Danfoss-LOGODanfoss Plate Type Heat Exchangers

Danfoss-Plate-Type-Heat-Exchangers-PRODUCT

Introduction

  • This user guide is a guide for installation, commissioning and maintenance of plate type heat exchangers supplied by Danfoss.
  • It is meant for those who are responsible for the installation, the use and maintenance of the heat exchangers. We recommend that you read this user guide carefully before commencing any work.
  • This user guide is applicable for all plate type heat exchangers produced and supplied by Danfoss.
  • Danfoss can not be held responsible or liable for damage as a result of incorrect installation, use and/or maintenance of Danfoss plate type heat exchanger or damage caused by as not complying with the instructions in this user guide.
  • Please note that our plate type heat exchangers are specially designed and built for the maximum design conditions (pressures, temperatures, capacities and type of fluids) provided by the customer and stated on the nameplate.
  • Sudden pressure peaks beyond the maximum operating pressure (or pressure surges) which can occur during start-up or stopping of the system can severely damage the heat exchanger and should be prevented. Danfoss can not be held responsible for any damage as a result of any operation deviating from the original design conditions.

Safety alert notices

The following must always be observed when installing or servicing plate heat exchangers:

  • Comply with national/local safety regulations
  • Ensure that the heat exchanger is unpressurized
  • Ensure that the heat exchanger is cooled down to a temperature below 40 °C (104 °F)

Warning symbols refer to safety alert notices. Warning/safety notices should be observed carefully to prevent:

Personal injury caused by:

  • Wrong transport/lifting
  • Burning/freezing as a result of touching parts with extreme temperatures.
  • Burning/freezing/poisoning as a result of uncontrolled release of pressurized media
  • Contact with chemicals
  • Touching sharp edges of e.g plates or cassettes

Equipment damage caused by:

  • Wrong transport/lifting
  • Liquid hammering
  • External forces
  • Corrosion
  • Chemical action
  • Erosion
  • Material fatigue
  • Thermal and/or mechanical shock
  • Freezing
  • Blocking of the heat exchanger due to particles

General

  • Identification of the heat exchanger
  • All plate type heat exchangers supplied by Danfoss are provided with a name plate positioned on the front (head) of the heat exchanger.
  • On this plate main technical details of the heat exchanger are specified.
  • Before installation please make sure that the intended application is compliant with the name plate application data and use limitations.

Danfoss-Plate-Type-Heat-Exchangers- (1) Danfoss-Plate-Type-Heat-Exchangers- (2)

Fig. 1. Nameplate examples. (*) Danfoss Quality approval confirms PHE has passed leak test procedure 

Each heat exchanger comes with a data list specifying key components and relevant accessories as per specified  customer order, heat exchanger dimensions, and an assembly drawing.

Datalist (example)

Customer: Contact person:
Project: E-mail:
HEX Type: SW40A-72-TM Engineer: IR
Unit: 1 (Parallel) Code: Date: 04-03-2019 16:28:08
Calculated parameters Unit Ref Side Brine Side
Flow Type Co-Current
Load kW 350,00
Inlet temperature °C -7,59 -1,00
Evaporating temperature °C -8,00
SuperHeating K 0,00
Outlet temperature °C -8,00 -5,00
Inlet/Outlet quality 0,000/0,667
Mass flow rate kg/h 1464,4 83899,1
Volumetric flow rate L/min 1346,458
Total pressure drop kPa 5,03 93,71
Pressure drop – In port kPa 0,63 5,20
Total area m 26,60
Surface margin % 8,7
LMTD K 4,48
HTC(Available / Required) W/m -K 3189/2935
Heat flux kW/m 13,158
Abs.Evaporating pressure bar 3,15
Port velocity m/s 0,09(Inlet)/15,22(Outlet) 3,23
Shear stress Pa 5,41 109,07
Properties of fluid Unit Ref Side Brine Side
Fluid Ammonia Ethylene glycol(25,00%)
Liquid viscosity mPa-s 0,1855 3,6207
Liquid density kg/m 649,1 1039,1
Liquid heat capacity kJ/kg-K 4,575 3,755
Liquid thermal conductivity W/m-K 0,583 0,451
Vapor viscosity mPa-s 0,0088
Vapor density kg/m 2,6
Vapor heat capacity kJ/kg-K 2,570
Vapor thermal conductivity W/m-K 0,023
Specification: Unit Ref Side Brine Side
HEX Type: SW40A-72-TM
Number of plates: 72
Max.number of plates in current frame: 84
Grouping: (35TM)/(36TM)
Plate thickness / material: 0,5mm / EN1.4301(AISI304)
Main Gasket / Ring Gasket: NITRIL HT (H) / CHLOROPRENE
Connection: DN 100 Flange cl. AISI316 PN16 DN 100 Flange cl. AISI316 PN16
Counter Flange Yes Yes
Frame type / color: C2L / RAL3020
Certification/Approval type: PED
Volume: L 26,28 28,7
Weight: kg 253,74
Min. wall temperature °C -7 -6,56
Design Temp. (Max/Min): °C 50/-12
Design Pressure(Max) Ref./Brine: bar 16/16

