Danfoss HLH061 Climate Solutions Design Center Instruction Manual
Instructions
Optyma™ G & D HBP
HLH061 OP-HRSM0500N C0217N / C0218Q / C0219R
DSH105 OP-HRSM0750N C0213Q / C0214R
DSH140 OP-HRSM1000N C0215Q / C0216R
Designation system
1 | Application H = HBP/Universal |
2 | Design R = Air cooled condenser, Twin fan, Scroll compressor |
3 | Refrigerant S = R410A/R454B/R452B |
4 | Condenser M = Microchannel condenser size 100°F Max Ambient |
5 | Unit SIze (Nominal HP)HP rating in hundredths of HP, i.e.: 0033=1/3 HP, 1000 = 10HP |
6 | Version NCXXXX = Customer specific unit with unique identification Number |
7 | Voltage code N = Compressor 230V/1ph/60Hz, Fan(s) 230V/1ph/60HzQ = Compressor 230V/3ph/60Hz, Fan(s) 230V/1ph/60HzR = Compressor 460V/3ph/60Hz, Fan(s) 460V/3ph/60Hz |
Warnings
The condensing unit must only be used for its designed purpose(s) and within its scope of application. |
Under all circumstances, the ASHRAE15 or UL60335 (or other applicable local safety regulation) requirements must be fulfilled. |
The condensing unit is delivered under nitrogen gas pressure (1 bar) and hence it cannot be connected as it is; refer to the «installation» section for further details. It does not contain refrigerant on delivery. |
The condensing unit must be handled with caution in the vertical position (maximum offset from the vertical: 15°) |
Installation and servicing of the condensing units by qualified personnel only. Follow these instructions and sound refrigeration engineering prac- tice relating to installation, commissioning, maintenance and service. |
This product is designed to be integrated into an Outdoor End-Product as an Air cooled chiller. Any different Application shall be according withUL Standard or Compliance with National Regulations. The installation of the condensing unit in a refrigeration system is the responsibility of the system designer |
These instructions pertain to Optyma G&D HBP HLH061, DSH105 & DSH140 condensing units (R410A/R452B/R454B) used for refrigeration systems. They provide necessary information regarding safety and proper usage of this product.
Note: These HRSM0500N models are only qualied to use R410A and R454B refrigerant.
The condensing unit includes following:
- Scroll compressor
- Microchannel heat exchanger
- Fix low Pressure cartridge
- Fix high Pressures cartridge
- EC Fan Motor
- Stop Valves Suction/ Liquid
- Heater for Compressor
- Receiver Vessel
- Accumulator Vessel
- Check Valve in Discharger Pipe
Handling and storage
- It is recommended not to open the packaging before the unit is at the nal place for installation.
- Handle the unit with care. The packaging allows for the use of a forklift or pallet jack.
Use appropriate and safe lifting equipment. - Store and transport the unit in an upright position.
- Don’t expose the packaging to rain or corrosive atmosphere.
- Store the unit between -31°F to 122°F (-35°C to 50°C).
- After unpacking, check that the unit is complete and undamaged.
Installation precautions
Do not braze as long the condensing unit is under pressure.
A brazed, welded, or mechanical connection shall be made before opening the valves to permit refrigerant to two between the refrigerating system parts.
Never place the unit in a ammable atmosphere.
Place the unit in such a way that it is not blocking or hindering walking areas, doors, windows or similar.
- The installation instructions shall be installed in accordance with the Safety Standard for Refrigeration Systems, ANSI/ ASHRAE 15 or Compliance with National Regulations.
- The Installation shall include protection from physical damage in operation and service and be in compliance with national and local codes and standards, such as ANSI/ASHRAE 15, IAPMO Uniform Mechanical Code, ICC International Mechanical Code, or CSA B52. All eld joints shall be accessible for inspection prior to being covered or enclosed.
