Danfoss ERC 211 Digital Controller For Refrigeration And Defrost Installation Guide

ERC 211 Digital Controller For Refrigeration And Defrost

Product Information

Specifications

  • Model: ERC 211 Digital Controller
  • Relay: 1
  • Temperature Sensing Control: Yes
  • Applications: Refrigeration and Heating
  • Dimensions: 83mm x 36mm x 61.2mm
  • Quick Programming Tool: EKA 183B

Product Usage Instructions

1. Installation

Follow the assembly and rear mount instructions provided in the
manual.

2. Wiring

Refer to the wiring diagram (Danfoss 80G8139.02) for proper
electrical input. Connectors should be tightened with a maximum
torque of 0.4 Nm.

3. User Interface

Use the buttons on the controller for different functions:

  • – Press and hold down on startup to RESET FACTORY SETTINGS (FAC
    is displayed)
  • – Press for one second: BACK, PULL-DOWN
  • – Press for one second: TEMPERATURE SETPOINT/OK, MENU
  • – Press for one second: UP, DOWN
  • – Press and hold down: PULL-DOWN, MENU, ON/OFF, DEFROSTING

4. Quick-Start Configuration

Within 30 seconds of startup, follow the instructions provided
in the manual for quick configuration.

FAQ

Q: How do I reset the factory settings?

A: Press and hold down on startup to reset to factory settings
(FAC is displayed).

Q: What is the maximum torque for tightening connectors?

A: The maximum torque for connectors is 0.4 Nm.

“`

520H11056

520H11056

Installation guide
ERC 211 Digital controller for refrigeration and defrost, 1 relay.
The ERC 211 is a smart, multipurpose integrated refrigeration controller with temperature and defrost management, available with 1 relay. This controller is for Operating temperature sensing control, suitable for refrigeration and heating applications. Integrated control has been designed to fulfil today’s requirements for commercial refrigeration applications.

Danfoss 80G8101.01

Dimensions (mm)
83
Assembly

36

61.2 66
Rear mount (clip fixing)

28

71 29
Drilling template

Danfoss 80G8102.01

Assembly

Removal

Danfoss 80G8139.02

Wiring diagram
Sair DO1

Quick programming tool: EKA 183B

Sc DO1

12

3L 4N 5 6 7

~~

~~

Electrical input

(on the basis of product code)

GND

GND

8 9 10 11 12 13 14

Sair

Sc/DI1

Connectors: Max. Torque = 0.4 Nm

© Copyright Danfoss | Published by ADAP-KOOL | 2018.10

Installation guide | ERC 211

DKRCE.PI.RL0.P4.02 | 1

Installation guide – ERC 211

1 – Technical features
· Easy to use: the four buttons, the easy-to-read menu structure and the preinstalled application solutions guarantee optimal usability.
· Simple installation: the 16 A relay means heavy loads can be connected directly without having to use an intermediate relay: compressors up to 2 HP on the basis of the power factor and efficiency of the motor (over 0.65 at 230 V and over 0.85 at 115 V). A vast range of compatible sensor types and screw terminals guarantee highly flexible installation.
· Unit protection: special software functions, protecting the compressor from voltage fluctuations or high condensation temperature, to guarantee optimal unit performance.
· Energy efficiency: defrosting on request, day/night mode and intelligent evaporator fan management guarantee maximum energy efficiency.

2 – User interface
Button function

Press and hold down on startup RESET FACTORY SETTINGS (“FAC” is displayed)

Press for one second: BACK Press and hold down: PULL-DOWN

Press for one second: TEMPERATURE SETPOINT/OK Press and hold down: MENU

Display icons

Night mode (energy saving)

Fan on

Compressor on Blinks in pull-down mode

Alarm activated

Press for one second: UP Press and hold down: ON/OFF Press for one second: DOWN Press and hold down: DEFROSTING
Defrosting
Units (°C or °F)