Drawing (example)

Danfoss-Plate-Type-Heat-Exchangers- (3)

Fig. 2. Standard documentation datalist and drawing (examples)

Design:  Single plate and Semi-weldedDanfoss-Plate-Type-Heat-Exchangers- (4)

 

Fig. 3. Construction of generic Semi-welded heat exchanger.  Single Plate construction is identical except plates are not paired (welded) into cassettes.

  • Frame
    The heat exchanger consists of a frame plate (head), a pressure plate (follower), a carrying bar, a guiding bar and a column. Tie bolts are used to press the plate package together. The size and number of bolts depend on the type of heat exchanger.
  • Single Plates
    Single plate pack consists of single plates fitted with a flow gasket on each plate to seal the plate pack. The number of plates, size and dimension depend on the thermal output required. The number of plates determines the total heat transfer area (surface).
  • Semi-welded plates (plate cassettes)
    A plate cassette consists of two single flow plates welded together, creating a sealed flow channel. The cassettes are fitted with two individual gaskets, a ring gasket and a field gasket, to seal the plate pack preventing the intermixing of media. This gasket design allows the use of different gasket materials for the ring and field gaskets respectively for best fit to the actual media and temperature conditions.

The ring gasket material is carefully selected to match the combination of temperature and chemical resistance requirements (e.g., NH˛ and compressor oil on the welded side).

Gaskets
The following gasket types are used in Danfoss plate type heat exchangers:

  • Sonderlock gaskets
  • Glued gaskets
  • Sonder Snap gaskets (semi-welded plate heat exchangers, large range)
  • Hang-on gaskets (semi-welded plate heat exchangers)

Danfoss-Plate-Type-Heat-Exchangers- (5)

  • Right (R)/ Left (L) plates
  • Plates are designed in such a way that they can be used both as right and left plates by alternately turning them 1800. Semi-welded cassettes are not turned.

Right and left plates, Single plates:

  • On a right plate the flow runs from porthole 2 to 3 or reverse from porthole 3 to 2.
  • On a left plate the flow runs from porthole 1 to 4 or reverse from porthole 4 to 1.
  • The opening of the corner portholes is described in a “plate code index”. For instance 1234 means that all corner portholes are open. Every plate can be identified by the gasket configuration, the plate code index, and the plate geometry (e.g. thermal short or thermal long geometry).

Danfoss-Plate-Type-Heat-Exchangers- (6) Danfoss-Plate-Type-Heat-Exchangers- (7)

Fig. 6. Semi-welded plates (cassettes) have no Left and Right plates. Refrigerant always flows in port and 4

Storage

  • If storing the plate heat exchanger for a longer period of time, i.e. more than one month/30 days, the following precautions should be taken to prevent unnecessary equipment damage:
  • Preferably the plate heat exchanger should be stored inside in dry conditions at room temperatures around 15 – 20 °C (59 – 68 °F) and a humidity of maximum 70%.
  • If this is not possibly, place the plate heat exchanger in a wooden box provided with a lining on the inside that will prevent against moisture penetration.

Rubber gasket material is sensitive to certain agents and ultraviolet radiation.

  • Plate heat exchangers must be stored in rooms with no ozone producing equipment such as electric motors or arc-welding equipment as ozone may destroy several rubber materials
  • Plate heat exchangers should not be stored together with any organic solvents or acids in the room
  • Do not expose the plate heat exchanger to ultraviolet radiation

Installation

  • Foundation
    Install the heat exchanger on a °at foundation providing su˙cient support for the frame.
  • Space
    Ensure enough space around the plate heat exchanger for servicing the unit (renewal of plates, tightening of the plate pack).
    As a rule, free space around the unit should be 1.5 to 2 x the width of the unit. See Fig. 7.
  • Drip tray
    Replaceable plate heat exchangers involve a risk of leakage.
    It is recommended to take this into account while installing. Preferably install a drip tray underneath the heat exchanger to prevent leakages onto the °oor and/or harm to electrical equipment.
  • Screen plate
    If the heat exchanger is being used with temperatures above 60 °C or with aggressive  fluids, we advise that you cover the heat exchanger with a screen plate to prevent the risk of human exposure to the surface and fluids.

