Danfoss-LOGO

Danfoss Scroll Compressor

Danfoss-Scroll-Compressor-PRODUCT

Specifications

  • Model: LLZ compressors
  • Refrigerants: r404A / r507
  • Operating Limits: Standard and Economizer Cycle
  • Electrical Connections: Three Phase

Product Usage Instructions

Installation and Servicing

  • Installation and servicing should be performed by qualified personnel following sound refrigeration engineering practices.

Operating Limits

  • The operating limits for LLZ compressors with R404A/R507 refrigerants are provided in the manual. Ensure to operate within the specified temperature and superheat ranges.

Electrical Connections

  • Refer to the wiring diagram for electrical connections. Ensure proper connection of terminals and follow the instructions for the control circuit.

Usage Guidelines

  • Do not operate the compressor under nitrogen gas pressure. Use the compressor only for its designed purpose. Follow all safety regulations and guidelines during operation.

Maintenance

  • Ensure regular maintenance of the compressor. Use rubber grommets provided for sealing. Check for leaks and maintain proper refrigerant charge limits.

Safety Precautions

  • Wear protective goggles and work gloves when handling the compressor. Avoid low-pressure operation and follow all safety standards.

PRODUCT OVERVIEW

  • A: Model number
  • B: Serial Number
  • C: Technical number
  • D: Manufacturing year
  • E: Internal protection
  • F: Supply voltage range
  • G: Locked rotor current
    • Maximum operating current
  • H: Lubricant type and nominal charge
  • I: Approved RefrigerantDanfoss-Scroll-Compressor-FIG-2
  • Installation and servicing of the compressor by qualified personnel only. Follow these instructions and sound refrigeration engineering practice relating to installation, commissioning, maintenance, and service.Danfoss-Scroll-Compressor-FIG-1

Operating limits

Danfoss-Scroll-Compressor-FIG-3

  • The compressor must only be used for its designed purpose(s) and within its scope of applica-tion (refer to «operating limits»). Consult the Application guidelines and datasheet available from cc.danfoss.com
  • Never operate a compressor without the terminal box cover in place and secured.
  • The compressor is delivered under nitrogen gas pressure (between 0.3 and 0.4 bar / 4 and 6 psi). Do not disassemble bolts, plugs, fittings, etc, unless all pressure has been relieved from the compressor.
  • Under all circumstances, the EN378 (or other appli-cable local safety regulation) requirements must be fulfilled.
  • Wear protective goggles and work gloves.
  • The compressor must be handled with caution in the vertical position (maximum offset from the vertical: 15°).

Electrical connections

Danfoss-Scroll-Compressor-FIG-4

Wiring diagram

Three-phase (Wiring diagram with pump-down cycle)Danfoss-Scroll-Compressor-FIG-5

Introduction

  • These instructions pertain to the LLZ scroll compressors used for refrigeration systems. They provide necessary information regarding safety and proper usage of this product.

Handling and storage

  • Handle the compressor with care. Use the dedicated handles in the packaging. Use the compressor lifting lug and use appropriate and safe lifting equipment.
  • Store and transport the compressor in an upright position.
  • Store the compressor between -35°C and 70°C / – 31°F and 158°F.
  • Don’t expose the compressor and the packaging to rain or corrosive atmosphere.

Safety measures before assembly

  • Never use the compressor in a flammable atmosphere.
  • Mount the compressor on a horizontal flat surface with less than a 7° slope.
  • Verify that the power supply corresponds to the compressor motor characteristics (see nameplate).
  • When installing a compressor for R404A, R507or R407A, use equipment specifically reserved for HFC refrigerants that was never used for CFC or HCFC refrigerants.
  • Use clean and dehydrated refrigeration-grade copper tubes and silver alloy brazing material.
  • Use clean and dehydrated system components.
  • The piping connected to the compressor must be flexible in 3 dimensions to dampen vibrations.
  • The compressor must always be mounted with the rubber grommets supplied with the compressor.

Assembly

  • Slowly release the nitrogen holding charge through discharge and suction ports.
  • Connect the compressor to the system as soon as possible to avoid oil contamination from ambient moisture.
  • Avoid material entering the system while cutting tubes. Never drill holes where burrs cannot be removed.
  • Do not exceed the maximum tightening torque for rotolock connections
Rotolock connections Tightening torque
1” Rotolock 80 Nm
1” 1/4 Rotolock 90 Nm
1” 3/4 Rotolock 110 Nm

Instructions

  • Connect the required safety and control devices. When the schrader port, if any, is used for this, remove the internal valve.
  • For parallel assemblies of the compressors in version C8, contact Danfoss.

Leak detection

  • Never pressurize the circuit with oxygen or dry air. This could cause fire or explosion.
  • Do not use leak detection dye.
  • Perform a leak detection test on the complete system.
  • The low side test pressure must not exceed 31 bar /450 psi.
  • When a leak is discovered, repair the leak and repeat the leak detection.