- Ensure adequate space around the unit for air circulation and to open doors. Refer to picture 1 for minimal values of distance to walls, for End-Products.
- Avoid installing the unit in locations which are daily exposed to direct sunshine for longer periods.
- Avoid installing the unit in aggressive and dusty environments.
- Ensure a foundation with horizontal surface (less than 3° slope), strong and stable enough to carry the entire unit weight and to eliminate vibrations and interference.
- The unit ambient temperature may not exceed 122°F (50°C) during o cycle.
- Ensure that the power supply corresponds to the unit characteristics (see nameplate).
- When installing units for HFO refrigerants, use equipment specically reserved for HFO refrigerants which was never used for CFC or HCFC refrigerants.
- Use clean and dehydrated refrigeration grade copper tubes and silver alloy brazing material.
- Use clean and dehydrated system components.
- The suction piping connected to the compressor must be exible in 3 dimensions to dampen vibrations.
Furthermore, piping has to be done in such a way that oil return for the compressor is ensured and the risk of liquid slug over in compressor is eliminated.
Q: Air in R: Air out
Unit | W | X | Y | Z | |
Housing | In | 10 | 30 | 23 | 23 |
mm | 250 | 760 | 581 | 581 |
- This product is to be installed in accordance with the requirements in ANSI/ASHRAE 15 or Compliance with National Regulations.
The condensing unit itself is not a “unit” in the scope this directive. - The unit must be securely installed on a stable and rigid support and xed from the beginning.
- It is recommended to install the unit on rubber grommets or vibration dampers (Not supplied).
- Slowly release the nitrogen holding charge through the Schrader port.
- Connect the unit to the system as soon as possible to avoid oil contamination from ambient moisture.
- Avoid material entering the system while cutting tubes. Never drill holes where burrs cannot be removed.
- Braze with great care using state-of-the-art technique and vent piping with nitrogen gas ow.
- Connect the required safety and control devices. When the Schrader port is used for this, remove the internal valve.
- It is recommended to insulate the suction pipe up to the compressor inlet with 0.75 in (19 mm) thick insulation.
- Copper piping material should comply with ASHRAE 15. And all pipe joints should comply with SAE J513f.
- Connecting pipes shall be made before opening the valves to permit refrigerant to tow between the refrigerating system parts.
Leak detection
Never pressurize the circuit with oxygen or dry air. This could cause re or explosion.
- Do not use dye for leak detection.
- Perform a leak detection test on the complete system.
- The maximum test pressure is 464 psi (32 bar).
- When a leak is discovered, repair the leak, and repeat the leak detection.
Vacuum dehydration
Never use the compressor to evacuate the system.
- Connect a vacuum pump to both the LP & HP sides.
- Pull down the system under a vacuum of 500 μm Hg (0.67 mbar) absolute.
- Do not use a megohmmeter nor apply power to the compressor while it is under vacuum as this may cause internal damage.
Electrical connections
- Switch or and isolate the main power supply.
- Ensure that power supply cannot be switched on during installation.
- All electrical components must be selected as per local standards and unit requirements.
- Refer to wiring diagram for electrical connections details.
- Ensure that the power supply corresponds to the unit characteristics and that the power supply is stable (nominal voltage ± 10% and nominal frequency ±2,5 Hz).
- Dimension the power supply cables according to unit data for voltage and current.
- Protect the power supply and ensure correct earthing.
- Make the power supply according to local standards and legal requirements.
- The supply cable must be sized for the electrical characteristics mentioned on nameplate.
- The power supply must be connected with electrical connectors or cable glands, with a degree of protection equal to or greater than IP54, in the electrical box in such a way that no external force is exerted on the terminals.
- The unit is equipped with high- and lowpressure switches, which directly cut the power supply to the compressor in case of activation.
- For units with a 3-phase scroll compressor, correct phase sequence for compressor. rotation direction shall be observed.
- Determine the phase sequence by using a phase meter in order to establish the phase orders of line phases L1, L2 and L3.
