Danfoss ICS 25-65 Servo Operated Valve

Danfoss-ICS-25-65-Servo-Operated-Valve-procyct

Installation

Refrigerants

Applicable to all common non-flammable refrigerants, including R717 and non-corrosive gases/liquids dependent on sealing material compatibility.
Flammable hydrocarbons are not recommended.
The valve is only recommended for use in closed circuits. For further information please contact Danfoss.

Temperature range

–60/+120°C (–76/+248°F)

Pressure range
The valves are designed for a max. working pressure of 52 bar g (754 psi g).

Technical data

The ICS can be used in suction, liquid, hotgas and liquid/vapor lines. The ICS regulates the flow of the medium by modulation or on/off function, depen ding on the control impulse from the screwed on pilot valve or valves.

Regulating range

Dependent on the chosen type and combination of pilot valves.

Opening differential pressure (p)

The ICS main valve requires a minimum opening differential pressure of 0.07 bar (1 psi) to begin to open and 0.2 bar (3 psi) to be completely open.
The valve must be protected against back pressure. A check valve should be installed upstream of the ICS in installations where there is a risk of back pressure. Back pressure can affect the correct position of the piston ring.

Design (fig. 4) 

Danfoss-ICS-25-65-Servo-Operated-Valve- (5)

  1. Body
  2. Top cover
  3. Function module
    3a Valve plate (available as spare part)
    3b Washer plate
  4. Gasket
  5. Bolts
  6. Plug
  7. Gasket
  8. Manual operating spindle
  9. Plug
  10. Gasket
  • The valve must be installed with the spindle in vertically upwards position (fig. 1).
  • The valve must be installed with the arrow in the direction of the flow and the top cover upwards (fig. 2). The top cover can be rotated 4 X 90° in relation to the valve body.
    Danfoss-ICS-25-65-Servo-Operated-Valve- (2) Danfoss-ICS-25-65-Servo-Operated-Valve- (3)
  • The valve is fitted with a spindle for manual opening. If an external pilot valve is used, the pilot line must be connected to the upper side of the main line so that any dirt and oil from the plant will not find its way into the pilot line.
  • If the ICS 1 is to be used as a solenoid valve in a liquid line, external control pressure cannot be recommended because it can cause liquid hammer.
  • The valve is designed to withstand a high internal pressure. However, the piping system should be designed to avoid liquid traps and reduce the risk of hydraulic pressure caused by thermal expansion. It must be ensured that the valve is protected from  pressure transients like “liquid hammer” in the system.

Welding (fig. 3, 4 and 5)
The top cover (fig. 4, pos. 2) and function module (fig. 4, pos. 3), must be removed before welding to prevent damage to o-rings and teflon (PTFE) in the function module and to avoid getting welding debris in the module.

Danfoss-ICS-25-65-Servo-Operated-Valve- (4)

The function module can be lifted out using a bolt size M6 or multi-function tool screwed into the threaded hole of the piston on the function module (fig. 3). Debris blocking the bolt hole will need cleaning.
Note: Remove all parts from the valve body  before welding (as shown in fig. 5).

Danfoss-ICS-25-65-Servo-Operated-Valve- (6)

The internal surfaces and weld connections of the enclosed ICS/ ICM valve have been applied with an anti-corrosion treatment.

  • In order to maintain the effectiveness  of this anti-corrosion treatment, it is important to ensure that the valve is disassembled just prior to the welding / brazing process being undertaken.
  • In the event that the function modules are to be left disassembled for any length of time, please ensure that the function modules are further protected by placing in a polyethylene bag or by applying a rust protection agent (e.g. refrigeration oil or BRANOROL) on the surfaces.
  • Only materials and welding methods, compatible with the valve body material, must be welded to the valve body. The valve should be cleaned internally to remove welding debris on completion of welding and before the valve is reassembled.
  • Avoid welding debris and dirt in the valve body and the function module. The valve body must be free from stresses  (external loads) after installation.
  • The valves must not be mounted in systems where the outlet side of the valve is open  to atmosphere. The outlet side of the valve must always be connected to the system  or properly capped off, for example with a welded-on end plate.

Assembly
Remove welding debris and any dirt from pipes and valve body before assembly. Check that the o-rings are intact before replacing the function module. If possible, apply some refrigeration oil to ease the insertion and to protect the o-rings. Check that the top gasket has not been damaged. If the surface has been damaged or the gasket has been bent, it must be replaced.

Tightening (fig. 6)
Tighten the top cover with a torque wrench, to the values indicated in the table.

Danfoss-ICS-25-65-Servo-Operated-Valve- (7)

Colours and identification
The ICS valves are Zinc-Chromated from factory. The Zinc-Chromatization does not cover the welding connections. If further corrosion protection is required, the valves can be painted.
Precise identification of the valve is made via the ID plate on the top cover.
The external surface of the valve housing must be protected against corrosion with  a suitable top coating after installation involving welding and consequent assembly. Protection of the ID plate when painting the valve is recommended.

The function module can be lifted out using a bolt size M6 screwed into the threaded hole of the piston on the function module (fig. 3). Debris blocking the bolt hole will need cleaning.

Upon opening and removal of the function module:

  • Check that the o-rings on the function module has not been damaged. A valve with a damaged o-ring might not modulate according to the specification.
  • Check that the piston and cylinder isfree of scratches and look for wear marks. If the wear is excessive the function module should be replaced to prevent false pilot signal around the piston ring.
  • Check that the movement of the cylinder and valve seat is free and with low friction.
  • If the teflon valve plate is damaged it must be replaced. It is available as spare part:
Type Code number
ICS 25 027H2222
ICS 32 027H3222
ICS 40 027H4222
ICS 50 027H5222
ICS 65 027H6222
ICS 80 027H8222

For mounting instructions please see DKRCI.PI.HS0.D.

Assembly
Remove any dirt from the body before the valve is assembled. Check that all channels in the valve are not blocked by particles or similar.
If possible, apply some refrigeration oil to ease the insertion and to protect the o-rings.

Tightening (fig. 6)
Tighten the top cover with a torque wrench, to the values indicated in the table.
Always carry out this operation when the manual operation device has been in use (see fig 7)

  1. Danfoss-ICS-25-65-Servo-Operated-Valve- (1)Remove the cap (A) and tighten the spindle (B) anticlockwise with 8 Nm (5.9 lb/ft)
  2. Remount the cap (A) and tighten it clockwise with 8 Nm (5.9 lb/ft)

Use only original Danfoss parts, including

  • O-rings and gaskets for replacement. Materials of new parts are certified for the relevant refrigerant.
  • In cases of doubt, please contact Danfoss.
  • Drawings are only for illustration, not for dimensioning or construction.
  • Danfoss accepts no responsibility for   errors and omissions. Danfoss Industrial Refrigeration reserves the right to make changes to products and specifications without prior notice.
  • The following text is applicable to the UL listed products ICS 25-65 Applicable to all common non-flammable refrigerants, including/excluding (+) R717 and to non-corrosive gases/liquids dependent on sealing material compatibility (++). The design pressure shall not be less than the value outlined in Sec. 9.2 of ANSI/ASHRAE 15 for the refrigerant used in the system. (+++).

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies already on order provided that such alterations can be made without changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.