KPU 19 Temperature and Pressure Controls

Danfoss-KPU-19-Temperature-Pressure-Controls-product

Specifications

KPU 19 Thermostats

  • Bulb type: Remote bulb
  • Contact/Reset: -30 to 80 SPST/Auto
  • Capillary tube length: 3.6 to 12.6 inches
  • Maximum tube length at lowest bulb: 140 inches

KPU 60/70 Thermostats

  • Bulb type: Straight capillary tube
  • Contact/Reset: -20 to 60 SPDT/Auto
  • Capillary tube length: 80 inches
  • Differential at lowest temp. setting: 10 to 40
  • Differential at highest temp. setting: 2.5 to 13

KPU Pressure Switches

  • Pressure system: 6 to 108 in. Hg/psig
  • Reset: Low Automatic SPDT
  • Contact range: 10 to 60 psig
  • Max. working pressure: 250 psig

KPU Dual Pressure Switches

  • Low-pressure side range: 6 to 108 in. Hg/psig
  • High-pressure side range: 100 to 465 psig
  • Reset: Automatic SPST (NO/NC)
  • Max. working pressure (low/high side): 250/510 psig

KPU temperature and pressure controls are designed for easy installation and service. They feature bottom and rear knockouts, a differential adjustment dial, a tamper-resistant design, and a robust thermoplastic housing. Danfoss KPU temperature and pressure controls maintain precise set point values and are easy to set and adjust. Learn more about how to select the right Danfoss products for your needs at choose.danfoss.com. Reliable temperature and pressure controls designed for flawless performance.

Technical data and ordering

KPU 19 Thermostats

KPU

Series

 

Bulb type

Range (°F) Contact/ Reset Capillary tube length (in.)  

at lowest temp. setting

Maximum bulb

temperature (°F)

Competitor part no. Danfoss type  

Danfoss Code No.

 

 

KPU 19

 

 

 

 

Remote bulb

 

 

−30 to 80

 

 

SPDT/Auto

 

 

120

 

 

3.6 to 12.6

 

 

140

A19ABC-24C A19ABC-37C A19ABC-74C A19AAC-4C A19AAF-20C  

 

KPU19

 

 

060L21501

 

KPU 19

 

−30 to 80

 

SPST/Auto

 

80

 

3.6 to 12.6

 

140

A19AAD-5C A19ABA-40C A19AAD-12C  

KPU19

 

060L21511

 

 

KPU 19                 Room bulb

 

 

−30 to 80

 

 

SPDT/Auto

 

 

Room sensor

 

 

3.6 to 12.6

 

 

140

A19BBC-2C A19BAB-3C A19BAC-1C A19BAF-1C  

 

KPU19

 

 

060L2152

As 060L1250 is SPDT, 060L2150 can replace competitor parts crossed to both 060L2150 and 060L2151.

KPU 60/70 Thermostats

 

Danfoss Type

 

Bulb type

 

Range (°F)

 

Contact/ Reset

Capillary tube length (in.) Di erential Maximum bulb

temperature (°F)

 

Competitor part no.

 

Danfoss Code No.

at lowest temp. setting at the highest temp. setting
KPU 61  

 

Remote air coil

 

 

−20 to 60

 

 

SPDT/Auto

 

 

80

 

 

10 to 40

 

 

2.5 to 13

 

 

250

O10-1408 O10-1409 O10-1473 O16-104 O10-1410  

 

060L5203

O10-1072
KPU 62 Room sensor −20 to 60 SPDT/Auto Room sensor 10 to 40 2.5 to 13 250 O10-1418

O16-594

060L5206
O60-101
 

KPU 73

 

Remote bulb

 

-15 to 60

 

SPDT/Auto

 

80

 

6.5 to 32

 

5 to 50

 

175

 

O60-100 O60-120

 

060L5208

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary for specications already agreed. All trademarks in this material are the property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

KPU Pressure Switches

 

Danfoss Type

 

Pressure

 

Reset

 

Contact system

 

Range (in. Hg/psig)

 

Differential (psig)

Max. working pressure (psig)  

Competitor part no.1

Danfoss Code No.
¼ in. M flare 36 in. capillary tubes with ¼ in. flare nuts
O10-1402
KPU 2 Low Automatic SPST (NO) 6 to 73 6 to 30 250 P70AB-12C 060-5237 060-5235
P170AB-12C
 

KPU1B

 

Low

 

Manual

 

SPDT

 

28 to 100

 

10.2

 

250

 

060-5232

 

060-5234

O16-108
KPU 6W2 High Automatic SPDT 100 to 600 58 to 145 675 P170CA-400C 060-5243 060-5245
P70CA-3C

KPU Dual Pressure Switches

 

 

 

Danfoss Type

 

Low-pressure side

 

High-pressure side

Reset  

 

Contact system (LP/HP)

 

 

Max. working pressure (low/high side) (psig)

 

 

 

Competitor part no.1

 

Danfoss Code No.

 

Range (in. Hg/psig)

 

Differential (psig)

 

Range (psig)

 

Differential (psig)

 

Low-pressure side

 

High-pressure side

 

¼ in. M flare

36 in. capillary tubes with

¼ flare

nuts

KPU 15                 6 to 108               10 to 60          100 to 465 Automatic Automatic SPST 250/510 O12-1549 060-5247 060-5248
(NO/NC) P170LB-1C
KPU 15B 6 to 108 10 to 60 100 to 465 Automatic Manual SPST 250/510 P70LB-1C 060-5249 060-5250
60 (NO/NC) P70MA-1C
O12-4834
KPU 16B               6 to 108               10 to 60          100 to 600 Convertible3 Convertible3 SPDT/

SPST (NO)

250/675 P170LB-1C

P70LB-1C

060-5253 060-5254
P70MA-1C
  1. Competitor part no. equipped with a capillary tube for all but P170LB-1C which has connections.
  2. KPU 6 and the high-pressure side of KPU 16 are designed with fail-safe double bellows.
  3. Convertible reset controls can be adjusted for either automatic or manual reset. Adjust the reset setting to match the product being replaced.

All controls are supplied with universal mounting brackets and mounting screws. Ambient temperature: −40 °F to +122 °F (175 °F for maximum 2 hours). KPUs 1, 2, 6, and 16 are suitable for all HFC refrigerants, including R-410A.

Danfoss-KPU-19-Temperature-Pressure-Controls-fig-1

Spare Parts and Accessories

For the complete portfolio of KPU products, scan the QR code to access the Quick Select Guide.

Danfoss-KPU-19-Temperature-Pressure-Controls-fig-2

Installation

  1. Ensure the power source is switched off before installation.
  2. Locate a suitable position for the temperature and pressure controls.
  3. Follow the provided guidelines for wiring and connections.

Setting and Adjusting

  1. Use the differential adjustment dial to set the desired temperature or pressure values.
  2. Make sure the controls are securely fastened in place after adjustment.

Maintenance

  1. Regularly check for any signs of wear or damage on the controls.
  2. Clean the controls as needed to ensure proper functioning.