Danfoss - logoInstallation guide
Pressure switch
Type KP 21

Ambient temperatures

Danfoss KP 21 Pressure Switch -

Warning icon Caution: Do not mount a switch in a position where dirt, sediment or oil will affect the operation of the switch.

Test pressure (p test)

Danfoss KP 21 Pressure Switch - Ambient temperatures

Enclosure

Danfoss KP 21 Pressure Switch - Enclosure

Warning icon CAUTION: The mounting panel must be plane to avoid damage of switch.

Danfoss KP 21 Pressure Switch - Low pressure

Danfoss KP 21 Pressure Switch - Low pressure1

Warning icon CAUTION: Disconnect power supply before wiring connections are made or service to avoid possible electrical shock or damage to equipment. Do never touch live parts with your fingers or with any tool.

Contact load
Alternating current:
AC 1: 16 A, 400 V
AC 3: 16 A, 400 V
AC15: 10 A, 400 V
Max. starting current (L.R.): 112 A, 400 V
Direct current:
DC13: 12 W, 220 V control current

Function

Danfoss KP 21 Pressure Switch - Low pressure2

Note!
= Load
Danfoss - icon1 = Signal option
Danfoss - icon2 = Bellows movement on pressure rise
Danfoss - icon3 = Bellows movement on pressure drop

Controls with low pressure (LP) and high pressure (HP) signal

Terminal block

Danfoss KP 21 Pressure Switch - Terminal block

Warning icon CAUTION: Use terminal screws furnished in the contact block.
Use tightening torque (20 lb.) in 2.3 Nm.
Use copper wire only.
Low pressure (LP) side:
A-C close on LP rise
A-C open on LP drop
High pressure (HP) side.
A-C open on HP rise
A-C close on HP drop
LP signal option:
A-B close on LP drop
HP signal option
A-D close on HP rise

AN104986438177en-000302
© Danfoss | Climate Solutions | 2021.07
Danfoss - logoDanfoss - icon060R9410
Info for UK customers only: Danfoss Ltd., 22 Wycombe End, HP9 1NB,

Documents / Resources

Danfoss KP 21 Pressure Switch [pdf] Installation Guide
KP 21 Pressure Switch, KP 21, Pressure Switch, Switch