Danfoss OP-FPZP Optyma Inverter
Information
- A: Model
- B: Code number
- C: Serial Number and bar code
- D: Supply voltage, Locked Rotor Ampere
- E: Housing Service Pressure
- F: Refrigerant
- G: Oil
Installation and servicing of the condensing units by qualified personnel only. Follow these instructions and sound refrigeration engineering practice relating to installation, commissioning, maintenance and service.
The condensing unit must only be used for its designed purpose(s) and within its scope of application.
Under all circumstances, the EN378 (or other applicable local safety regulation) requirements must be fulfilled.
The condensing unit is delivered under nitrogen gas pressure (1 bar), and hence it cannot be connected as it is; refer to the «installation» section for further details.
The condensing unit must be handled with caution in the vertical position (maximum offset from the vertical: 15°)
Danfoss Optyma™ INVERTER can work with more than one cold room, once these conditions are met:
- If the chambers have different operating setpoints (different evaporation temperatures, such as, for example, a cooling chamber and a freezing chamber), it is mandatory to use a KVP valve according to the diagram below. In case of any doubts, please refer to KVP application guide available in the Danfoss Product Store.
- The maximum value of the sum of the volumes of the evaporators operating with the same INVERTER condensing unit must not exceed 25 liters to obtain the maximum cooling capacity mentioned in the catalogue.
- Total refrigerant charge must not exceed 9.0 kg due to system pump down. The unit was designed to guarantee 40 meters of line for a total evaporator volume of 16.5 liters when operating at an evaporation temperature of -10°C.
- To obtain the maximum performance of the unit in relation to energy consumption, it is recommended to use electronic expansion valves in the refrigeration system.
Introduction
These instructions pertain to Optyma™ INVERTER condensing units OP-FPZP (R507A, R404A) used for refrigeration systems. They provide necessary information regarding safety and proper usage of This product.
The condensing unit includes following:
- Reciprocating compressor
- Microchannel heat exchanger
- Adjustable low- and High-Pressure switch
- Frequency INVERTER for Danfoss compressor
- Rotolock Valve Suction / Discharge
- Service valves Suction/ liquid
- Oil Separator
- AC Fan motor
- Weatherproof housing
- Filter drier
- Crankcase heater for the compressor
- Receiver with stop valve
- Sight glass
- Fully pre-wired electrical panel (Contactor)
Handling and storage
- It is recommended not to open the packaging before the unit is at its final place for installation.
- Handle the unit with care. The packaging allows for the use of a forklift or pallet jack. Use appropriate and safe lifting equipment.
- Store and transport the unit in an upright position.
- Store the unit between -35°C and 50°C.
- Don’t expose the packaging to rain or a corrosive atmosphere.
- After unpacking, check that the unit is complete and undamaged.
Installation precautions
- Do not braze as long as the condensing unit is under pressure.
- Never place the unit in a flammable atmosphere
- Place the unit in such a way that it is not blocking or hindering walking areas, doors, windows or similar.
- Ensure adequate space around the unit for air circulation and to open doors. Refer to picture 1 for the minimal values of distance to walls.
- Avoid installing the unit in aggressive and dusty environments.
- Ensure a foundation with a horizontal surface (less than 3° slope), strong and stable enough to carry the entire unit weight and to eliminate vibrations and interference.
- The unit ambient temperature may not exceed 50°C during off-cycle.
- Ensure that the power supply corresponds to the unit characteristics (see nameplate).
- When installing units for HFC refrigerants, use equipment specifically reserved for HFC refrigerants which was never been used for CFC or HCFC refrigerants.
- Use clean and dehydrated refrigeration-grade copper tubes and silver alloy brazing material.
- Use clean and dehydrated system components.
- The suction piping connected to the condensing unit must be flexible in 3 dimensions to dampen vibrations. Furthermore, piping has to be done in such a way that oil return for the compressor is ensured and the risk of liquid slug over in the compressor is eliminated.
Installation
- The unit must be securely installed on a stable and rigid support and fixed from the beginning. See picture 2.
- It is recommended to install the unit on rubber grommets or vibration dampers (not supplied).
- Slowly release the nitrogen holding charge through the schrader port.
- Connect the unit to the system as soon as possible to avoid oil contamination from ambient moisture.
- Avoid material entering into the system while cutting tubes. Never drill holes where burrs cannot be removed.
- Braze with great care using state-of-the-art technique and vent piping with nitrogen gas flow.
- Connect the required safety and control devices. When the schrader port is used for this, remove the internal valve.
- It is recommended to insulate the suction pipe up to the compressor inlet minimum of 19 mm thick insulation.
Leak detection
- Never pressurize the circuit with oxygen or dry air. This could cause fire or explosion.
- Do not use dye for leak detection.
- Perform a leak detection test on the complete system.
- The maximum test pressure is 32 bar.
- When a leak is discovered, repair the leak and repeat the leak detection.
Vacuum dehydration
- Never use the compressor to evacuate the system.
- Connect a vacuum pump to both the LP & HP sides.
