Danfoss OPTBE Board Functional Extensions User Manual

ENDAT/ SSI , SI N- COS OPTI ON BOARD OPTBE

OPTBE l ayo u t a n d d esc r i pt i o n

Description:                 Encoder board for VACON® NXP with an input for EnDat/SSI absolute encoder and Sin/Cos type encoder.

Allowed slots:              C, D, E (Sin/Cos signals can only be used in slot C)

Type ID:                       16965

Terminals:                   One terminal block; Screw terminals (M2.6); No coding.

Jumpers:                     X1 and X2 (see page 5)

Board parameters:      Yes (see page 7)

An absolute encoder is a type of encoder capable of specifying its absolute position. The position data is retained even during a power failure or breakdown. The position data carried by the absolute encoder can be used by the AC drive in motor control and position control applications.

Sin/ Cos encoder produces a pair of analog sinusoidal signals. There are several sine cycles (for example 1024 or 2048) per mechanical revolution.

Encoder cableHeidenhain cable Max. length 100m

It is recommended to use a cable which contains individual shield for

each twisted pair.

Encoder voltage5V, 12V or 15V

Max. current consumption 300mA

Measuring steps/ revolution4.2 billion (max. 32bit)
Distinguishable revolutions0 65535 (max. 16bit)
Sin/Cos signal periods/revolution1  65535
EnDat and SSI data transfer rate200 kHz

EnDat is a bidirectional synchronous serial interface for encoders. For example, the absolute encoder position data can be read and encoder parameters can be set via the EnDat connection. It also forwards the messages related to the encoder functions.
All EnDat connections are available in terminal X6. The board uses EnDat version 2.1.
SSI (Synchronous Serial Interface) is a single directional interface for transmitting absolute position value.
The absolute position value beginning with the Most Significant Bit (MSB first) is transferred on the DATA lines in synchronism with a CLOCK signal transmitted by the control. The SSI standard data word length for single turn absolute encoders is 13 bits, and for multiturn absolute encoders 25 bits.
More information on EnDat/SSI: http://www.heidenhain.com.

OPTBE j u mp er s

NOTE! It is recommended to use a 12 V or 15 V supply voltage instead of 5 V. OPTBE interface does not support “sense” function to compensate voltage drop with a long cabling. Therefore with 5 V supply voltage the cable length limit is about 60 meters with 0.5 mm2 wire section. With 5 V supply voltage it is recommended to use two or more wires in parallel for the supply connection. Jumper X1 selects encoder supply voltage on the OPTBE board, see jumper settings below:

Jumper X2 selects Sin/Cos signals connection on the OPTBE board, see jumper settings below:

NOTE! Be careful with the jumper settings, wrong settings may damage the encoder.

OPTBE LEDs

There are two LEDs on the OPTBE board:

  • Yellow LED (Board Status LED)
    Slow blinking – > Board state is ready Fast blinking – > Board state is faulted
  • Green LED (Encoder LED)

ON – > Encoder serial communication is OK OFF – > No serial connection to encoder

1.2   I / O t er mi n a l s o n OPTBE, enc o d er t er mi n a l X6

 

Terminal

Heidenhain colour code 

Technical data

1DATA+Grey 

Data line 120W/RS-485

2DATAPink
3CLOCK+VioletClock line 120W/RS- 485 (200kHz)
4CLOCKYellow
5A+, COS+Green/black 

1Vpp (±0.5V); impedance 120W; Max. input 350 kHz

6A ,COS-Yellow/black
7B+, SIN+Blue/black 

1Vpp (±0.5V); impedance 120W; Max. input 350 kHz

8B , SIN-Red/black
9GNDWhite/greenInput ground
 

10

 

Encoder voltage

 

Brown/green

Selectable encoder voltages: 5V, 12V and 15V Max. current consumption 300mA

Analog Sin/Cos signals deserve some more precautions for noise immunity than pulse encoders. It is recommended to use a cable which contains individual shield for each twisted pair. Use one pair for SIN+/SIN- signals, another pair for COS+/COS- signals, another pair for DATA+/DATA- signals and another pair for CLOCK+/CLOCK- signals.

1.3   OPTBE Pa r amet er s

Notes for selecting Operating Mode:

In modes “EnDat + Sin/Cos” and “SSI+Sin/Cos” Sin/Cos signals and absolute serial information are used:

  • Modes can be used in VACON®NXP option board slot
  • Closed loop motor control mode can be
  • Jumper X2 is installed into OPTBE board because Sin/Cos signals are In modes “Endat Only” and “SSI Only”, only the absolute serial information is used:
  • Modes can be used in VACON®NXP option board slots C, D and
  • Closed loop motor control mode cannot be Usage of closed loop in these modes causes Fault 43 (Encoder fault) with Subcode 10.
  • Jumper X2 is removed from OPTBE board because Sin/Cos signals are not
NumberPar ameterMinMaxDefaultNote
 

 

7.x.1.1

 

 

Operating Mode

 

 

4

 

 

8

 

 

4

4 = EnDat + Sin/Cos (default)

5 = EnDat Only

6 = SSI+Sin/Cos

7 = SSI Only

8 = Sin/Cos Only

7.x.1.2Pulse/revolution1655351024 
 

7.x.1.3

 

Invert direction

 

0

 

1

 

0

0 = No

1 = Yes

 

 

 

 

7.x.1.4

 

 

 

 

Reading rate

 

 

 

 

0

 

 

 

 

4

 

 

 

 

1

Time used to calculate speed actual value. Note: Use value 1 in Closed Loop mode.

