuit shows lower than recommended operating pressure.

Fill water on the system and check the functioning of the pressure expansion vessel if required.

Air pockets in the system.

 Vent the installation thoroughly.

Limiting of the return temperature adjusted too low.

Adjust according to instructions.

Defective radiator valves.

Check – replace.

Uneven heat distribution in building because of incorrectly set balancing valves, or because there are no balancing valves.

Adjust/install balancing valves.

Diameter of pipe to substation too small or branch pipe too long.

Check pipe dimensions.

Uneven heat distribution.

 Air pockets in the system.

 Vent the installation thoroughly.

DH supply temperature too high.

Wrong setting of thermostat or of automatic controls, if any.

Adjust automatic controls, – see

instructions for automatic controls.

Defective controller. The controller does not react as it should according to the instructions.

Call automatic controls manufacturer or replace the regulator.

Defective sensor on self-acting thermostat.

Replace thermostat – or sensor only.

DH supply temperature too low.

Wrong setting of automatic controls, if any.

Adjust automatic controls – see instructions for automatic controls.

Defective controller. The controller does not react as it should according to the instructions.

Call in automatic controls manufacturer or replace controller.

Defective sensor on self-acting thermostat.

Replace thermostat – or sensor only.

Wrong placement/fitting of outdoor temperature sensor.

Adjust location of outdoor temperature sensor.

Strainer clogged.

 Clean gate/strainer.

22 | © Danfoss | 2019.05 VI.JV.P3.02 / LUK40283

Operating Guide Termix VMTD MIX-IE with complete insulation

Too high DH return temperature.

Too small heating surface/too small radiators compared to the total heating requirement of the building.

Increase total heating surface.

Poor utilization of existing heating surface. Defective sensor on self-acting thermostat.

Make sure the heat is distributed evenly across the full heating surface – open all radiators and keep the radiators in the system from heating up at the bottom. It is extremely important to keep the supply temperature to the radiators as low as possible, while maintaining a reasonable level of comfort.

The system is single pipe loop.

The system should feature electronic controls as well as return sensors.

Pump pressure too high.

 Adjust pump to a lower level.

Air in system.

Vent the system.

Defective or incorrectly set radiator valve(s). Single pipe loop systems require special one-pipe radiator valves.

Check – set/replace.

Dirt in the motorized valve or in the differential pressure controller.

Check – clean out.

Defective motorized valve, sensor or automatic controller.

Check – replace.

Electronic controller not adjusted correctly.

 Adjust according to instructions.

Noise in system.

Pump pressure too high.

 Adjust pump to a lower level.

Heat load too high.

Defective motorized valve, sensor or electronic controller.

Check – replace.

VI.JV.P3.02 / LUK40283 © Danfoss | 2019.05 | 23

Operating Guide Termix VMTD MIX-IE with complete insulation

7.4 Disposal

Disposal

This product should be dismantled and its components sorted, if possible, in various groups before recycling or disposal.

Always follow the local disposal regulations.

24 | © Danfoss | 2019.05 VI.JV.P3.02 / LUK40283

Operating Guide Termix VMTD MIX-IE with complete insulation

25 | © Danfoss | 2019.05 VI.JV.P3.02 / LUK40283

Operating Guide Termix VMTD MIX-IE with complete insulation

26 | © Danfoss | 2019.05 VI.JV.P3.02 / LUK40283

Operating Guide Termix VMTD MIX-IE with complete insulation

8.0 Declaration
8.1 Declaration of conformity

Category 0 with electrical equipment

VI.JV.P3.02 / LUK40283 © Danfoss | 2019.05 | 27

Operating Guide Termix VMTD MIX-IE with complete insulation

28| © Danfoss | 2019.05 VI.JV.P3.02 / LUK40283