Danfoss KVP 12 Pressure Regulating Valve
Specifications
- Product Name: Pressure Regulating Valve
- Models: KVP, KVL, KVR, KVD, KVC
- Refrigerants:
- KVP: R22, R1270*, R134a, R290*, R404A, R407A, R407C, R407F,
R448A, R449A, R450A, R452A, R507A, R513A, R600*, R600a*
- KVP: R22, R1270*, R134a, R290*, R404A, R407A, R407C, R407F,
- Material: 15% Ag
- Tightening Torques:
- KVL: 3Nm (finger tight + 1/4 turn)
- KVR: 3Nm (finger tight + 1/2 turn)
- Maximum Pressure: 18 bar (260 psig)
Installation
- Ensure the correct model of the pressure regulating valve based on your requirements.
- Follow the recommended tightening torques when installing the valve to prevent leaks.
- Refer to the specific installation guide for each model for detailed installation steps.
Maintenance
Regularly check for any leaks or damage to the valve. If there are any issues, consult a professional for maintenance or repair.
Safety Precautions
- Always handle the valve with care to avoid any damage.
- Do not exceed the maximum pressure rating to prevent accidents.
- When using flammable refrigerants, ensure that the tightening torques are respected to maintain safety.
Installation guide
Pressure regulating valve KVP, KVL, KVR, KVD, KVC
Refrigerants:
- R22, R1270*, R134a, R290*, R404A, R407A, R407C, R407F, R448A, R449A, R450A, R452A, R507A, R513A, R600*, R600a*
- Applicable for KVP 12 – KVP 22, KVL 12 – KVL 22, KVR 12 – KVR 22, KVD 12 – KVD 15, KVC 12 – KVC 22
- For a complete list of approved refrigerants, visit www.products.danfoss.com and search for individual code numbers, where refrigerants are listed as part of technical data.
NB!
Tightening torques must be respected, especially when used with flammable refrigerant.s
KVP |
KVP 12 |
360° ~ 0.45 bar (6 psi) |
|
KVP 15 | |||
KVP 22 | |||
KVP 28 |
360° ~ 0.30 bar (4 psi) |
||
KVP 35 | |||
KVL |
KVL 12 |
360° ~ 0.45 bar (6 psi) |
|
KVL 15 | |||
KVL 22 | |||
KVL 28 |
360° ~ 0.30 bar (4 psi) |
||
KVL 35 | |||
KVC |
KVC 12 |
360° ~ 0.45 bar (6 psi) |
|
KVC 15 | |||
KVC 22 | |||
KVR |
KVR 12 |
360° ~ 2.50 bar (36 psi) |
|
KVR 15 | |||
KVR 22 | |||
KVR 28 |
360° ~ 1.50 bar (22 psi) |
||
KVR 35 | |||
KVD |
KVD 12 |
360° ~ 2.50 bar (36 psi) |
|
KVD 15 | |||
KVD 22 |
tmax | tmin | PS/MWP | |
KVP | 130 °C (265 °F) | -45 °C (-50 °F) | 18 bar (260 psig) |
KVL | 130 °C (265 °F) | -60 °C (-75 °F) | 18 bar (260 psig) |
KVR, KVD, KVC | 130 °C (265 °F) | -45 °C (-50 °F) | 28 bar (406 psig) |
FAQs
- Q: What should I do if I notice a leak in the pressure regulating valve?
A: If you notice a leak, immediately shut off the system and contact a professional for inspection and repair. - Q: Can I use refrigerants not listed in the manual with this valve?
A: It is recommended to only use refrigerants listed in the manual to ensure proper functioning and safety of the valve.
Documents / Resources
![]() |
Danfoss KVP 12 Pressure Regulating Valve [pdf] Installation Guide KVP 12, KVP 15, KVP 22, KVP 28, KVP 35, KVL 12, KVL 15, KVL 22, KVL 28, KVL 35, KVC 12, KVC 15, KVR 12, KVR 15, KVR 22, KVR 28, KVR 35, KVD 12, KVD 15, KVD 22, KVP 12 Pressure Regulating Valve, KVP 12, Pressure Regulating Valve, Regulating Valve |