3 – Quick-start configuration
· STEP 1: Startup · STEP 2: Select quick-start configuration menu
Within 30 seconds of startup, press “<” BACK for 3 seconds. The main switch “r12” is automatically set to OFF. · STEP 3: Select the preinstalled application “o61” The display automatically shows the application selection parameter “o61”. Press SET to select the preinstalled application. The display shows the default value (for example “AP0”, blinking). Select the type of application by pressing UP/DOWN and then SET to confirm. The regulator presets the parameter values on the basis of the application selected and hides any irrelevant parameters. Tip: you can easily switch from AP0 to AP6 and therefore select the simplified parameters list by pressing the UP button (circular list).

App App 0 App 1 App 2 App 3 App 4 App 5

Description None (no preset application) Medium temperature (4 ­ 20 °C), without defrost Medium temperature (2 ­ 6 °C), with timed natural defrost Medium temperature (2 ­ 6 °C), with natural defrost stop on air temperature Heating Thermostat (20 ­ 60 °C) None (no preset application) with simplified parameter list

· STEP 4: Select the sensor type “o06” The display automatically shows the sensor selection parameter “o06”. Press SET to select the type of sensor. The display shows the default value (for example “n10”, blinking). Select the type of sensor by pressing UP/DOWN (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) then SET to confirm. NOTE: all the sensors must by the same type.

© Copyright Danfoss | Published by ADAP-KOOL | 2018.10

Installation guide | ERC 211

DKRCE.PI.RL0.P4.02 | 2

Danfoss 80G140.01

Installation guide – ERC 211

4 – Menu structure
SET: press for 3 seconds for state, settings and service 1) Parameters group
Password (if enabled)

Input states Configuration

2) Parameter names SET
Main switch

Application

To scroll the parameter names

Sensor type

3) Value
Application 1-2-3-4-5
SET Application 0
Application 5-4-3-2-1

To scroll the parameter groups
5 – Quick configuration with “cFg” menu
· Press SET for three seconds to open the parameter groups. · Select the “cFg” menu and press SET to open. The first menu “r12” (main switch) is displayed. · Set the main switch to OFF (r12=0) to change the preinstalled application. · Press UP/DOWN to scroll through the parameters list. · Configure the parameter “o61” to select a preinstalled application:
– Press SET to open the parameter “o61”. – Press UP/DOWN to select an application (AP0= no application). – Press SET to confirm; “o61” is displayed. · Continue to set the following parameters (sensor type “o06”) in the “cFg” menu.

© Copyright Danfoss | Published by ADAP-KOOL | 2018.10

Installation guide | ERC 211

DKRCE.PI.RL0.P4.02 | 3

Installation guide – ERC 211

Danfoss 80G115.01

6 – Basic functions
Adjusting the setpoint temperature (short press) SET: adjust the setpoint temperature.
UP/DOWN: change the temperature setpoint (in setting mode the setpoint flashes).

SET: saves the temperature setpoint.
Initiate a manual defrost DEFROST: press for 3 seconds to initiate a defsost.
DEFROST: press for 3 seconds to stop manual defrost. The DEFROST icon is shown during defrost.
Initiate a pull down PULL DOWN: press for 3 seconds to initiate pull down.

“Pud”: is shown for 3 seconds to indicate pull down. The PULL DOWN icon flashes during pull down. PULL DOWN: press for 3 seconds to stop pull down.
View an active alarm
Temperature and alarm codes alternate flashes until the alarm is resolved. The alarm bell is shown.
Unlock keyboard – After 5 minutes of inactivity, the keypad will be locked (if P76 = YES). – When the keypad is locked, if any key is selected, “LoC” appears on the display. – Press UP and DOWN buttons simultaneously for 3 seconds to unlock the keyboard. “unl” is displayed for 3 seconds.

