Installation guide
Actuator
Type ICAD 600B / 600B-TS / 1200B
027R9001

ICAD 600B Motor Actuator

Danfoss ICAD 600B Motor Actuator - fig 1Danfoss ICAD 600B Motor Actuator - fig 2

Installation

Do not install ICAD before welding. This apply for electrical as well as for mechanical installation. Please observe that ICAD when connected to 24 V DC, will send out acoustic noise at stand still. This has no influence on the function/ operation of the ICAD.
Use
ICAD 600B, ICAD 600B-TS and ICAD 1200B can be used together with the following Danfoss valves (fig. 1, 5a and 5b).

ICAD 600B ICAD 600B-TS  ICAD 1200B
ICM 20 ICMTS 20 ICM 40
ICM 25 ICMTS 50 ICM 50
ICM 32 ICMTS 80 ICM 65
ICM 100
ICM 125
ICM 150
CVE pilot valve

Electrical data
Supply voltage is galvanically isolated from in-/output.
ICAD is a Class III product.
PSUs connected to ICAD must be SELV<100 VA For UL compliance: PSU must be Class 2 NEC
Supply voltage
24 V DC (Tolerances; see below table)
Load ICAD 600B, ICAD 600B-TS: 1.2 A ICAD 1200B: 2.0 A

24 Volt DC ONLY

Danfoss ICAD 600B Motor Actuator - icon 1 Please observe cable voltage drop.
Distance between the applied DC transformer and the ICAD terminal box may cause a voltage drop. Cross section of cables and size of DC transformer must be calculated so that the voltage at all time at the ICAD terminal box*, both during standstill and during operation of ICAD, is within this range:

Prefabricated ICAD cable length Code number 1.5 m
027H0426
3 m
027H0438
10 m
027H0427
15 m
027H0435
Voltage ICAD terminal
(600B/12006) [V DC]
Min. 21 22 23 24
Max. 26.4

* Do not measure inside the ICAD itself (value can be checked in ICAD B menu).
Fail safe supply
24 V DC (Tolerances; see table above)
Load ICAD 600B, ICAD 600B-TS: 1.2 A ICAD 1200B: 2.0 A
Data communication
RS 485: It is important that the installation of the data communication cable is done correctly. For further guidance, see literature No. RC8AC902.
Remember termination at the bus termination.
Max lenght of cable: 1200 m with specific cable and limited data rate. Follow RS485 standard.
Insulation from power supply input, metallic part and interface output : 500 V DC: *For input/output connections
Anolog Input – Current or Voltage Current
Input range: 0/4 – 20 mA
Max input range: 0 – 24 mA
Input resistance: 120 W + diode voltage 0.7 V DC
Measurement error: <±1.5% of the full scale
Reverse polarity protection: yes
Overcurrent protection: yes
Voltage
Input range: 0/2 – 10 V DC
Max input range: 0 – 12 V DC
Measurement error: <±1.5% of the full scale
Reverse polarity protection: yes
Analog Output
Output range: 0/4 – 20mA
Load: <800 W
Output error: <±1.5% of the full scale
Recommended external resistor for Hot application:
Rext=800 W-load 1W power rate
Digital Input – Digital ON/OFF input by means of voltfree contact (Signal/Telecom relays with gold-plated contacts recommended) – Voltage input used
Rth rise(OFF): >10 kW
Rth fall(ON): < 45 W
Digital Output – 3 pcs. NPN transistor output
External supply: 7 – 24 V DC (same supply as for ICAD can be used, but please note that the galvanically isolated system will then be spoiled).
On resistance: 55 W + diode voltage 0.7 V DC
Max 70 W at 50 mA
Max Output current: 50 mA
Reverse polarity protection: Yes
Overcurrent protection: No
Temperature range (ambient)
-30 °C/+50 °C (-22 °F/122 °F)
Enclosure
IP67 (~NEMA 6)
Electrical connection
Connection to ICAD is done via M12 connectors. ICAD has two M12 male and one M12 female connectors build-in:
Power supply: 4 poled M12 male connector
Control signals: 8 poled M12 male connector
Data communication: 4 poled M12 female connector
Power Supply cable with 4 poled M12 female connector
4 x 0.34 mm2 (4 x ~22 AWG) (fig. 6)
I: Black (+) 19 – 24 V DC fail safe supply (optional)
II: White (+) 24 V DC
III: Brown (–) 24 V DC
IIII: Blue (+) UPS signal of health
Control cable with 8 poled M12 female connector
7 x 0.25 mm2 (7 x ~24 AWG) (fig. 7)
A: Black (–) Digital output Common Alarm
B: Brown (–) Digital output ICM fully open
C: Red (–) Digital output ICM fully closed
D: Orange (–) GND – Ground
E: Yellow (+) Analog input 0/4 – 20 mA)
F: Green (+) Analog input 0/2 – 10 V / DI1 – Digital ON/OFF input.
G: Blue (+) Analog output 0/4 – 20 mA)
Data communication cable with 4 poled M12 male connector:

RS 485 / Ethernet RS 485 /  Ethernet
1: White/Blue (-) / TX+ Data – (B) / Transmit Pair(+)
2: White/Orange GND / RX+ Ground / Receiving Pair(+)
 3: Blue (+) / TX- Data + (A) / Transmit Pair(-)
 4: Orange GND / RX- Ground / Receiving Pair(-)

