Danfoss-LOGO

Danfoss DCR Filter Drier, Shell with Cross Gasket

Danfoss-DCR-Filter-Drier,-Shell-with-Cross-Gasket-PRODUCT

Specifications

  • Product Name: Filter drier, shell with cross gasket Type DCR, DCR/H, DCR E
  • Refrigerants Compatibility:
    • R1233zd, R134a, R407A, R407C, R407F, R407H, R410A, R422B, R422D, R448A, R449A, R449B, R450A, R452A, R513A, R515B, etc.
    • R1234yf, R1234ze, R32, R444B, R452B, R454A, R454B, R454C, R455A, R457A, R516A, etc.
    • R1234yf, R1234ze, R32, R444B, R452B, R454A, R454B, R454C, R455A, R457A, R516A, R290, R600a, etc.
  • Working Pressure: From 7 to 13 bar (PS) / 100 to 667 psig (MWP)
  • Material: Copper Steel
  • Brazing Material: Min. 5% Ag Silver-flo 55 + Easy-flow flux

Product Usage Instructions

Installation
When installing the filter drier:

  • Use a ratcheting wrench of 13mm for DCR and DCRE gasket installation.
  • Use an Allen wrench of 6mm for DCR/H gasket installation.
  • Apply a small amount of oil to the gasket before assembly.

Tightening Instructions
Follow these steps to tighten the bolts:
Finger-tighten all bolts using the specified sizes for each type (M8-1.5 x 35mm for DCR/M8-1.5 x 35mm G12.9 for DCR/H/M10-1.5 x 40mm for DCRE).

  1. Step 1: 3 Nm / 2.21 ft lb
  2. Step 2: 10 Nm / 7.37 ft-lb
  3. Step 3: 20 Nm / 14.75 ft-lb
  4. Step 4: 28 Nm / 20.65 ft-lb

Maintenance
Replace the gasket every time the filter is opened to ensure proper sealing.

Safety Precautions
Keep flames away from the body during brazing. Ensure correct gasket selection before installation.

Refrigerants

DCR Standard (A1, Group 2)

  • R1233zd, R134a, R407A, R407C, R407F, R407H, R410A, R422B, R422D, R448A, R449A, R449B, R450A, R452A, R513A, R515B, etc.
  • For other refrigerants, please contact your Danfoss representative.

Media Temperature: -40 – 70 °C / -40 – 160 °F

DCR/H (A2L, Group 1) – UL Listed, for use in the US market only R1234yf, R1234ze, R32, R444B, R452B, R454A, R454B, R454C, R455A, R457A, R516A, etc.

Also compatible with DCR Standard Refrigerants.

DCRE (A3, A2L, Group 1) – PED approved

  • R1234yf, R1234ze, R32, R444B, R452B, R454A, R454B, R454C, R455A, R457A, R516A, R290, R600a, etc.
  • Also compatible with DCR Standard Refrigerants.

Design

DCR and DCR/H       

Danfoss-Type-DCR-Filter-Drier-Shell-With-Cross-Gasket-fig-1                                                                                 

DCR E

Danfoss-Type-DCR-Filter-Drier-Shell-With-Cross-Gasket-fig-2

Position. Description
1 Plug for cover
2 Bolts for cover
3 Top cover
4 Spring
5 Top cover gasket
6 Wing Nut (DCR) / Bolt (DCRE)
7 Lock washer
8 top plate
9 Core felt gasket
10 Solid core
11 Core holder felt gasket
12 Core plate
13 Distance rods
14 Wire Mesh
15 Core holder
16 Cross gasket
17 Washer
18 Hex socket head screw
19 Cover

The inner taper of the core always faces the filter outlet. This applies to all DCR Families.

Installation

Danfoss-Type-DCR-Filter-Drier-Shell-With-Cross-Gasket-fig-3

Type

Minimum Maximum working pressure PS / MWP [bar] / [psig]
[mm] [in]
DCR DCR/H 048 170 7 46 / 667 *
DCR DCR/H 096 310 13 46 / 667 *
DCR DCR/H 144 310 13 35 / 507 1 )
46 / 667 2 )
DCR DCR/H 192 310 13 28 / 406 1 )
40 / 580 2 )
DCRE 048 170 7 50 / 725
  1. For use with a strainer or as a receiver application
  2. For the “drier” application using all permissible cores
  3. For 1* or 2*

MWP shall not be less than the pressure described in section 9.2 of ANSI/ASHRAE 15 for the refrigerant used in the system. After charging, the system shall be marked with the refrigerant and oil used.

“The DCRE can only be used for A2L when the solid core is placed. The DCRE is not allowed to be used as a receiver.”

Brazing

Danfoss-Type-DCR-Filter-Drier-Shell-With-Cross-Gasket-fig-4

Welding

Danfoss-Type-DCR-Filter-Drier-Shell-With-Cross-Gasket-fig-5

Customer best practices will still be required:

  • Use wet wrap when installing.
  • Braze the joints.
  • Let them cool.
  • Clean the brazing/welding area after installation (remove the remaining flux with a brush).
  • This is an important operation and needs to be done with great care to remove all remaining flux.
  • Paint / Anti-corrosive needs to cover all exposed steel parts, areas where the original black paint has burned away due to brazing and at least 3 cm around the copper.
  • Paint the joints twice.

How to tighten bolts

Danfoss-Type-DCR-Filter-Drier-Shell-With-Cross-Gasket-fig-6

Danfoss-Type-DCR-Filter-Drier-Shell-With-Cross-Gasket-fig-9

Gasket

Danfoss-Type-DCR-Filter-Drier-Shell-With-Cross-Gasket-fig-7

Do not install a gasket before soldering.

Note: Confirm the correct top cover gasket is selected. There are 2 gaskets:

  • DCR and DCR/H
  • DCRE

Recommendation

  • Apply a small amount of oil to the gasket before assembly.
  • Preferably POE or PVE synthetic oil, although any general-purpose oil can be used.

Note: Do not reuse the gasket.

Optional Fuse and/or Plug, recommended tightening torques:

  • Fuse: 1/4”NPT – 3/8” Flare: 20 Nm / 14.75 ft-lb applying 2 to 3 wraps of Teflon tape.
  • Plug: 1/4” NPT: 50 Nm / 36.87 ft-lb applying 2 to 3 wraps of Teflon tape.

Reference

Danfoss-Type-DCR-Filter-Drier-Shell-With-Cross-Gasket-fig-8

The torque values ​​mentioned only apply to bolts supplied by Danfoss.

Each step should be applied after the image sequence.

FAQ

Q: Can DCRE be used as a receiver?
A: No, DCRE cannot be used as a receiver. It is only suitable for A2L when the solid core is placed.

Q: What type of oil should be applied to the gasket?
A: Preferably synthetic POE or PVE oil is recommended for applying to the gasket before assembly. However, any general-purpose oil can be used.

Documents / Resources

Danfoss DCR Filter Drier, Shell with Cross Gasket [pdf] Installation Guide
023R9543, 23M71.12, 23M115.10, 23Z85, DCR Filter Drier Shell with Cross Gasket, DCR, Filter Drier Shell with Cross Gasket, Drier Shell with Cross Gasket, Shell with Cross Gasket, Cross Gasket, Gasket

References

Leave a comment