Danfoss KP 1 Series Pressure Switch
Product Specifications
- Model Numbers: KP 1, KP 1W, KP 1A, KP 2, KP 4, KP 5, KP 5A, KP 6W, KP 6B, KP 6S, KP 6AW, KP 6AB, KP 6AS, KP 7W, KP 7B, KP 7S
- Refrigerants: R22, R134a, R404A, R407A, R407C, R407F, R410A, R422B, R422D, R448A, R449A, R452A, R507A, R513A, R717
- Test Pressure (Ptest) Range: Maximum values vary by model
- Regulation Range: Varies by model
- Enclosure: IP30 for some models, IP44 for others
- Electrical Rating: AC-3: 16 A / 250 V AC, AC-15: 10 A / 250 V AC
- Voltage: 250V AC
Product Usage Instructions
Ambient Temperatures
- KP 1, KP 2, KP 4: Specific ambient temperature and mounting requirements apply
- KP 5, KP 6, KP 7: Different ambient temperature and mounting requirements compared to KP 1, KP 2, KP 4
Connections
Ensure proper connections based on the model specifications. Test pressure values should not exceed the maximum working pressure.
Regulation Range
Adjust the regulation range according to the requirements of your system. Be aware of the maximum working pressure.
Connections for KP 1A, KP 5A, KP 6AS
Mounting
Follow the mounting guidelines provided in the manual. Use appropriate tools and materials for secure installation.
Electrical Wiring
Ensure power is disconnected before making any wiring connections. Follow the electrical rating guidelines for safe operation.
Enclosure
Adjustment and Reset
Use manual trip or automatic reset functions as needed. Follow the differential and range settings based on the model type.
Refrigerants
R22, R134a, R404A, R407A, R407C, R407F, R410A*) R422B, R422D, R448A, R449A, R452A, R507A, R513A, R717) For complete list of approved refrigerants, go to
http://products.danfoss.com/all-products
- only for KP 6W, KP 6B, KP 6S, KP 6AW, KP 6AB, KP 6AS
- only for KP 1A, KP 5A, KP 6AW, KP 6AB, KP6 AS
CAUTION
Disconnect power supply before wiring connections are made or service to avoid possible electrical shock or damage to equipment. Do never touch live parts with your fingers or with any tool.
AC 1: 16 A | DC 13 | ||
AC 3: 16 A | |||
400 V a.c. | 12 W | ||
220 V | |||
AC 15: 10 A |
- Short circuit protection: Fuse 16 Amp.
- When used acc. to UL regulations
- Listed refrigeration controller 61B5
Voltage | FL LR
A A |
Resist. load |
Pilot duty |
||
AC DC | |||||
240 | — | 8 | 48 | 8 A |
3A |
120 | — | 16 | 96 | 16 A | |
— | 240 | — | — | — | 12 W |
Use copper wire only. Tightening torque 20 lb.. in.
Manual trip function
Manual reset
Type | Differential |
KP 1, KP 1A | 0.7 bar (10 psi) |
KP 5, KP 5A | 3 bar (43 psi) |
KP 6B, KP 6S, KP 6AB, KP 6AS, KP 7B, KP 7S |
4 bar (58 psi) |
Adjustment
CAUTION
Only for selected A2L refrigerants: R455A, R454C, R1234yf, R1234yz, R1234ze For complete list of approved A2L refrigerants, go to http://products.danfoss.com all-products
Electrical rating
- AC-3: 16 A / 250 V AC
- AC-15: 10 A / 250 V AC
Voltage |
Current range |
Power factor
(cos phi) |
Frequency |
250V AC | ≤ 4.0 A | PF ≥ 0,400 | 50Hz/60Hz |
250V AC | > 4.0 to 6.0 A | PF ≥ 0,594 | 50Hz/60Hz |
250V AC | > 6.0 to 16,0 A | PF ≥ 0,780 | 50Hz/60Hz |
IMPORTANT NOTICE
Safety requirements
- KP pressure switches shall only be employed in the units/systems that comply with the requirements for charge limits and requirements for avoiding ignition sources of IEC 60335-2-24, IEC 60335-2-40, IEC 60335-2-89, ISO 5149, EN378-1, or equivalent.
- Applying the overload on the KPs must be prevented. If by any chance it was damaged, the system/unit shall be stopped, and KP shall be replaced as necessary.
- Electrostatic discharge protection and Electrical leakage protection shall be implemented by grounding or other measures.
- Only trained personnel are authorized to handle flammable refrigerants systems and may do the installation, maintenance and exchange of the switch by using appropriate tools.
- It is recommended to regularly check the function of the KP switch.
- KP pressure switches must be installed in an area with a low risk of mechanical damage.
- Corrosion protection of KP pressure switches must be taken into account when used in a corrosive environment.
- Cables shall not be in contact with sharp edges. The cables shall be connected with adequate stress relieve in order to prevent that pulling forces can be carried thorough the cable to the terminal.
- In the event of pressure pulsation in the system, where switch is connected, these must be effectively dumped to prevent failure of the bellows. The cycle frequency of KP switch shall be kept as low as possible.
- The KP switches shall not be installed in places where a high level of vibration is present.
Disclaimer
The user is responsible for ensuring that third parties also comply with this Notice, e.g., in case the KP switches are supplied to third parties, and e.g., that all installation guides are available with the KP switches during installation. It is required that all conditions of this guide are met and secured when using KP pressure switches. Danfoss shall not be responsible for any kind of direct and indirect, or consequential damage or loss, including, but not limited to, loss of property, production, loss of profit, human injury arising out of the explosion or fire caused by the flammable nature of refrigerant.
FAQs
Q: Can I use any refrigerant with this pressure switch?
A: No, only approved refrigerants listed in the manual should be used. Refer to the complete list for more information.
Q: What safety requirements should be considered when using this product?
A: Ensure compliance with specific safety standards mentioned in the manual to prevent hazards and ensure proper functioning.
Documents / Resources
![]() |
Danfoss KP 1 Series Pressure Switch [pdf] Installation Guide KP 1, KP 1W, KP 1A, KP 2, KP 4, KP 5, KP 5A, KP 6W, KP 6B, KP 6S, KP 6AW, KP 6AB, KP 6AS, KP 7W, KP 7B, KP 7S, KP 1 Series Pressure Switch, KP 1 Series, Pressure Switch, Switch |