7 – Default application settings

App Mode Description

App 0

Cooling / Heating

None (no preset application)

App 1 Cooling Medium temperature without defrost

App 2 Cooling Medium temperature with timed natural defrost

App 3 Cooling Medium temperature with natural defrost stop on air temperature

App 4 Heating Heating thermostat

App 5

Cooling/ Heating

None (no preset application) with simplified parameter list

Temp. Def. type Def. end

(4 ­ 20 °C) (2 ­ 6 °C) (2 ­ 6 °C) (20 ­ 60 °C)

None Natural Natural None

None Time Air temp. None

APP 1/2/3

DI1

Sair

APP 4

DI1

Sair

Danfoss 80G141.01

230 V AC DO1

230 V AC DO1

© Copyright Danfoss | Published by ADAP-KOOL | 2018.10

Installation guide | ERC 211

DKRCE.PI.RL0.P4.02 | 4

Installation guide – ERC 211

8 – Technical Data
FEATURES Purpose of control Construction of control Input Rated power Inputs
Types of sensors allowed
Sensors in “Kit Solution”
Precision
Type of action
Output
Display Operating Conditions Storage conditions Protection Environmental data Overvoltage category
Heat and fire resistant EMC category
Certifications

DESCRIPTION Operating temperature sensing control suitable for incorporation into commercial airconditioning and refrigeration applications Incorporated control Low voltage, regulated, galvanically isolated, 115 V AC or 230 V AC, 50/60 Hz input
Less than 0.7 W
Sensor inputs, Digital inputs, Programming key Connected to SELV limited energy <15 W
NTC 5000 Ohms at 25 °C (beta = 3,980 at 25/100 °C – EKS 211 for example) NTC 10000 Ohms at 25 °C (beta = 3,435 at 25/85 °C – EKS 221 for example) PTC 990 Ohms at 25 °C (EKS 111 for example) Pt1000 (AKS 11, AKS 12, AKS 21 for example)
NTC 10000 Ohms at 25 °C, 1.5 m cable
Measuring range: -40 ­ 105 °C (-40 ­ 221 °F)
Controller accuracy: +/-1 K below -35 °C, +/-0.5 K between -35 ­ 25 °C, +/-1 K above 25 °C
1B (relay)
Compressor relay DO1: 16 A, 16 (16) A, EN 60730-1 10 FLA / 60 LRA at 230 V, UL60730-1 16 FLA / 72 LRA at 115 V, UL60730-1
LED 3-figure display, decimal point and multifunction icons, °C + °F scale
-10 ­ 55 °C (14 ­ 131 °F), 90% Rh
-40 ­ 70 °C (-40 ­ 158 °F), 90% Rh
Front: IP65 (with seal) Rear: IP00
Pollution degree II, condensate free
II – 230 V supply version – (ENEC, UL recognized) III – 115 V supply version – (UL recognized)
Category D (UL94-V0) Temperature for ball pressure test statement “According to Annex G” (EN 60730-1)
Category I
UL acknowledgement (USA and Canada) (UL 60730-1) ENEC (EN 60730-1) CQC EC (LVD and EMC Directives) EAC (GHOST) NSF ROHS2.0 HACCP temperature monitoring in compliance with EN134785 Class I if used with sensor AKS 12

© Copyright Danfoss | Published by ADAP-KOOL | 2018.10

Installation guide | ERC 211

DKRCE.PI.RL0.P4.02 | 5

Installation guide – ERC 211

9 – Parameters

Parameter name – ERC 211

Code

Configuration

cFg

Main switch -1=service, 0=OFF, 1=ON

r12

Predefined applications AP0, AP1, AP2, AP3, AP4, AP5

o61

Sensor type selection

n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC,

o06

Pt1=Pt1000

Reference/thermostat

r–

Temperature setpoint

r00

Differential

r01

Min set point limitation

r02

Max set point limitation

r03

Display offset

(correction value in display

r04

temperature)

Display unit (°C/°F)

r05

Calibration of Sair (offset for air temperature calibration)

r09

Main switch -1=service, 0=OFF, 1=ON

r12

Night set back

(offset temperature during night

r13

mode)

