ECL MODBUS OPC ECL Comfort Controllers Server
“
Product Information
Specifications:
- Product Name: ECL MODBUS OPC
- Version: 1.1
- Communication Protocol: OPC Data Access Specification version
2.0 - Compatible with: ECL Comfort controllers with ECA 71
module - Interface: Windows COM ports
Product Usage Instructions:
1. Installation:
Before installation, ensure you have the necessary cables as per
the equipment requirements. Refer to the MODBUS RS-485 converter
documentation for details.
2. Program Installation:
Follow the steps outlined in the user manual to install the ECL
MODBUS OPC program on your system.
Use the Configurator to set up the Server. Note that setup
changes will only take effect after restarting the Server.
4. Getting Started:
- Perform a network scan to identify available devices.
- Scan for devices and assign appropriate names and tags.
- Set up conversions if necessary.
- Integrate third-party products as required.
5. Installation and Technical Information:
Refer to the technical information section in the manual for
detailed installation guidelines and technical specifications.
6. Troubleshooting:
If you encounter any issues, refer to the troubleshooting
section of the manual for assistance.
FAQ:
Q: What is the recommended backup procedure for the OPC
database?
A: It is recommended to make a backup of the OPC database before
making any modifications to ensure data safety.
Q: How can I connect a third-party OPC Client to the ECL MODBUS
OPC Server?
A: You can connect a third-party OPC Client, such as a SCADA
system, to the ECL MODBUS OPC Server via the Danfoss MODBUS OPC
server using TCP/IP, USB, or RS-232 to RS-485 (MODBUS)
connections.
“`
DH-SMT/DK
ECL MODBUS OPC Instructions
VI.KT.A2.02 © Danfoss 01/2008
Instructions
ECL MODBUS OPC
Table of Contents
1. Introduction
3
1.1 Prior to installation…………………………………………………………………………………………………………………………………………………………………………………………….4
2. How to install the program
4
3. Navigation in the Configurator
5
4. How to get started
5
4.1 Network scan………………………………………………………………………………………………………………………………………………………………………………………………………6
4.2 Device scan …………………………………………………………………………………………………………………………………………………………………………………………………………7
4.3 Device and tag names……………………………………………………………………………………………………………………………………………………………………………………….8
4.4 Conversions ………………………………………………………………………………………………………………………………………………………………………………………………………..8
4.5 Third party products …………………………………………………………………………………………………………………………………………………………………………………………9
5. Installation and technical information
9
6. Troubleshooting
10
VI.KT.A2.02 © Danfoss 01/2008
DH-SMT/DK
Instructions
ECL MODBUS OPC
1. Introduction
This instruction covers the ECL MODBUS OPC, i.e. the ECL MODBUS Configurator and the ECL MODBUS OPC Server.
The ECL MODBUS OPC Server uses the OPC Data Access Specification version 2.0.
The ECL MODBUS OPC Configurator and Server can communicate with ECL Comfort controllers with ECA 71 module. The communication takes place by means of Windows COM ports, e.g. COM1. The Server can use multiple COM ports to support multiple networks.
The ECL MODBUS OPC Configurator and Server are in the following referred to as Configurator and Server. The Configurator is used for the setup of the Server. Setup changes will not take effect until the Server has been restarted.
The Configurator is an online tool that can scan a network for ECL Comfort devices and their parameters. Devices, groups and parameters can also be added manually. The network scan searches a network for installed ECL Comfort devices. The search is done from address 1 to address 247. The network scan can only add new devices existing devices will NOT be deleted.
The device scan retrieves the parameter list from the selected ECL Comfort controller. The parameters are placed in a hierarchical structure depending on the ECL Comfort application. The device scan can only add new folders and parameters existing folders and parameters will NOT be deleted.
This help file is written for ECL MODBUS OPC version 1.1
It is recommended to make a backup of the OPC database before modifications are carried out.
Third party OPC Client
SCADA system: Connected via Danfoss MODBUS OPC server
TCP/IP, USB or RS-232 to RS-485 (MODBUS)
ECL Comfort M-Bus connection
Heat meter
DH-SMT/DK
VI.KT.A2.02 © Danfoss 01/2008
3
Instructions
ECL MODBUS OPC
1.1 Prior to installation
Min. PC requirements · Intel Pentium or equivalent processor · Windows 2000®, Windows NT or Windows XP · 128 MB RAM · 500 MB free hard disk space
References Type ECA 71
Description
MODBUS communication module
Documentation available on http://heating.danfoss.com: Instructions, ECA 71 protocol Instructions, ECA 71 / 72 installation and user guide
Code No. (Parts list No.) 087B1126
(087R9775, English) (087R9769, English)
Cables The required cables will depend on the used equipment. Consult the MODBUS RS-485 converter documentation for further details.