- Pull down the system under a minimum vacuum value of 500 μm Hg (0.67 mbar) absolute. • Do not use a megohmmeter nor apply power to the compressor while it is under vacuum, as this may cause internal damage.
Electrical connections
- Switch off and isolate the main power supply.
- Ensure that the power supply can not be switched on during installation.
- All electrical components must be selected as per local standards and unit requirements.
- Refer to the wiring diagram for electrical connection details.
- Ensure that the power supply corresponds to the unit characteristics and that the power supply is stable (nominal voltage ±10% and nominal frequency ±2,5 Hz).
- Dimension the power supply cables according to the unit data for voltage and current.
- Protect the power supply and ensure correct earthing.
- Make the power supply according to local standards and legal requirements.
- The unit is equipped with high and low pressure switches, which directly cut the power supply to the compressor in case of activation. Parameters for high and low pressure cut-outs should be set by installing, considering the compressor model, refrigerant and application.
Filling the system
- Wear protective stuff like goggles and protective gloves.
- Never start the compressor under vacuum. Keep the compressor switched off.
- Before charging the refrigerant, verify that the oil level is between ¼ and ¾ on the compressor oil sight glass. If additional oil is required please refer to the compressor’s label for the type of oil.
- Use only the refrigerant for which the unit is designed.
- Fill the refrigerant in the liquid phase into the condenser or liquid receiver. Ensure a total System
The charge must not exceed 9,0 kg due to the pump-down capacity of the system. - The system is designed to guarantee 40 40-meter line distance for a maximum sum of evaporator volume of 16.5 liters at evaporating temperature = -10°C. The maximum sum of evaporator internal volume should not exceed 25 liters.
- Do not put liquid refrigerant through the suction line.
- It is not allowed to mix additives with the oil and/or refrigerant
- The remaining charge is done until the installation has reached a level of stable nominal condition during operation.
- Never leave the filling cylinder connected to the circuit.
Verification before commissioning
- Use safety devices such as a safety pressure switch and a mechanical relief valve in compliance with both generally and locally applicable regulations and safety standards. Ensure that they are operational and properly set.
- Check that the settings of high-pressure switches and relief valves don’t exceed the maximum service pressure of any system component.
• Verify that all electrical connections are properly fastened
and in compliance with local regulations.
• The condensing unit must be energized at least
12 hours before initial start-up and start-up after
prolonged shut-down period.
Start-up
- Never start the unit when no refrigerant is charged.
- All service valves must be in the open position.See picture 3.
- Check compliance between unit and the power supply.
- Check that the crankcase heater is working and was initiated 12 hours before.
- Check that the fan can rotate freely.
- Check that the cardboard protection sheet has been removed from the backside of the condenser.
- Respect the operating limits, high pressure can not be higher than 7 bar at a temperature of 5ºC, and low pressure can not be lower than 2 bar at a temperature of -30ºC
- Turn on the unit by connecting the cables coming from the electrical panel (customer) to the available connectors,and turn the main switch from the OFF (0) position to the ON (1) position. Its operation should start immediately. If not, follow the steps below:
Check with the running unit
- Check the fan rotation direction. Air must flow from the condenser towards the fan.
- Check the current draw and voltage.
- Check suction superheat to reduce the risk of slugging.
- When a sight glass is provided, observe the oil level at start and during operation to confirm that the oil level remains visible.
- Respect the operational limits demonstrated in the envelopes of the condensing unit in Range (T. Evap: -30ºC to 5 ° C, T. AMB: 10 ° C to 43 ° C)
- Check all tubes for abnormal vibration. Movements in excess of 1.5 mm require corrective measures such as tube brackets.
- When needed, additional refrigerant in the liquid phase may be added in the low-pressure side as far away as possible from the compressor. The compressor must be operating during this process.
- Do not overcharge the system.
- Never release refrigerant to the atmosphere.
- Before leaving the installation site, carry out a general installation inspection regarding cleanliness, noise, and leak detection.
- Record type and amount of refrigerant charge as well as operating conditions, as a reference for future inspections.
Maintenance
Always switch off the unit at the main switch before removing the fan panel. Internal pressure and surface temperature are dangerous and may cause permanent injury. Maintenance operators and installers require appropriate skills and tools. Tubing temperature may exceed 100°C and can cause severe burns. Ensure that periodic service inspections to ensure system reliability, and as required by local regulations, are performed.
To prevent system-related problems, the following
Periodic maintenance is recommended:
- Verify that safety devices are operational and properly set.
- Ensure that the system is leak-tight.
- Check the compressor current draw.
- Confirm that the system is operating in a way consistent with previous maintenance records and ambient conditions.
- Check that all electrical connections are still adequately fastened.
- Keep the unit clean and verify the absence of rust and oxidation on the unit components, tubes, and electrical connections. Check the level and color of the oil to see if it is clean and sufficient to turn on the compressor, indicating a level of 3/4 of the total capacity.