Electrical installation
General procedure for ICAD 600B/ICAD 600B-TS/1200B installed on all ICM, ICMTS & CVE valves.
All necessary electrical connections to be made.
Fig. 6
• Analog operation – 7 wired cable (A-G)
Modulation control. Valve to be controlled from Danfoss electronics, type EKC/EKE (fig. 7), or third party electronics (like e.g. PLC).
Connect analog input signals. Currrent (mA) or Voltage (V). See Parameter list for configuration of analog input signals
Yellow (+) and Orange (GND) are used for current (mA) input
or
Green (+) and Orange (GND) are used for Voltage (V) input
Blue (+) and Orange (GND) are used for current (mA) output (optional, not mandatory)
Fig. 6
• Digital operation – 7 wired cable (A-G)
ON/OFF ICM solenoid valve operation. ICM valve to be controlled by means of a digital voltfree contact.
– Connect digital input signals (fig. 8). See Parameter list for configuration of digital input signals
– Green (+) and Orange (GND) are connected to a voltfree contact
Digital output signals are optional, not mandatory.
– Black (–) and Orange (GND) are connected to auxiliary relay for Common Alarm
– Brown (–) and Orange (GND) are connected to an auxiliary relay indicating ICM fully open
– Red (–) and Orange (GND) are connected to an auxiliary relay indicating ICM fully closed
Supply voltage – 4 wired cable(I, II, III, IIII)
ICAD must be connected to a normal 24 V DC supply. As an option, a fail safe supply is possible by means of a battery or UPS (Uninterruptible Power Supply). When voltage is applied as described below, ICAD is ready to be configurated.
See Parameter list.
ICAD configuration can be done independently whether the ICAD is installed on the valve or not.
See Mechanical installation.
Connect the White (+) and Brown (–) to 24 V DC supply voltage (fig. 6)
Fail safe supply as an option (not mandatory).
Connect the Black (+) and Brown (–) to a fail safe supply.
Mechanical installation
General procedure for ICAD 600B/ICAD 600B-TS/1200B installed on all valves (fig. 3).

  • Check that the two socket screws are fully unscrewed counter clockwise with a 3 mm Hexagon key
  • If valve is fitted with PTFE ring and O-ring, remove both and replace it with O-ring included in ICAD (as instructed in fig. 3)
  • Mount ICAD by slowly lowering it on top of the valve.
  • The magnet coupling will drag the valve and ICAD together and in position
  • Push ICAD in place
  • Fasten valve and ICAD with the two socket set screws using a 3 mm Hexagon key

Danfoss ICAD 600B Motor Actuator - icon 1 Special moisture seal is damaged if screws are removed (fig. 3).

Power on & start operation

ICAD has a light guide viewable from three sides, which indicates the status. Immediately after power on the light guide and display lights up.Danfoss ICAD 600B Motor Actuator - viewableDanfoss ICAD 600B Motor Actuator - viewable1The main screen layout and navigation is as described below. ICAD will start up in alarm mode as the ICM configuration needs to be defined to start operation. Follow the steps on next page to set this up correctly.

STATUS BAR

Danfoss ICAD 600B Motor Actuator - viewable2

Set valve (A1 alarm)

Danfoss ICAD 600B Motor Actuator - viewable3Press enter Danfoss ICAD 600B Motor Actuator - icon 24
*Pressing and holding Danfoss ICAD 600B Motor Actuator - icon 24 will go directly to the passcode screenDanfoss ICAD 600B Motor Actuator - viewable4Press down Danfoss ICAD 600B Motor Actuator - icon 26 until Service is selected, then press enter Danfoss ICAD 600B Motor Actuator - viewable5Enter the 8 digit service passcode* using Danfoss ICAD 600B Motor Actuator - icon 25 press enter Danfoss ICAD 600B Motor Actuator - icon 24 to enter next number
*factory is 12131400Danfoss ICAD 600B Motor Actuator - viewable6Navigate to Advanced control in the service menu using Danfoss ICAD 600B Motor Actuator - icon 26 , then press enter Danfoss ICAD 600B Motor Actuator - icon 24Danfoss ICAD 600B Motor Actuator - viewable7

Navigate to Valve configuration using Danfoss ICAD 600B Motor Actuator - icon 26 , then press enter Danfoss ICAD 600B Motor Actuator - icon 24Danfoss ICAD 600B Motor Actuator - viewable8

Select the ICM size or CVE. Press enter Danfoss ICAD 600B Motor Actuator - icon 24 to set, and you will be navigated back to the previous screen. Continue to next step or press Danfoss ICAD 600B Motor Actuator - icon 23 to get back to main screenDanfoss ICAD 600B Motor Actuator - viewable9Change analog input signal (optional)
ICAD will function based on factory settings as soon as the valve configuration has been set. The default settings are Modulation using an analog input of 4–20 mA.Danfoss ICAD 600B Motor Actuator - viewable10Navigate back from the advanced control menu using Danfoss ICAD 600B Motor Actuator - icon 23
If starting from main screen press enter Danfoss ICAD 600B Motor Actuator - icon 24 and navigate to the service menu like in previous step.Danfoss ICAD 600B Motor Actuator - viewable11Now navigate to Control in the service menu using Danfoss ICAD 600B Motor Actuator - icon 29 , then press enter Danfoss ICAD 600B Motor Actuator - icon 24Danfoss ICAD 600B Motor Actuator - viewable12Next navigate to Input signal in the service menu using Danfoss ICAD 600B Motor Actuator - icon 26 , then press enter Danfoss ICAD 600B Motor Actuator - icon 24Danfoss ICAD 600B Motor Actuator - viewable13Select the desired input signal. Press enter Danfoss ICAD 600B Motor Actuator - icon 24 to set, and you will be navigated back to the previous screen.
Press Danfoss ICAD 600B Motor Actuator - icon 23 to get back to main screen
Further languages and documentationDanfoss ICAD 600B Motor Actuator - QRwww.icadb.danfoss.com
Danfoss A/S
Climate Solutions
danfoss.com 
+45 7488 2222
Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product.
All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.

Danfoss logoAN461947453648en-000101