AVQM is a self-acting flow control with required max. flow setting facilities.
AMV gear motor is mounted onto AVQM and controlled by e.g. weather compensator, type ECL.

Fitting

AVQM can be fitted in any position in heating-system flow or return with flow in cast-in arrow-direction. A strainer must be fitted in flow line, e.g. Danfoss strainer type FV (1 and 2 – AVQM fitted in return).
Fitting
Fitting
Fitting

Starting

Gradually open flow line shut-off cock before opening return line shut-off cock

Pressure testing

Max. test pressure: PN 16 = 25 bar, PN 25 = 40 bar.

Flow adjustment

All district heating connections and bypass, if any, must be open to achieve max. flow. Flow is adjusted either with or without motor mounted onto AVQM.

Without motor

Setting diagrams (see 3, ∆ pb = 0.2 bar and 3a, ∆ pb = 0.5 bar) show required flow depending on scale setting 1 to 10 (14) from closed position (see 4a). Use the tool delivered with the AVQM (see4b) for turning adjustment screw clockwise until it cannot be turned any further (min. flow). Flow can be roughly adjusted in turning adjustment screw counter-clockwise.
Without motor
Without motor
Without motor

With motor

Turn adjustment screw to max. setting (see 4b) and the valve will be opened electrically or manually to ensure required flow, then set adjustment screw on required flow. Without flowmeter it might be necessary to readjust flow with adjustment screw and motor.
With motor

Use enclosed plate for covering flow setting. Cover plate is pushed across setting windows (see 4c) and sealed (see 4d)
With motor
With motor

Fault location

If the control does not function as required, check whether valve body is correctly fitted and whether the impulse tube is blocked.

Dimension

DN L
15 65 mm
20 70 mm
25 75 mm
30 100 mm

Dimension

DN L1
15 131 mm
20 142 mm
25 159 mm
32 196 mm

Dimension

DN L2
15 139 mm
20 154 mm
25 159 mm
32 184 mm

Dimension

DN L3
15 69 mm
20 74 mm
25 79 mm
32 104 mm

Dimension

Service

There must be no pressure on the system when dismantling the control.
Therefore the control must be disconnected.

Spare parts 

Description Code No.
Diaphragm section for AVQM 003H2305
Valve insert, kvs = 1.6 m3 /h 003H2310
Valve insert, kvs = 2.5 m3 /h 003H2311
Valve insert, kvs = 4.0 m3 /h 003H2312
Valve insert, kvs = 6.3 m3 /h 003H2313
Valve insert, kvs = 10.0 m3 /h 003H2314
Contr. valve kvs = 1.6 m3 /h 003H2336
Contr. valve kvs = 2.5 m3 /h 003H2337
Control valve kvs = 4.0 m3 /h 003H2338
Control valve kvs = 6.3 m3 /h 003H2339
Control valve kvs = 10.0 m3 /h 003H2340

Logo

Documents / Resources

Danfoss PN 16 Self Acting Flow Control [pdf] Instructions
003R9105, 003H2305, 003H2310, 003H2311, 003H2312, 003H2313, 003H2314, 003H2336, 003H2337, 003H2338, 003H2339, 003H2340, PN 16 Self Acting Flow Control, PN 16, Self Acting Flow Control, Acting Flow Control, Flow Control

References

Leave a comment

Your email address will not be published. Required fields are marked *