Danfoss-Plate-Type-Heat-Exchangers- (8)

Transport and lifting

WARNING:
To prevent personal injury always use appropriate hoisting equipment. If you are to lift the heat exchanger itself, straps should be used. The straps should be placed as shown in fig. 8.

  • Usually the heat exchanger will be supplied horizontally on a pallet.
  • The back side of the head will then be secured to the pallet. This allows the unit to be transported by means of a forklift truck.

Raising of the unit: see fig . 8.

  • Remove all tightening elements from the pallet
  • Place straps around opposite bolts on each side of the column (1)
  • Lift the unit vertically from the pallet (2)
  • Remove the pallet securely (3)
  • Slowly lower the heat exchanger to the floor (4)
  • Remove the straps at the unit bottom side (5)
  • Lift one-sided in an appropriate lifting angle (6) and follow the raising of the unit carefully. Avoid any bumps or shocks
  • Once the heat exchanger is in upright position place the straps in the dedicated lifting eyes (7) and lift the unit to its final position (8)
  • Remove the straps and mount the heat exchanger securely to the floor

Danfoss-Plate-Type-Heat-Exchangers- (9)

Never lift the heat exchanger using any other method than described above. Never use the connections, studs or any intermediate plates (if fitted) for lifting (fig. 9). Danfoss-Plate-Type-Heat-Exchangers- (10)

Piping system

Filtration
If the fluid in the plate heat exchanger contains particles larger than Ø0.5mm an inline filter should be fitted.

Installing the pipe connections

  • Most plate heat exchangers are intended for counter-current flow directions, but some specified applications require co-current flow. Refer to name-plate for information on each speciÿc plate heat exchanger.
  • Danfoss plate type heat exchangers are provided with various connection types depending on size, application and conditions.
  • Single plate heat exchangers come with threaded pipe connections or studded angles ready for counter/blind flanges.
  • Semi-welded heat exchangers come with factory installed welding flanges. The refrigerant side is hermetically closed by blind plates and pressurized with nitrogen.
  • Before connecting any piping to the plate heat exchanger make sure to clean and flush the piping system thoroughly for any foreign objects.
  • When connecting the piping system to the plate heat exchanger make sure that the piping system does not subject the plate heat exchanger to stress or strain.
  • Make sure that the piping system, connected to the plate heat exchanger, is secured against pressure peaks/ surges and temperature shocks!
  • When doing any welding in the flange/ valve/piping system make earthing to the piping opposite of the plate heat exchanger. Never use the heat exchanger for earthing as plates and gaskets might be severely damaged.
  • When fitting threaded pipe to the threaded plate heat exchanger connection make sure that the connection do not rotate during tightening as this might damage internal ring gaskets. A secure counter-hold is needed.
  • For studded flange connection, insert the gaskets before bolting the blind flanges to the end plate. Tighten the bolts evenly – do not over-tighten as this might damage bolts/threads.

Note:

  • Identify actual flow inlets/outlets on the name plate before commencing piping work
  • Heavy piping should be supported. This will prevent heavy forces on the plate heat exchanger
  • To be able to open/close and dismantle the plate heat exchanger shut-off valves should be installed in all connections
  • Remove flanges from the plate heat exchanger before connecting to the valve/piping system.
  • Nitrogen pressurized refrigerant side must be depressurized through the small valve in the blind plate before removing the flanges
  • Always install  connections on the follower to prevent vibrations on the plate heat exchanger. The    connections also help prevent expansion of the pipes, which could be caused by temperature influence
  • Flexible connections must be fitted perpendicular to the header/follower
  • Install vents on both sides of the plate heat exchanger
  • The vents should be fitted on the highest point in the direction of the media flow
  • The installation must be ÿtted with safety valves according to current pressure vessel regulations

Commissioning

  • Commissioning, control, maintenance and repair of the installation should be done by authorized, trained and properly instructed staff.
  • Before commissioning check if all connections are fitted correctly.
  • Check the pressures and the temperatures of the media and make sure they are within the limits of the values speciÿed on the name plate.