0 = No

1 = 1 ms

2 = 5 ms

3 = 10 ms

4 = 50 ms

 

 

 

7.x.1.5

 

 

 

Interpolation

 

 

 

0

 

 

 

1

 

 

 

0

If activated, the sinusoidal incremental pulses are used to calculate the polar angle in order to optimize the encoder accuracy

0 = No

1 = Yes

 

7.x.1.6

 

SSI data coding

 

0

 

1

 

1

0 = Binary

1 = Gray

7.x.1.7SSI total bits05513 
7.x.1.8SSI revol bits0160 

1.4 OPTBE mo n i t o r ed va l u es

CodeMonitor ed valueUnitDescr iption
7.x.2.1Encoder frequencyHzEncoder frequency in Hz
7.x.2.2Encoder speedrpmEncoder Speed in rpm
7.x.2.3Com Counter Message counter for serial encoder communication 0-65535
 

7.x.2.4

 

Revolution counter

 In case multiturn encoders this monitored value counts the revolutions. 0- 65535
7.x.2.5Absolute position Hi word absolute position up from 16 bits to 32bits
7.x.2.6Absolute position Lo word absolute position up to 16 bits

SI N- COS OPTI ON BOARD OPTAK
OPTAK l a yo u t a n d d esc r i pt i o n

 Description:               Encoder board for VACON® NXP with an input for Sin/Cos type encoder.

Programmable control voltage.

Allowed slots:              C (Sin/Cos signals can only be used in slot C)

Type ID:                      16715

Terminals:                  One terminal block; Screw terminals (M2.6); No coding.

Jumpers:                    X1 (see page 10)

Board parameters:    Yes (see page 11)

Sin/Cos encoder produces a pair of analog sinusoidal signals. There are several sine cycles (for example 1024 or 2048) per mechanical revolution.

OPTAK j u mper set t i n gs

NOTE! It is recommended to use a 12 V or 15 V supply voltage instead of 5 V. OPTAK interface does not support “sense” function to compensate voltage drop with a long cabling. Therefore with 5 V supply voltage the cable length limit is about 60 meters with 0.5 mm2 wire section. With 5 V supply voltage it is recommended to use two or more wires in parallel for the supply connection.Jumper X1 selects encoder supply voltage on the OPTAK board, see jumper settings below:

NOTE! Be careful with the jumper setting, wrong voltage may damage the encoder.

2 . 3 I / O t er mi n a l s o n OPTAK, enc o d er t er mi n a l X6

TerminalTechnical data
1N.C. 

Not Connected

2N.C.
3R+Max 10Vpp (±5V), Min 1Vpp (±0.5V). Typically signal is ~2.5Vpp (±1.25V): at reference
mark moment positive signal, other time negative signal.
  
4R-Impedance 120Ω
  Max input 350 kHz
  Reference mark signal
5SIN+ 

1Vpp (±0.5V); impedance 120W; Max. input 350 kHz,

6SIN-
7COS+ 

1Vpp (±0,5V); impedance 120W; Max. input 350 kHz

8COS-
9GNDInput ground
 

10

 

Encoder voltage

Selectable encoder voltages: 5V, 12V and 15V Max. current consumption 300mA

NOTE! Analog Sin/Cos signals deserve some more precautions for noise immunity than pulse encoders. It is recommended to use a cable which contains individual shield for each twisted pair. Use one pair for SIN+/SIN- signals, another pair for COS+/COS- signals and another pair for R+/R- signals.

2 . 4 OPTAK p a r a met er s

NumberPar ameterMinMaxDefaultNote
7.3.1.1Pulse/revolution1655351024 
 

7.3.1.2

 

Invert direction

 

0

 

1

 

0

0 = No

1 = Yes

 

 

 

 

7.3.1.3

 

 

 

 

Reading rate

 

 

 

 

0

 

 

 

 

4

 

 

 

 

1

Time used to calculate speed actual value. Note: Use value 1 in Closed Loop mode.

0 = No

1 = 1 ms

2 = 5 ms

3 = 10 ms

4 = 50 ms

 

 

 

7.3.1.3

 

 

 

Interpolation

 

 

 

0

 

 

 

1

 

 

 

0

If activated, the sinusoidal incremental pulses are used to calculate the polar angle in order to optimize the encoder accuracy

0 = No

1 = Yes

2 . 5 OPTAK mo n i t o r ed va l u es

CodeMonitor ed valueUnitDescr iption
7.3.2.1Encoder frequencyHzEncoder frequency in Hz
7.3.2.2Encoder speedrpmEncoder Speed in rpm

I NSTALLATI ON

3 . 1 I n st al l i n g op t i on bo a r d s

Option boards OPTBE, OPTAK and OPTAR can only be used with VACON® NXP drives.
OPTAK and OPTAR can be connected to slot C. OPTBE board can be connected to slots C, D or E, but Sin/Cos signals can only be used in slot C. If OPTBE board is connected to slots D or E, the Sin/Cos signals have to be disconnected using the jumpers (see chapter 1.2).
Disconnect the drive from the mains before starting the installation.



 

 

Read More About This Manual & Download PDF:

Documents / Resources

Danfoss OPTBE Board Functional Extensions [pdf] User Manual
OPTBE Board Functional Extensions, OPTBE Board, Functional Extensions, Extensions

References

Leave a comment

Your email address will not be published. Required fields are marked *