- Connect line phases L1, L2 and L3 to main switch terminals T1, T2 and T3 respectively.
Filling the system
Assure that Condensing Unit (partial unit) shall only be connected to an appliance suitable for the same refrigerant.
NOTE: A2L Refrigerants are filled in cylinders with left-hand thread. To connect to a standard fexible hose, you need to use an inter-connector on cylinders.
- Wear protective stuff like goggles and protective gloves.
- Never start the compressor under vacuum.
Keep the compressor switched off. - Vacuum system shall be approved for A2L.
- Before charging the refrigerant, verify that the oil level is between ¼ and ¾ on the compressor oil sight glass. If additional oil is required, please refer to the compressors label for type of oil.
- Use only the refrigerant for which the unit is designed for.
- Only ll the refrigerant in liquid phase into the condenser or liquid receiver. Ensure a slow charging of the system 58 to 72 psi (4 – 5 bar).
- Do not put liquid refrigerant through suction line.
- It is not allowed to mix additives with the oil and/or refrigerant.
- The remaining charge is done until the installation has reached a level of stable nominal condition during operation.
- Never leave the flling cylinder connected to the circuit.
- Stop Valve as Schrader port for service operation like Gas Charging, pressure measurement.
- In the case of 1-Valve cylinder (without dip tube). To place carefully and safely cylinder upside down. (see the picture 2).
- In the case of 2-Valve cylinder (with dip tube). To charge from liquid (red) Valve.
Picture 2: 1 and 2-Valve cylinder
Verification before commissioning
Use safety devices such as safety pressure switch and mechanical relief valve in compliance with both generally and locally applicable regulations and safety standards.
Ensure that they are operational and properly set.
Check that the settings of high-pressure switches and relief valves don’t exceed the maximum service pressure of any system component.
- Verify that all electrical connections are properly fastened and in compliance with local regulations.
- When a crankcase heater is required, it must be energized at least 12 hours before initial start- up and start-up after prolonged shut-down period.
Start-up
- Never start the unit when no refrigerant is charged.
- All service valves must be in the open position.
- Check compliance between unit and power supply.
- Check that the crankcase heater is working.
- Check that the fan can rotate freely.
- Check that the protection sheet has been removed from the backside of condenser.
- Balance the HP/LP pressure.
- Energize the unit. It must start promptly.
If the compressor does not start, check wiring conformity, voltage on terminals and sequence phase. - Eventual reverse rotation of a 3-phase compressor can be detected by following phenomena; unit doesn’t start, the compressor doesn’t build up pressure, it has abnormally high sound level and abnormally low power consumption. In such case, shut down the unit immediately and connect the phases to their proper terminals.
- If the rotation direction is correct the low pressure indication on the low-pressure gauge shall show a declining pressure and the high-pressure indication on the high pressure gauge shall show an increasing pressure.
Check with running unit
- Check the fan rotation direction. Air must low from the condenser towards the fan.
- Check current draw and voltage.
- Check suction superheat to reduce risk of slugging.
- The optimum compressor suction superheat is around 41°F (6K). The maximum allowed superheat is 86°F (30K).
- When a sight glass is provided observe the oil level at start and during operation to conrm that the oil level remains visible.
- Respect the operating limits.
- Check all tubes for abnormal vibration.
Movements in excess of 0.06 in (1.5 mm) require corrective measures such as tube brackets. - When needed, additional refrigerant in liquid phase may be added in the lowpressure side as far away as possible from the compressor. The compressor must be operating during this process.
- Do not overcharge the system.
- Never release refrigerant to atmosphere.
- Before leaving the installation site, carry out a general installation inspection regarding cleanliness, noise, and leak detection.
- Record type and amount of refrigerant charge as well as operating conditions as a reference for future inspections.
- Compressor failure to build up pressure: Check all bypass valves in the system to ensure that none of these has been opened. Also check that all solenoid valves are in their proper position.