The plate heat exchanger must not be subject to thermal or mechanical shock as this could lead to premature gasket failure.

Start-up process
Single plate heat exchanger
For plate heat exchangers with liquid on both sides (liquid/liquid flow) the flow with an operating temperature closest to the ambient temperature is to start ÿrst, i.e.

  1. Flow 1
    Delta T to ambient temperature lowest
  2. Flow 2
    Delta T to ambient temperature highest

Start liquid flow 1 first, then liquid flow 2.
For both flows follow these steps:

  • Vent the system fully
  • Close shut off valve fitted between pump and plate heat exchanger
  • Fully open valve fitted into return line from the plate heat exchanger
  • Start the circulation pump usually placed at the inlet
  • Gradually open the closed shut off  valve between pump and plate heat exchanger
  • Vent system again if necessary

Start-up process

Semi-welded heat exchanger
For semi-welded plate heat exchangers with refrigerant on one side and glycol/water on the other side, the glycol/water side, i.e. the liquid flow, must be started steps.

  • Start liquid flow first, then refrigerant flow.
  • For the liquid flow follow steps mentioned above.

For refrigerant flow follow these steps:

  • Keep shut-off valves at the plate heat exchanger connections closed, while evacuating the heat exchanger completely
  • Gradually open the shut-off valve at the outlet for pressure equalization and subsequently gradually open the inlet to the heat exchanger
  • Activate the refrigerant system following normal procedure

If a high pressure difference is present and refrigerant in liquid phase in connecting pipes, precautions should be taken to avoid liquid hammer. Liquid hammer may cause considerable damage to the equipment and cause refrigerant leakage to the ambient.

Check during operation
For proper and safe operation

  • Check the system for potential pressure pulses caused by pumps or control valves. In case of pressure pulses, stop operation and rectify
  • Continuous pressure pulses could cause fatigue issues of flow plates
  • Check that no leakages appear from the unit
  • Check that all vents are closed to prevent air being sucked into the system
  • Check that the operating conditions including media temperatures and pressures are within the limitations stated on the name plate. These must not be exceeded

When in operation the conditions should not be changed. Media temperatures and pressures must be within the limitations stated on the name plate and should not be exceeded.

Shut-down

Shut-down for a short period
If the plate heat exchanger has to be shut down for a short period the following procedure should be followed:

  • Gradually close the inlet control valve in the refrigerant (flow 2) circuit whilst maintaining the full flow in the liquid circuit (flow 1)
  • For high temperature applications cool down the heat exchanger to below 40 °C ( 104 °F)
  • Gradually close the inlet control valve in the liquid (flow 1) circuit
  • Switch off the liquid (flow 1) circuit pump

Shut-down for a long period
If the unit is to be shut down for an extended period of time then the following procedure should be followed:

  • Follow steps above
  • Allow unit to reach ambient temperature
  • Ensure a minimum amount of refrigerant in the heat exchanger. Boil off using flow 1 in evaporators or use liquid drain in condensers.
  • Evacuate refrigerant side
  • Drain flow 1 circuit
  • Lubricate threads on the tie bolts
  • Loosen tie bolts according to the instruction in “opening the plate heat exchanger” section until the length of the plate pack reaches:
    • Single plate: A-measure max. +10%
    • Semi-welded: A-measure Nominal +10%
  • The tie bolts should not be removed or loosened to such an extent that dirt is allowed to enter in-between the plates. It is recommended to attach a warning notice to the plate heat exchanger to remind personnel that the tie bolts need adjustment before the unit can be put back into service
  • Cover the plate pack with black plastic to exclude any sunlight

Maintenance

CIP cleaning

  • Clean-in-Place (CIP cleaning, allows cleaning the plate heat exchanger without opening it and is done by circulating cleaning agents in the heat exchanger.
  • CIP cleaning of the refrigerant circuit is not allowed. CIP cleaning can be done only on the brine circuit.
  • The use of CIP cleaning is relevant for soluble fouling only. Prior to CIP cleaning ensure that all materials in the entire circulation system are resistant to the cleaning agent/CIP liquid used.
  • We advise to ask for a confirmation from the supplier of the cleaning agent that it will not damage the materials in the heat exchanger.
  • Check maximum allowable working temperature on the name-plate mounted on the head of the plate heat exchanger before performing CIP cleaning. Maximum working temperature should not be exceeded at any time. Consult Danfoss if in doubt.
  • If the solution requires recirculation, select a flow that is as high as possible, and no less than the service or operation flows.
  • Follow the instructions from the supplier of the cleaning agent. For re-circulated cleaning, we recommend that fluid is circulated in the plate heat exchanger for no less than 30 minutes.