Please do also consult the ECA 71 instructions for details about the network layout and connection.
MODBUS RS-485 Converters The MODBUS network uses a 2-wire RS-485 interface. This interface is typically not part of a standard PC, and it is therefore necessary to connect a MODBUS RS-485 converter.
Basically there are 4 groups of converters: · RS-232 RS-485 · USB RS-485 · TCP/IP RS-485 · Expansion module, e.g. PCI RS-485
Common requirements for all converters are that they have to be capable of running MODBUS RS-485, the desired communication setting (baud rate, parity etc.) and must offer a Windows COM (Virtual COM) port interface to the Configurator and Server.
The MODBUS standardspecifies line termination and polarization. It is an advantage if this is built into the converter. It is recommended to use isolated converters (and repeaters) to increase robustness.
For specific details, please consult the specifications · Modbus Application Protocol V1.1a. · MODBUS over Serial Line, Specification & Implementation guide V1.0 both of which can be found on http://www.modbus.org/
Achievable performance will depend on the chosen converter.
2. How to install the program
Run the Setup.exe file on the PC onto which the OPC Server and Configurator must be installed. Follow the installation wizard. The next step is to read the section on “How to get started”.
4
VI.KT.A2.02 © Danfoss 01/2008
DH-SMT/DK
Instructions
ECL MODBUS OPC
3. Navigation in the Configurator
The Configurator resembles the Windows Explorer, with a left-hand side for level/item navigation and a right-hand side with details for the selected level/item.
In the Configurator new ports, devices, groups and parameters can be added with a right-click of the mouse or by means of the menu item `Edit’ `New’.
The illustration shows the hierarchical structure (as known from the Windows Explorer) with the newly created folders `NewPort’, `NewDevice’, `NewFolder’ and `NewDataItem’.
4. How to get started
After installation it is necessary to configure the database or select an already existing (valid) database. The database configuration must be carried out with the Configurator.
An existing database can be selected by opening the database and closing the Configurator. When this is carried out, the Configurator will ask whether the new database should be used for the Server.
For the configuration of a new database, the following steps must must be carried out for each network:
1. Run the Configurator (located in the start menu, `Programs’ `District Heating’ `ECL MODBUS OPC Server’ ‘Configurator’)
2. Add/select a port by specifying the COM port and the serial settings 3. Scan the network or add devices manually 4. Scan each device or add groups and parameters/tags manually 5. Close the Configurator
DH-SMT/DK
VI.KT.A2.02 © Danfoss 01/2008
5
Instructions
ECL MODBUS OPC
The database is configured and the Server has the parameters/tags which an OPC client can use.
If the network is updated or expanded, e.g. new controllers are added or application cards changed, it is recommended to follow the steps above for an update of the database configuration.
4.1 Network scan
The network scan is used to search the network for new devices. Third party products are not supported by this function, and must be added manually.
The network scan can be activated in the port window. Before the scan, the correct communication parameters must be set. The network scan takes approximately 1 5 minute to complete.
6
VI.KT.A2.02 © Danfoss 01/2008
DH-SMT/DK
Instructions
ECL MODBUS OPC
4.2 Device scan
Device scan is used for finding the groups and parameters of a device. Whenever a device has been replaced, the application changed etc., this function should be used. Third party products are not supported by this function, and must be added manually.
The device scan can be activated in the device window after the network scan. Before a scan, a device must be selected. The device scan takes approximately 1 5 minute to complete.
The device scan can only be used for ECL type devices.
If a device is re-scanned, the old folders should be deleted.
The button `Fill Conversions’ must be used before a scan if the database does not contain the necessary scales. It adds/repairs the necessary default conversions items.
DH-SMT/DK
VI.KT.A2.02 © Danfoss 01/2008
7
Instructions
ECL MODBUS OPC
4.3 Device and tag names
Device and tag names are generated automatically. The names will therefore be the same from scan to scan if nothing is changed (version of Configurator, ECA 71, ECL Comfort, or Application).