- Abnormal running noise: Ensure the absence of any liquid flood-back to the compressor by means of measuring the return gas superheat and compressor sump temperature. The sump should be at least 41°F (6K) above the saturated suction temperature under steady-state operating conditions.
- The high-pressure switch trips out: Check condenser operations (condenser cleanliness, fan operation, water flow and water pressure valve, water filter, etc.). If all these are OK, the problem may be due to either refrigerant overcharging or the presence of a non-condensable (e.g., air, moisture) in the circuit.
- The low-pressure switch trips out: Check evaporator operations (coil cleanliness, fan operations, water flow, water filter, etc.), liquid refrigerant flow and pressure drops (solenoid valve, filter dryer, expansion valve, etc.), refrigerant charge.
- Low refrigerant charge: The correct refrigerant charge is given by the liquid sight glass indication, the condenser delta T in relation to the refrigerant pressure tables (pressure temperature), the superheat and the sub cooling, etc. (if additional charge is deemed necessary, refer to section 8).
Maintenance
Always switch off the unit at main switch before remove fan panel.
Internal pressure and surface temperature are dangerous and may cause permanent injury. Maintenance operators and installers require appropriate skills and tools. Tubing temperature may exceed 212°F (100°C) and can cause severe burns.
Ensure that periodic service inspections to ensure system reliability and as required by local regulations are performed.
Risk Of Fire Or Explosion. flammable Refrigerant Used. To Be Repaired Only By Trained Service Personnel. Do Not Puncture Refrigerant Tubing.
To prevent system related problems, following Periodic recommended:
- Verify that safety devices are operational and properly set.
- Ensure that the system is leak tight.
- Check the compressor current draw.
- Confirm that the system is operating in a way consistent with previous maintenance records and ambient conditions.
- Check that all electrical connections are still adequately fastened.
- Keep the unit clean and verify the absence of rust and oxidation on the unit components, tubes and electrical connections.
The condenser must be checked at least once a year for clogging and be cleaned if deemed necessary. Access to the internal side of the condenser takes place through the fan panel. Microchannel coils tend to accumulate dirt on the surface rather than inside, which makes them easier to clean than fin-& tube coils.
- Switch off the unit at main switch before remove any panel from the condensing unit.
- Remove surface dirt, leaves, fibers, etc., with a vacuum cleaner, equipped with a brush or other soft attachment. Alternatively, blow compressed air through the coil from the inside out, and brush with a soft bristle. Do not use a wire brush. Do not impact or scrape the coil with the vacuum tube or air nozzle.
If the refrigerant system has been opened, the system has to be flushed with dry air or nitrogen to remove moisture and a new filter drier has to be installed. If evacuation of refrigerant has to be done, it shall be done in such a way that no refrigerant can escape to the environment.
Warranty
Always transmit the model number and serial number with any claim filed regarding this product.
The product warranty may be void in following cases:
- Absence of nameplate.
- External medications; in particular, drilling, welding, broken feet and shock marks.
- Compressor opened or returned unsealed.
- Rust, water or leak detection dye inside the compressor.
- Use of a refrigerant or lubricant not approved by Danfoss.
- Any deviation from recommended instructions pertaining to installation, application or maintenance.
- Use in mobile applications.
- Use in explosive atmospheric environment.
- No model number or serial number transmitted with the warranty claim.
Disposal
Danfoss recommends that condensing units and oil should be recycled by a suitable company at its site.