Rinsing
After using any type of cleaning agent, always rinse the plate heat exchanger thoroughly with fresh water. After CIP cleaning, circulate fresh water for at least 10 minutes.

Cleaning agents guidance

  • Oil and grease can be removed with a water emulsifying oil solvent.
  • Organic and grease cover can be removed with sodium hydroxide (NaOH) maximum concentration 1.5% – max. temp. 85 °C (185 °F). Mixture for 1.5% concentration = 5 l 30% NaOH per 100 l water.
  • Stone and limestone can be removed with nitric acid (HNO˛) – max. concentration 1.5% – max. temp. 65 °C.
  • Mixture for 1.5% concentration = 2.4 l HNO˛ 62% per 100 l water.

Nitric acid has an build up   on the passivation  of stainless steel.

CAUTION:
Nitric acid and Sodium Hydroxide may cause injury to exposed skin, eyes, and mucous membranes. Use of protective eyewear and gloves is strongly recommended.

Opening the plate heat exchanger
When opening and disassembling the plate heat exchanger observe the following:

  • Mark the plate package before opening. This can be done by a diagonal line (see fig. 10) or by numbering each individual plate in sequence
  • Measure and note the actual assembly measure (Reference name plate for validation).
  • Use appropriate tools and lubricant
  • Shut down the heat exchanger as described in section “Shut down”
  • Make sure the heat exchanger cools down (<40 OC (104 OF))
  • The liquid side must be drained and the refrigerant side must be properly evacuated before the heat exchanger is opened
  • Clean the tie bolts and grease the threads
  • Loosen all the short tie bolts while leaving the long tie bolts in tension
  • Loosen the long tie bolts evenly in the numbered order 1, 2, 3, 4 (fig. 10) i.e. the follower shall have a parallel opening motion

CAUTION:
Ensure unit is depressurized and drained of hot and/or aggressive fluid before unit is opened to prevent personal injury.Danfoss-Plate-Type-Heat-Exchangers- (11)

  • Remove all tie bolts
  • Pull the follower back towards the column
  • Remove the plates/cassettes one by one without damaging the gaskets

CAUTION:
Plates/cassettes have sharp edges  When handling plates/cassettes always wear gloves Danfoss-Plate-Type-Heat-Exchangers- (12)

Mechanical/Manual Cleaning

  • Plates/Cassettes can be mechanically cleaned by use of water and a soft brush. Alternatively a high pressure cleaner might be used with caution and without abrasives
  • If needed cleaning agents may be used
  • Cassettes are only cleanable on the brine side and all precautions must be taken to avoid any water or cleaning agent entering the welded cassettes
  • Consult a cleaning specialist for choosing a suitable cleaning agent. Ensure that all agents used are compatible with the plate/cassette and gasket material

CAUTION:
Some cleaning agents may cause injury to exposed skin, eyes and mucous membranes. Use of protective eyewear and gloves is strongly recommended. Never allow any water or cleaning agent to enter the welded side of the cassettes. Danfoss-Plate-Type-Heat-Exchangers- (13)

Never use a metal brush, steel wool or sand/glass paper. This will damage the passivation film of the plates. Never use Hydrochloric for Stainless teel plates. Never use Hydrofluoric for Titanium plates.

  • Always remove plates/cassettes one by one and number them in right order
  • Plates/cassettes removed for manual cleaning must be re-fitted in the same order
  • Single plates may be immersed into a solvent bath to dissolve hard fouling

Before fitting chemical cleaned plates they need to be thoroughly rinsed with fresh water!

Plate/Cassette replacement
If a plate/cassette has to be renewed because of serious damage, it is recommended to replace the plates/ cassettes next to this plate/cassette.

  • Plates/Cassettes must be replaced if damaged or not cleanable
  • When ordering new plates/cassettes all data from the nameplate is required
  • New plates/cassettes are supplied with complete gaskets ready for immediate installation

Gasket replacement
Glue free gaskets / Sonder Snap, Sonderlock &

Hang-on gaskets
These gaskets are mounted without the use of any glue. They are positioned by pushing the gasket fully down into the gasket groove or fastened by special devices. Make sure groove and gasket are clean.