Thermostat reference displacement (offset temperature)

r40

Pull-down duration

r96

Pull-down limit temperature

r97

Alarm

A–

Delay for temperature alarm during normal conditions

A03

Delay for temperature alarm during pull-down / start-up / defrost

A12

High temperature alarm limit (Cabinet / room)

A13

Low temperature alarm limit

A14

DI1 delay (time delay for selected DI1 function)

A27

Condenser high alarm limit

A37

Condenser high block limit

A54

Voltage protection enable

A72

Minimum cut-in voltage

A73

Minimum cut-out voltage

A74

Maximum voltage

A75

Defrost

d–

Defrost method no=no defrost, nAt=natural

d01

Defrost stop temperature

d02

N.B.: hidden parameters are greyed out

Min
-1 AP0
n5
-100.0 0.1
-100.0 -100.0 -10.0
-C -20.0
-1
-50.0
-50.0 0
-100.0
0 0 -100.0 -100.0 0 0 0 no 0 0 0
no 0.0

Max
1 AP5
Pt1
200.0 20.0 200.0 200.0 10.0 -F 20.0
1
50.0
50.0 960 200.0
240 240 200.0 200.0 240 200 200 yES 270 270 270
nAt 50.0

Unit

App. 0 (Def.)

App. 1

App. 2

App. 3

App. 4

App. 5

1

1

1

1

1

1

AP0 AP1 AP2 AP3 AP4 AP5

n10 n10 n10 n10 n10 n10

C/F

2.0

8.0

4.0

K

2.0

2.0

2.0

C/F -35.0 4.0

2.0

C/F 50.0 20.0 6.0

K

0.0

0.0

0.0

-C

-C

-C

K

0.0

0.0

0.0

1

1

1

4.0 40.0 2.0

2.0

2.0

2.0

2.0 20.0 -35.0

6.0 60.0 50.0

0.0

0.0

0.0

-C

-C

-C

0.0

0.0

1

1

K

0.0

0.0

0.0

0.0

0.0

0.0

K

0.0

0.0

0.0

0.0

0.0

min

0

0

0

C/F 0.0

0.0

0.0

min 30

45

45

45

30

30

min 60

60

90

90

60

60

C/F 8.0

16

10

10

80

8.0

C/F -30.0 0.0

0.0

0.0

10 -30.0

min 30

30

30

30

30

30

C/F

80

80

80

80

C/F

85

85

85

85

no

no

no

no

no

no

V

0

0

0

0

0

0

V

0

0

0

0

0

0

V

270 270 270 270 270 270

no

no

nAt nAt

no

no

C/F 6.0

8

6.0

© Copyright Danfoss | Published by ADAP-KOOL | 2018.10

Installation guide | ERC 211

DKRCE.PI.RL0.P4.02 | 6

Installation guide – ERC 211

Parameter name – ERC 211

Code

Min

Max

Unit

App. 0 (Def.)

App. 1

App. 2

App. 3

App. 4

App. 5

Defrost interval

d03

0

240 hours 8

6

6

8

Max defrost time

d04

0

480 min 30

45

60

30

Defrost delay at power up (or DI signal)

d05

0 240.0 min

0

0

0

Drip delay

d06

0

60 min

0

0

0

Defrost stop sensor

configuration, non=time,

d10 non Air

non

non Air

non

Air=Sair (air temperature)