OP-HRSM0500NC0217N / OP-HRSM0500NC0218Q / OP-HRSM0500NC0219R
H | L | D | a1 | a2 | b1 | |
in | 28.1 | 49.4 | 31.5 | 48.4 | 47.2 | 26.1 |
mm | 715 | 1254 | 800 | 1230 | 1200 | 664 |
OP-HRSM0750NC211Q / OP-HRSM0750NC211R
H | L | D | a1 | a2 | b1 | |
in | 38.5 | 61.2 | 31.5 | 60.2 | 58.6 | 27.4 |
mm | 977 | 1554 | 800 | 1530 | 1488 | 696 |
OP-HRSM1000NC211Q / OP-HRSM1000NC211R
H | L | D | a1 | a2 | b1 | |
in | 52.5 | 65.2 | 35.8 | 64.2 | 62.8 | 23.1 |
mm | 1333 | 1655 | 910 | 1631 | 1595 | 588 |
Code: OP-HRSM0500NC0217N
119-9673 230V 1PH 60Hz
A1- Controller*
B1- Pressure switch 061F7526
B2- Pressure switch 061F9575
B3- Sensor DST P110 07564047
B4- Sensor DST P110 07564025
C1- Start capacitor
C2- Run capacitor
K1- Compressor contactor*
K2- Potential start relay
M1- Scroll compressor
M2-Fan 1
M3- Fan 2
PE- Protective earth
Q1- Circuit breaker*
R1- Crankcase heater
TB1-Terminal block 3 pole
TB2-Terminal block 6 pole
*Provided by customer — Field wiring
Notes:
- White fan wires must be insulated separately inside the electrical box
- For fan speed control remove red fan wires and insulate it separately inside the electrical box
- In the field re-connect crankcase heater in series with compressor contactor N.C. auxiliary contact
Code: OP-HRSM0500NC0218Q / OP-HRSM0750NC0213Q / OP-HRSM1000NC0215Q
119-9674 230V 3PH 60Hz
A1- Controller*
B1- Pressure switch 061F7526
B2- Pressure switch 061F9575
B3- Sensor DST P110 07564047
B4- Sensor DST P110 07564025
K1- Compressor contactor*
M1- Scroll compressor
M2-Fan 1
M3- Fan 2
PE– Protective earth
Q1- Circuit breaker*
R1- Crankcase heater
TB1-Terminal block 3 pole
TB2-Terminal block 6 pole
*Provided by customer Field wiring
Notes:
- White fan wires must be insulated separately inside the electrical box
- For fan speed control remove red fan wires and insulate it separately inside the electrical box
- In the field re-connect crankcase heater in series with compressor contactor N.C. auxiliary contact
Code: OP-HRSM0500NC0219R / OP-HRSM0750NC0214R / OP-HRSM1000NC0216R
119-9675 460V 3PH 60Hz
A1- Controller*
B1- Pressure switch 061F7526
B2- Pressure switch 061F9575
B3- Sensor DST P110 07564047
B4- Sensor DST P110 075G4025
K1- Compressor contactor*
M1- Scroll compressor
M2-Fan 1
M3- Fan 2
PE- Protective earth
Q1- Circuit breaker
R1- Crankcase heater
TB1-Terminal block 3 pole
TB2-Terminal block 6 pole
*Provided by customer — Field wiring
Notes:
- White fan wires must be insulated separately inside the electrical box
- For fan speed control remove red fan wires and insulate it separately inside the electrical box
- In the field re-connect crankcase heater in series with compressor contactor N.C. auxiliary contact
Danfoss A/S
Climate Solutions danfoss.us +1 888 326 3677 baltimore@danfoss.com
Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in praduct manual, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such afterations can be made without changes to form, fit or function of the product All trademarks in this material are property of Danfoss A/S or Danfoss groop companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.
8 AN344017165464en-000401
Danfoss | DCS (CC) | 2024.04
Documents / Resources
![]() |
Danfoss HLH061 Climate Solutions Design Center [pdf] Instruction Manual HLH061, OP-HRSM0500N C0217N - C0218Q - C0219R DSH105, OP-HRSM0750N C0213Q - C0214R DSH140, OP-HRSM1000N C0215Q - C0216R, HLH061 Climate Solutions Design Center, HLH061, Climate Solutions Design Center, Solutions Design Center, Design Center, Center |