Whenever possible, the automatically generated names should be used, as this will reduce overall system setup modifications. Description field can be changed if desired.
4.4 Conversions
All values can be converted (scaled) by the OPC Server.
To add/modify a conversion: 1. `Add/Modify’ a conversion in the Conversions folder. 2. For the parameters that require conversion, select `Use conversion’ in the parameter dialog and then select the appropriate
conversion
Default conversions `ECL Scale x’ is a conversion which is equal to 10x, e.g. `ECL Scale -1′ is equal to 10-1 (division by 10). `ECL Scale Schedule’ is used for all schedule values. As default the conversion will divide the values by 100, i.e. 8:00 is 8 and 8:30 is 8,3 (not 800 and 830). The conversion can be changed if this representation is not desired.
8
VI.KT.A2.02 © Danfoss 01/2008
DH-SMT/DK
Instructions
ECL MODBUS OPC
4.5 Third party products
Third party products, such as general inputs/outputs, which support the standard MODBUS RTU interface can manually be added with the Configurator.
New devices, groups and parameters can be added by a right-click of the mouse or the menu item `Edit’ `New’.
Note that any third party products must use the same communication settings as the rest of the network (baud rate, parity etc.).
5. Installation and technical information
The installation includes the files `PNU & GROUP numbers parameter list.txt’ and `search list.txt’. These files are used during a device scan and are not to be modified.
Cache function The `Cache’ folder contains cached device scan results. When a new application type is scanned, a cache file is generated. If an application type is known, the cached file will be used, thus eliminating a complete device scan. This will speed up the process.
The cache function can be enabled/disabled by creating/deleting the `Cache’ folder.
Scan timeout The network scan timeout parameter can, if necessary, be changed by adding a DWORD value with the name ScanTimeout to the registration database key.
HKEY_CURRENT_USERSoftwareDanfoss A/SECL Modbus OPC ConfiguratorOptions
The default value is 250 ms. (The device scan uses the device read timeout).
Default database The installation includes a default database named ECL_ModbusOPCConfigurator.mdb.
Database compatibility Databases from ECL MODBUS OPC version 1.0 are usable after the `Fill Conversions’ function has run. Databases from Demo Iconics MODBUS OPC are not compatible.
DH-SMT/DK
VI.KT.A2.02 © Danfoss 01/2008
9
Instructions
ECL MODBUS OPC
6. Troubleshooting
Fault
Cause
Solution
No database
Installation not complete
· Uninstall and reinstall the program
Alternative
· Create a new database with `File’ ‘New’
· Or open an existing database with `File’ `Open’
When the program is closed, choose `Yes’ to set the new database as the current one.
Network scan does not find any devices
False communication port and/or settings
· Check that the COM port setting is correct.
· Check that the cable/network is connected correctly
· Check that cable termination and polarization is correct
Device scan does not find all parameters
Not fully supported module
· Manually insert the missing parameters
· Update the Configurator if possible
Low server performance
Invalid devices and/or parameters.
· Remove invalid devices (that do
To high update rate requested.
not exist in the network)
Low performing converters/repeaters
· Remove invalid parameters (that
do not exist in the device)
· Change the requested update rate to a more reasonable value
· Check that converters and repeaters are correctly installed and have the needed performance
· Converters that run over other media (e.g. the internet) can introduce delays
OPC server doesn’t work or client can’t The OPC Core Components are not · Install the OPC Core file from the
connect to it
fully installed
folder “{installpath}OPC Core
(this problem normally only occurs on
Components Redistributable x.xx.
a PC with no prior installation of an
xxxRelease”
OPC system)
10
VI.KT.A2.02 © Danfoss 01/2008
DH-SMT/DK
Instructions
ECL MODBUS OPC
DH-SMT/DK
VI.KT.A2.02 © Danfoss 01/2008
11
Instructions
ECL MODBUS OPC
Disposal Instruction Equipment containing electrical components shall not be disposed together with domestic waste. It must be collected separately with other electrical and electronic waste according to local legislation.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice.This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
VI.KT.A2.02 © Danfoss 01/2008
DH-SMT/DK
Documents / Resources
![]() |
Danfoss ECL MODBUS OPC ECL Comfort Controllers Server [pdf] Instructions ECL MODBUS OPC ECL Comfort Controllers Server, ECL MODBUS OPC, ECL Comfort Controllers Server, Comfort Controllers Server, Controllers Server |
