General features

MCX08M2 is an electronic controller that holds all the typical functionalities of MCX controllers in the compact size of 8 DIN modules: programmability, connection to the CAN bus local network, Modbus RS485 serial communication interface.
MCX08M2 with TTL version is moreover available in the version with display and power supply 110 – 230 V AC.

MCX08M2 with TTL

 MCX08M2 with TTL
ANALOG INPUTS
NTC, 0/1 V, 0/5 V, 0/10 V, PT1000, selectable via software4
Universal NTC, Pt1000, 0/1 V, 0/5 V, 0/10 V, ON/OFF, 0/20 mA, 4/20 mA, selectable via software4
Total number8
DIGITAL INPUTS
Voltage free contact8
Total number8
ANALOG OUTPUTS
0/10 V DC optoisolated2
0/10 V DC, PWM, PPM selectable via software2
Total number4
DIGITAL OUTPUTS
SPST relay 16 A (normally open contacts)2
SPST relay 8 A (normally open contacts)2
SPDT relay 8 A (changeover contacts)4
Total number8
OTHERS
Power supply 110 V / 230 V AC
Connection for programming key
Connection for remote display and keyboard
Buzzer
CANbus
RTC clock
Modbus RS-485 serial interface
Serial TTL
Dimensions (DIN modules)8
MountingDIN rail

General features and warnings

Plastic housing features

  • DIN rail mounting complying with EN 60715
  • Self extinguishing V0 according to IEC 60695-11-10 and glowing/hot wire test at 960 °C according to IEC 60695-2-12
  • Ball test: 125 °C according to IEC 60730-1. Leakage current: ≥ 250 V according to IEC 60112

Other features

  • Operating conditions CE: -20T60 / UL: 0T55, 90% RH non-condensing
  • Storage conditions: -30T80, 90% RH non-condensing
  • To be integrated in Class I and/or II appliances
  • Index of protection: IP40 only on the front cover
  • Period of electric stress across insulating parts: long
  • Suitable for use in environments with degree of pollution 2
  • Category of resistance to heat and fire: D
  • Immunity against voltage surges: category II
  • Software class and structure: class A

Compliance
This product is designed to comply with the following EU standards:

  • Low voltage directive LVD 2014/35/EU:
    • EN60730-1: 2011 (Automatic electrical control for household and similar use. General requirements)
    • EN60730-2-9: 2010 (Particular Requirements for Temperature Sensing Controls)
  • Electromagnetic compatibility EMC directive 2014/30/EU:
    • EN 61000-6-3: 2007 +A1: 2011 (Emission standard for residential, commercial and light-industrial environments)
    • EN 61000-6-2: 2005 (Immunity for industrial environments)
  • RoHS directive 2011/65/EU and 2015/863/EU:
    • EN50581: 2012

UL approval:

  • UL file E31024

General warnings

  • Every use that is not described in this manual is considered incorrect and is not authorised by the manufacturer
  • Verify that the installation and operating conditions of the device respect the ones specified in the manual, especially concerning the supply voltage and environmental conditions
  • This device contains live electrical components therefore, all the service and maintenance operations must be performed by qualified personnel
  • The device can’t be used as a safety device
  • Liability for injury or damage caused by the incorrect use of the device lies solely with the user

Installation warnings

  • Mounting position recommended: vertical
  • The installation must be executed accordin tog the local standards and legislation of the country
  • Always operate on the electrical connections with the device disconnected from the main power supply
  • Before carrying out any maintenance operations on the device, disconnect all the electrical connections
  • For safety reasons, the appliance must be fitted inside an electrical panel with no live parts accessible
  • Don’t expose the device to continuous water sprays or to relative humidity greater than 90%.
  • Avoid exposure to corrosive or pollutant gases, natural elements, environments where explosives or mixes of flammable gases are present, dust, strong vibrations or shock, large and rapid fluctuations in ambient temperature that in combination with high humidity, can condensate, strong magnetic and/or radio interference (e.g., transmitting antennae)
  • When connecting loads beware of the maximum current for each relay and connector
  • Use cable ends suitable for the corresponding connectors. After tightening the screws of connectors, slightly tug the cables to check their tightness
  • Use appropriate data communication cables. Refer to the Fieldbus Installation Guide for the kind of cable to be used and setup recommendations
  • Reduce the path of the probe and digital inputs cables as much as possible, and avoid spiral paths enclosing power devices. Separate from inductive loads and power cables to avoid possible electromagnetic noise
  • Avoid touching or nearly touching the electronic components fitted on the board to avoid electrostatic discharges