Glue type gaskets
The surfaces need to be clean and free of oil. Only use chloride free glues like Pliobond 20 or 30, Bastic 1782, 3M EC 1099 and Bond spray 77. Follow the instructions of the manufacturer.

CAUTION:
When using commercial solvents and adhesives, follow the manufacturers recommendations carefully. Most of these solvents are hazardous.

Closing the plate heat exchanger When assembling and closing the heat exchanger observe the following: 

  • Check that all gaskets are correctly positioned in the grooves
  • Check that plates/cassettes are hanging correctly on the carrying bar
  • Press the plate package together by pushing the follower
  • Make sure the plates are in the correct position according to the marked diagonal or numbering
  • Check the plate/cassette edge pattern for uniformity (see fig. 13)
  • Identify the A-measure noted prior to opening the heat exchanger (conÿrm with nameplate)
  • Use appropriate tools and lubricant
  • Ensure there is no flow to any part of the unit
  • Clean the tie bolts and grease the threads
  • Install the long tie bolts and tighten evenly in the numbered order 1, 2, 3, 4 (fig. 14) until a resistance can be noticed. i.e. the follower shall have a parallel closing motion
  • Tighten the long tie bolts in sequence 1 to 4 alternately until the A-measure has been reached at all long tie bolts
  • Tighten the short tie bolts in an alternating order until the A-measure has been reached at all tie bolts
  • Prepare for operation. Flow instructions in section “Start-up process”
  • If the heat exchanger does not seal immediately the tie bolts can gradually be tightened to  A- measure minimum (see name plate)

The A-measure shall never be less than A-measure minimum.

Danfoss-Plate-Type-Heat-Exchangers- (14) Danfoss-Plate-Type-Heat-Exchangers- (15)

Fig. 14. Closing the plate heat exchanger. Note: The A-measure shall never be less than A-measure minimum (see name plate)

Regular Service of the plate heat exchanger Service sequence – once a year as a minimum

  • Check temperatures and flows against commissioning data
  • Check general condition and look for any signs of leakage
  • Wipe clean all painted parts and check surfaces for signs of damage – “touch up” if necessary
  • Check bolts and bars for rust and clean. Coat threaded parts with molybdenum grease or a corrosion inhibitor (ensure that no grease, etc. falls onto the plate gaskets
  • If rollers are ÿtted to the follower, lubricate the bearings with light machine oil

Additional service for semi-welded heat exchanger:

Clean fluids/normal conditions Dirty fluids/severe   conditions
             Years after commis- sioning  2   PHE audit  Leak detection refrigerant  CIP and manual cleaning  Replace ring gaskets*
 3  PHE audit Leak detection refrigerant CIP cleaning
 5   PHE audit  Replace ring- and main body gaskets**  Leak detection refrigerant  CIP and manual cleaning   PHE audit  Replace ring- and main body gaskets**  Leak detection refrigerant  CIP and manual cleaning
 6
 7   PHE audit  Leak detection refrigerant   CIP cleaning   PHE audit  Leak detection refrigerant  CIP &manual cleaning  Replace ring gaskets*
 8
 10  Replace ring- and main body gaskets**  Leak detection refrigerant  CIP and manual cleaning   PHE audit  Replace ring- and main body gaskets**  Leak detection refrigerant  CIP &manual cleaning
 12
 13   PHE audit  Leak detection refrigerant   CIP cleaning   PHE audit  Leak detection refrigerant  CIP &manual cleaning  Replace ring gaskets*
 15

Fig. 15. Guideline for service intervals for semi-welded plate heat exchangers. Indicative for clean fluids/normal conditions and dirty fluids/severe temperature-pressure conditions respectively

* Ring gasket kit ** Full gasket kit

  • PHE audit: Visual inspection of operating conditions, leaks, corrosion and general condition Leak detection refrigerant: Electronic testing (sniffer)
  • CIP: Clean in place (See section “clean in place”)
  • Manual cleaning: Plate pack disassembly/plate cleaning
  • Replace gaskets: Plate pack disassembly/replace gaskets
  • At extreme fluids/conditions audits should be performed more frequent

Troubleshooting

Most common problems with a plate heat exchanger, can be solved by own trained personnel. Fig.16 lists a summary of possible problems together with relevant possible causes and solutions. To maintain a continuous proper function of the plate heat exchanger ,it is essential to keep the operating pressure and temperature within the ranges stated on the nameplate. Exceeding these values, even as short-lasting peaks, may damage the unit or could be the cause of problems/issues. To avoid costly repairs, it is recommended to have the installation and maintenance carried out by properly trained personnel.