The condenser must be checked at least once a year for clogging and be cleaned if deemed necessary. Access to the internal side of the condenser takes place through the fan panel. Microchannel coils tend to accumulate dirt on the surface rather than inside, which makes them easier to clean than fin-&-tube coils.
- Switch off the unit at the main switch before removing any panels from the condensing unit.
- Remove surface dirt, leaves, bres, etc., with a vacuum cleaner, equipped with a brush or other soft attachment. Alternatively, blow compressed air through the coil from the inside out, and brush with a soft bristle. Do not use a wire brush. Do not impact or scrape the coil with the vacuum tube or air nozzle. Do not use high high-pressure washer. If the refrigerant system has been opened, the system has to be flushed with dry air or nitrogen to remove moisture and a new filter-drier has to be installed. If evacuation of refrigerant must be done, it shall be done in such a way that no refrigerant can escape to the environment.
Warranty
Always transmit the model number and serial number with any claim filed regarding this product.
The product warranty may be void in the following cases:
- Absence of nameplate.
- External modifications, in particular, drilling, welding, broken feet, and shock marks.
- Compressor opened or returned without seal of warranty or seal violated.
- Rust, water, or leak detection dye inside the compressor or any other fluid different of the recommended.
- Use of a refrigerant or lubricant not approved by Danfoss.
- Any deviation from recommended instructions pertaining to installation, application or maintenance.
- Use in mobile applications.
- Use in an explosive atmospheric environment.
- No model number or serial number was transmitted with the warranty claim.
Delivery
When the condensing unit is hoisted with ropes for delivery, take care to maintain the center of gravity. It could drop off if the stability is lost.
- Determine the delivery route and deliver the unit to the installation place without removing the packing. When hoisting the unit, use a pair of ropes and cushioning material to protect sections chafed by ropes.
Disposal
Danfoss recommends that condensing units and oil be recycled by a suitable company at its site.
Frequency by-pass
If it is necessary to change the inverter, parameterize 4 frequency ranges in order to avoid resonance in the piping system in the specied range, according to the procedure below:
- Access the Main Meu of your INVERTER display available on the electrical box (image 1 and image 2). Then select Limits / Warnings (image 3).
- Using the arrow – select 4-6 Speed Bypass and click “OK” button – display will appear as image below (image 1). You have the possibility to skip 04 independent frequency path [0], [1], [2] and [3].
- Click “OK” to define the first frequency range on the first available path [0]. With the arrow adjust frequency from: 30 Hz; Press button “Back” and then press the arrow to scroll down the cursor, and you will be able to adjust frequency to: 33 Hz.
- Make the same procedure to:
[1]: from 36Hz (2160rpm) to 39Hz (2340rpm).
[2]: from 51Hz (3060rpm) to 55Hz (3300rpm).
[3]: from 75Hz (4500rpm) to 77Hz (4620rpm).
Crankcase resistance connection.
When the machine is energized, the Carter Resistor is on 100% of the time, to ensure that the oil is always at the correct temperature. However, before the first start, we must leave it running for 12 hours, so that the oil reaches the necessary viscosity so that there are no problems when starting. To do this, simply energize the machine and turn the On/O switch on the Panel door. Once this is done, the crankcase heater will be on, and after 12 hours, you will be able to start up your condensing unit Optyma™ INVERTER.
Setting the Electronic Controller
- The unit is equipped with an electronic controller that is factory-programmed with parameters for use with the specific unit. Refer to manual 158381 for details.
- By default, the electronic controller display shows the temperature corresponding to the suction pressure in °C. To display the temperature for the condensing pressure, press the lower button (see picture 2).
- The electronic controller is factory set to operate with refrigerant R404A/R507. The use of any other refrigerant is not allowed with the LAM Inverter.
- If necessary, change parameter r23 to the desired suction pressure temperature (°C/°F).
- Adjust parameter c33 to set the pump-down value according to your needs.
- Press the middle button; the default maximum discharge temperature is 125°C.
- If the customer wants to increase this value, press the upper button to select the new value (e.g., 130°C), then press the middle button to confirm the selected value.
- The maximum allowable discharge temperature (r84) must not exceed 130°C.
Annex – A
GA & PID Drawings
OP – FPZP086
OP – FPZP086
Line Color Table
- Red Line – High Pressure Line
- Blue Line – Liquid Line
- Green Line – Suction Line
- Black Line – Oil Line
Annex – B
Wiring Diagram
Legend
Code V: 380V / 3F / 50-60Hz
Contact
Danfoss do Brasil Ind. e Com. Ltda.
- Climate Solutions
- danfoss.com.br
- +55 0800 87 87 847
- sac.brasil@danfoss.com
Frequently Asked Questions
- Q: Can I change the inverter frequency?
- A: If necessary, you can change the inverter frequency by parameterizing four frequency ranges to avoid resonance in the piping system. Refer to the manual for detailed instructions on how to do this.
Documents / Resources
![]() |
Danfoss OP-FPZP Optyma Inverter [pdf] Instruction Manual OP-FPZP Optyma Inverter, OP-FPZP, Optyma Inverter, Inverter |