DISCLAIMER

Professional Use Only
This product is not subject to the UK PSTI regulation, as it is for supply to and use only by professionals with the necessary expertise and qualifications. Any misuse or improper handling may result in unintended consequences. By purchasing or using this product, you acknowledge and accept the professional-use-only nature of its application. Danfoss does not assume any liability for damages, injuries, or adverse consequences (“damage”) resulting from the incorrect or improper use of the product and you agree to indemnify Danfoss for any such damage resulting from your incorrect or improper use of the product.

Danfoss-MCX08M2-TTL-Electronic-Controller-FIG-5Disposal instruction
Equipment containing electrical components may not be disposed of together with domestic waste. It must be separately collected with electrical and electronic waste according to local and valid legislation.

Technical specifications

Power supply

  • 85 – 265 V AC, 50/60 Hz. Maximum power consumption: 20 VA. Insulation between the power supply and the extra-low voltage: reinforced
  • 20 – 60 V DC e 24 V AC ± 15% 50/60 Hz SELV. Maximum power consumption: 10 W, 17 VA. Insulation between power supply and the extra-low voltage: functional
I/OTYPENUMSPECIFICATIONS
Analog inputsNTC 0 / 1V

0 / 10V PT1000

4AI5, AI6, AI7, AI8

Analog inputs are selectable via software between:

•     0 / 1 V, 0 / 5 V, 0 / 10 V : impedance is greater than 1M O

•     NTC (10 kO at 25 °C)

•     Pt1000

Universal4AI1, AI2, AI3, AI4

Universal analog inputs selectable via software between:

•     ON/OFF (current: 20 mA)

•     0/1 V, 0/5 V, 0/10 V : impedance is greater than 1M O

•     0/20 mA, 4/20 mA

•     NTC (10 kO at 25 °C)

•     Pt1000

12 V+ power supply 12 V DC, 120 mA max for 4/20 mA transmitter (total on all outputs)

5 V+ power supply 5 V DC, 100 mA max for 0/5 V transmitter (total on all

outputs)

Digital inputVoltage-free contact8DI1, DI2, DI3, DI4, DI5, DI6, DI7, DI8

Current consumption: 10 mA

Analog outputs0 / 10 V DC options2AO3, AO4

•     Analog outputs optoisolated 0/10 V DC, minimum load 1K O (10 mA) for each output

 PWM PPM

0 / 10 V DC

2AO1, AO2

Analog outputs are selectable via software between:

•     0/10 V dc minimum load 1K O (10 mA) for each output

•     pulsing output, synchronous with the line, at modulation of impulse position (PPM) or modulation of impulse width (PWM)

•     pulsing output, at modulation of impulse position (PPM) with range 20 Hz to 1 KHz: open circuit voltage: 6.8 V

Digital outputRelay8Insulation between the relay: functional

Insulation between relays and the extra-low voltage parts: reinforced. Total current load limit: 32 A

C1-NO1, C2-NO2

High inrush current (80 A – 20 ms) normally open contact relays 16 A Characteristics of each relay:

•     10 A 250 V AC for resistive loads – 100.000 cycles

•     3.5 A 230 V AC for inductive loads – 230.000 cycles with cos(phi) = 0.5

C5-NO5, C6-NO6

Normally open contact relays 8 A. Characteristics of each relay:

•     6 A 250 V AC for resistive loads – 100.000 cycles

•     4 A 250 V AC for inductive loads – 100.000 cycles with cos(phi) = 0.6

C3-NO3-NC3, C4-NO4-NC4, C7-NO7-NC7, C8-NO8-NC8

Changeover contacts relay 8 A. Characteristics of each relay:

•     6 A 250 V AC for resistive loads – 100.000 cycles

•     4 A 250 V AC for inductive loads – 100.000 cycles with cos(phi) = 0.6

Connection diagram

TOP BOARD

Danfoss-MCX08M2-TTL-Electronic-Controller-FIG-2

BOTTOM BOARD

Danfoss-MCX08M2-TTL-Electronic-Controller-FIG-3

Connection

ConnectorsTypeDimensions
Top Board
Analog output 1-4 connector7 way screw plug-in connector type•      pitch 5 mm

•      section cable 0.2 – 2.5 mm²

Analog input 1-4 connector11 way screw plug-in connector type•      pitch 5 mm

•      section cable 0.2 – 2.5 mm²

Digital input 1-8 connector10 way screw plug-in connector type•      pitch 5 mm

•      section cable 0.2 – 2.5 mm²

Analog input 5-8 connector5 way screw plug-in connector type•      pitch 5 mm

•      section cable 0.2 – 2.5 mm²

TTL connector (only for 080G0335)5 way spring plug-in connector type•      pitch 2.5 mm

•      section cable 0.2 – 2.5 mm²

Bottom Board
Power supply connector2 way screw plug-in connector type•      pitch 5 mm

•      section cable 0.2 – 2.5 mm²

CAN connector4 way screw plug-in connector type•      pitch 5 mm

•      section cable 0.2 – 2.5 mm²

CAN-RJ connector6/6 way telephone RJ12 plug type 
RS485 connector3 way screw plug-in connector type•      pitch 5 mm

•      section cable 0.2 – 2.5 mm²

Digital output 1-2 connector4 way screw plug-in connector type•      pitch 5 mm

•      section cable 0.2 – 2.5 mm²

Digital output 3-4 connector6 way screw plug-in connector type•      pitch 5 mm

•      section cable 0.2 – 2.5 mm²

Digital output 5-6 connector4 way screw plug-in connector type•      pitch 5 mm

•      section cable 0.2 – 2.5 mm²

Digital output 7-8 connector6 way screw plug-in connector type•      pitch 5 mm

•      section cable 0.2 – 2.5 mm²

User interface

LCD Display
Display mode: STN blue transmissive
Backlight: white LED backlight adjustable via software
Display format: 128 x 64 dots
Active visible area : 58 x 29 mm
Contrast: adjustable via software

Keyboard
Number of keys: 6
Keys function is settled by the application software

Display settings adjustment
Setting of the LCD display like contrast and brightness might need to be adjusted due to external ambient factors. Press and release simultaneously the Enter and X key after power ON to access the BIOS menu and select the DISPLAY menu. Use UP and DOWN arrow keys to adjust the contrast or the brightness of the display at the desired level.

Dimensions

Danfoss-MCX08M2-TTL-Electronic-Controller-FIG-4

Product part numbers

DescriptionCode No.
MCX08M2, 230 V, LCD, RS485, TTL, Single Pack080G0335

Accessories part numbers

DescriptionCode No.
MCX08M CONNECTORS KIT080G0180

CONTACT

Via San Giuseppe 38/G 31015 Conegliano

(TV) Italy

  • Tel: +39 0438 336611
  • Fax:+39 0438 336699

info.mcx@danfoss.com
www.danfoss.com

Danfoss-MCX08M2-TTL-Electronic-Controller-FIG-1

Danfoss A/S
Climate Solutions • danfoss.com • +45 7488 2222

Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material.

Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivere,d provided that such alterations can be made without changes to form, fit or function of the product.

All trademarks in this material are the property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.

Documents / Resources

Danfoss MCX08M2 TTL Electronic Controller [pdf] Installation Guide
MCX08M2, MCX08M2 TTL Electronic Controller, TTL Electronic Controller, Electronic Controller, Controller

References

Leave a comment

Your email address will not be published. Required fields are marked *