Problem Possible cause Possible solution
Leakage Connection sealing damaged Check the rubber liners (if fitted)
Check the flange gasket (if fitted)
Check the ring gasket at first plate
Fit the pipes tension-free
Mixing of primary and secondary circuit Check the plates for holes and/or cracks
Single plate: Check the gaskets around the port and diagonal areas
Semi-welded: Check the diagonal part of the field gasket and ring gasket
Plate package sealing damaged Check the assembly distance “A”
Check the condition of the gaskets
Check the proper position of the gaskets
The operating conditions deviate from the specification Adjust the operating conditions
Insufficient capacity Air in the system Vent the piping system
Check the pipe work for possible air traps
The operating conditions deviate from the specification Adjust the operating conditions
The heat exchanger is fouled internally Clean the heat exchanger
The connections have been interchanged Redo the pipe work
Too high pressure drop Flow larger than the design flow Adjust the flow
Channels in plates blocked Flush / clean
Incorrect measurement Check the pressure indicator
Fluid deviating from the specification Check the chemical composition
Air in the system Vent the piping system
Check the pipe work for possible air traps

Fig. 16. Summary of possible problems, causes and solutions
For nearly all leakage problems it will be necessary to dismantle the unit before any attempts to rectify the fault can be made. Mark the area(s) where the leakage seems located with a felt tip marker or similar before disassembling the plate heat exchanger. Follow the instructions in section “Opening the plate heat exchanger”. “Cold leakage” is caused by a sudden change in temperature. The sealing properties of certain elastomers are temporarily reduced when the temperature changes suddenly. No action is required as the gaskets most often reseal after the temperature has stabilized.

Gasket failures are generally a result of

  • Material aging/degradation
  • Excessive exposure to ozone
  • High or low operating temperature – outside specified material limits
  • Exposure to pressure surges
  • Attack by chemicals from cleaning, refrigerants or oils
  • Physical damage from incorrect assembly work
  • Misaligned plates (check the hanging system at the top of the plate for distortion)

Decrease in performance is generally a result of

  • Plate surfaces require cleaning or descaling
  • Pumps or associated controls failing
  • Plate channels blocked
  • Liquid flows not as  Associated chiller / cooling tower / boiler under sized or dirty
  • Cooling fluid temperature to the plate heat exchanger is higher than the design temperature
  • Heating fluid temperature to the plate heat exchanger is lower than the design temperature
  • Refrigerant trap broken or jammed – unit becomes  with condensate
  • Plate package has been assembled incorrectly
  • Plate heat exchanger is running with co-current flow, instead of counter-current. (Check direction of pump flows)
  • Air trap has developed in the plate package or piping work

After sales service

Ordering parts
When ordering spare parts it is important to provide correct data for:

  • Project and order number
  • Plate heat exchanger type and manufacturing number (see name plate)
  • Required parts

When ordering separate plates it is important that the correct plate code index and type of plate is given. When ordering separate gaskets it is important to indicate the correct gasket material. When ordering tie bolts, the existing bolts should be measured in order to get spare bolts with the same dimensions.

Modifications to the heat exchanger

  • Please note that a plate heat exchanger is specified  designed and built for the operating parameters (pressures, temperatures, capacity and type of fluids) initial provided by the customer.
  • If the plate heat exchanger needs to operate at a different capacity this can be achieved by adding or removing plates/cassettes.
  • Modification of the plate heat exchanger to match other parameters may also be considered. Consult Danfoss for redesign and/or approval of any change to operating parameters.
  • After approval by Danfoss a new name plate will be issued.
  • You may only commission a plate heat exchanger under modiÿed conditions after written approval by Danfoss.

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

FAQ

  • Q: What should I do if I exceed the maximum working pressure?
    A: Do not exceed the specified maximum working pressure at any time to prevent damage to the heat exchanger. If you suspect an overpressure situation, shut down the system immediately and investigate the cause.
  • Q: Can I use fluids other than water in this heat exchanger?
    A: No, this heat exchanger is designed for water on both sides. Using other fluids may lead to performance issues or damage to the equipment.