Danfoss VICSG202 Composite Pipes
Product Specifications
- Brand: Danfoss
- Product Type: Composite Pipes
- Model: VICSG202
- Manufacturer: Danfoss A/S
- Country of Origin: Denmark
INSTALLATION INSTRUCTION
Connecting Danfoss Composite Pipes to FHF Manifold
- Fig. 1: Before connecting the heating circuit to the manifold, cleanly cut off the FH composite pipe to the correct length.
- Fig. 2: Centre pipe and bevel with bevelling tool – 2 mm all round bevel on inner pipe.
- Fig. 3: Slip compression fitting nut over FH composite pipe and push down fitting insert (Eurocone) until it meets end stops.
- Fig. 4: Tighten compression fitting nut with a 30 mm open-ended spanner.
- Fig. 5: Shut off the main supply and return ball valves. Heating circuits are individually flushed via fill and drain valves mounted on respectively supply and return manifolds.
- Fig. 6: Label the individual heating circuits. Carry out a pressure test in accordance with the pressure test protocol.
- Fig. 7: Open ball valves and all flow meters completely.
- Fig. 8: Preset manifold valve for each heating circuit according to calculations and the manifold data sheet.
- Fig. 9: Fix the actuator to the valve with a 2 mm Allen key and connect the actuator and room thermostats via the wiring centre or master controller.
- Fig. 10: Finally, fit the cabinet door.
Danfoss A/S Heating Solutions
- Haarupvaenget 11
- 8600 Silkeborg
- Denmark
- Phone:+45 7488 8000
- Fax: +45 7488 8100
- Email: ComfortControlsInternet@danfoss.com www.heating.danfoss.com
Danfoss can accept no responsibility for possible errors in catalogues, brochures, and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequent changes being necessary in specifications already agreed. All trademarks in this material are the property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Frequently Asked Questions
Q: How do I know if the pipes are securely connected to the manifold?
A: Ensure that the compression fitting nut is tightened properly using a 30mm open-ended spanner and that the Eurocone is correctly inserted until it meets the end stops.
Q: Can I perform the pressure test before labeling the individual heating circuits?
A: It is recommended to label the circuits first for clear identification before conducting any pressure tests.
Documents / Resources
![]() |
Danfoss VICSG202 Composite Pipes [pdf] Installation Guide AN002386455095en-010201, VICSG202, VICSG202 Composite Pipes, VICSG202, Composite Pipes, Pipes |