Compressor accumulated runtime to start defrost, 0=OFF

d18

0

96 hours 0

0

0

Defrost delay after pull-down 0=OFF

d30

0

960 min

0

0

0

Compressor

c–

Compressor minimum ON time

C01

0

30 min

0

0

0

0

0

0.0

Compressor minimum OFF time

C02

0

30 min

2

2

2

2

2

2.0

Compressor OFF delay at door open

C04

0

15 min

0

0

0

0

0

1

Zero crossing selection

C70

no

yES

yES yES yES yES yES yES

Others

o–

Delay of outputs at startup

o01

0

600 min

5

5

5

5

5

5

DI1 configuration

oFF=not used,

Sdc=status display output,

doo=door alarm with resumption,

doA=door alarm without resumption, SCH = main switch, nig=day/ night

o02 oFF

Sc

oFF oFF oFF oFF oFF oFF

mode, rFd=reference displacement,

EAL=external alarm,

dEF=defrost, Pud=pull-down,

Sc=condenser sensor

Serial address

o03

0

247

0

0

0

0

0

Password

o05 no 999

no

no

no

no

no

no

Sensor type selection

n5=NTC 5 K, n10=NTC 10 K,

o06

n5

Pt1

n10 n10 n10 n10 n10

Ptc=PTC, Pt1=Pt1000

Cooling/heating

rE=refrigeration (cooling)

o07

rE

Ht

rE

rE

rE

rE

Ht

rE

Ht=heating

Display resolution

0.1=steps of 0.1 °C, 0.5=steps of 0.5 °C,

o15

0.1

1.0

0.1

0.1

0.1

0.1

0.1

0.1

1.0=steps of 1.0 °C

Relay 1 counter (1 count=100 cycles of operation)

o23

0

999

0

0

0

0

0

Predefined applications

o61 AP0 AP5

AP0 AP1 AP2 AP3 AP4

Save settings as factory

WARNING: the earlier factory settings o67

no

yES

no

no

no

no

no

are overwritten

Display at defrost

Air=actual air temperature, FrE=freezed temperature,

o91

Air

-d-

-d-

-d-

-d-

-d-

-d-=”-d-” is displayed

Polarity

P–

DI1 input polarity

nc=normally closed,

P73

nc

no

no

no

no

no

no

no

no=normally open

Keyboard lock enable

P76

no

yES

no

no

no

no

no

N.B.: hidden parameters are greyed out

© Copyright Danfoss | Published by ADAP-KOOL | 2018.10

Installation guide | ERC 211

DKRCE.PI.RL0.P4.02 | 7

Installation guide – ERC 211

Parameter name – ERC 211
Readouts Controller status S0=cooling ON/Heating ON, S2=wait for compressor ON time to elapse, S3=wait for compressor OFF time to elapse-restart time, S4=drip OFF delay after defrost, S10=cooling stop, S11=cooling stopped by thermostat/ heating OFF, S14=defrosting state, S15=fan delay state after defrost, S17=door open (DI input), S20=emergency cooling, S25=manual control of outputs, S30=continous cycle / Pull-down, S32=delay of outputs at power up Air temperature (Sair) Read the present regulation reference DI1 input Status of night operation Condenser temperature (Sc) Compressor relay status Firmware version readout Alarm status Sair air temperature sensor error High temperature alarm Low temperature alarm High voltage alarm Low voltage alarm Condenser alarm Door alarm Standby alarm DI external alarm N.B.: hidden parameters are greyed out

Code u–
u00
u01 u02 u10 u13 U09 u58 u80 E29 A01 A02 A99 AA1 A61 A04 A45 A15

Min
S0
-100.0 -100.0 oFF oFF -100.0 oFF 000

Max
S32
200.0 200.0
on on 200.0 on 999

Unit

App. 0 (Def.)

App. 1

App. 2

App. 3

App. 4

App. 5

C/F

C/F

C/F

Safety standards
Check the input voltage is correct before connecting the instrument. Do not expose to water or damp: only use the regulator within the design operating limits, avoiding sudden temperature changes with high atmospheric humidity to prevent condensate forming.
Product disposal
The device (or product) must be disposed of in compliance with local waste disposal legislation.
EU design registration
002566703-0001

Contact info.: www.danfoss.com/erc

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice.This also applies to products

already on order provided that such alterations can be made without subsequential changes being necessary

eady agreed.

All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

© Copyright Danfoss | Published by ADAP-KOOL | 2018.10

Installation guide | ERC 211

DKRCE.PI.RL0.P4.02 | 8