Vacuum dehydration

  • Never use the compressor to evacuate the system.
  • Connect a vacuum pump to both the LP & HP sides.
  • Pull down the system under a vacuum of 500 µm Hg (0.67 mbar) / 0.02 inch Hg absolute.
  • Do not use a megohmmeter or apply power to the compressor while it is under vacuum, as this may cause internal damage.

Electrical connections

  • Switch off and isolate the main power supply.
  • All electrical components must be selected as per local standards and compressor requirements.
  • Refer to page 1 for electrical connections details. For three-phase applications, the terminals are labeled T1, T2, and T3.
  • Danfoss scroll compressors will only compress gas while rotating counter-clockwise (when viewed from the compressor top).
  • Three-phase motors, however, will start and run in either direction, depending on the phase angles of the supplied power.
  • Care must be taken during installation to ensure that the compressor operates in the correct direction.
  • Use ø 4.8 mm / #10 – 32 screws and ¼” ring terminals for the power connection with ring connect screw terminal (C type). Fasten with 3 Nm torque.
  • Use a self-tapping screw to connect the compressor to the earth.

Filling the system

  • Keep the compressor switched off.
  • Keep the refrigerant charge below the indicated charge limits if possible. Above this limit, protect the compressor against liquid flood-back with a pump-down cycle or suction line accumulator.
  • Never leave the filling cylinder connected to the circuit.
Compressor models Refrigerant charge limit
LLZ013-015-018 4.5 kg / 10 lb
LLZ024-033 7.2 kg / 16 lb

Verification before commissioning

  • Use safety devices such as a safety pressure switch and a mechanical relief valve in compliance with both generally and locally applicable regulations and safety standards. Ensure that they are operational and properly set.
  • Check that the settings of high-pressure switches don’t exceed the maximum service pressure of any system component.
  • A low-pressure switch is recommended to avoid low-pressure operation.
  • Minimum setting for R404A / R507 1.3 bar (absolute) / 19 psia
  • Verify that all electrical connections are properly fastened and in compliance with local regulations.
  • When a crankcase heater is required, it must be energized at least 24 hours before initial start-up and after prolonged shutdown.

Start-up

  • Never start the compressor when no refrigerant is charged.
  • Do not provide any power to the compressor unless the suction and discharge service valves are open, if installed.
  • Energize the compressor. It must start promptly. If the compressor does not start, check wiring conformity and voltage on terminals.
  • Eventual reverse rotation can be detected by following phenomena: excessive noise, no pressure differential between suction and discharge, and line warming rather than immediate cooling.
  • A service technician should be present at initial start-up to verify that supply power is properly phased and that the compressor is rotating in the correct direction. For LLZ compressors, phase monitors are required for all applications.
  • If the internal overload protector trips out, it must cool down to 60°C / 140°F to reset. Depending on ambient temperature, this may take up to several hours.

Check with the running compressor

  • Check the current draw and voltage. Measurement of amps and volts during running conditions must be taken at other points in the power supply, not in the compressor electrical box.
  • Check suction superheat to reduce the risk of slugging.
  • Observe the oil level in the sight glass (if provided) for about 60 minutes to ensure proper oil return to the compressor.
  • Respect the operating limits.
  • Check all tubes for abnormal vibration. Movements in excess of 1.5 mm / 0.06 in require corrective measures such as tube brackets.
  • When needed, additional refrigerant in liquid phase may be added in the low-pressure side as far as possible from the compressor. The compressor must be operating during this process.
  • Do not overcharge the system.
  • Never release refrigerant to the atmosphere.
  • Before leaving the installation site, carry out a general installation inspection regarding cleanliness, noise, and leak detection.
  • Record type and amount of refrigerant charge, as well as operating conditions, as a reference for future inspections.

Maintenance

  • Internal pressure and surface temperature are dangerous and may cause permanent injury. Maintenance operators and installers require appropriate skills and tools.
  • Tubing temperature may exceed 100°C / 212°F and can cause severe burns.
  • Ensure that periodic service inspections to ensure system reliability and as required by local regulations, are performed.
  • To prevent system-related compressor problems, the following periodic maintenance is recommended.
  • Verify that safety devices are operational and properly set.
  • Ensure that the system is leak-tight.
  • Check the compressor current draw.
  • Confirm that the system is operating in a way consistent with previous maintenance records and ambient conditions.
  • Check that all electrical connections are still adequately fastened.
  • Keep the compressor clean and verify the absence of rust and oxidation on the compressor shell, tubes, and electrical connections.
  • Acid/moisture content in the system and oil should be checked regularly.

Warranty

  • Always transmit the model number and serial number with any claim filed regarding this product.

The product warranty may be void in the following cases:

  • Absence of nameplate.
  • External modifications, in particular, drilling, welding, broken feet, and shock marks.
  • Compressor opened or returned unsealed.
  • Rust, water, or leak detection dye inside the compressor.
  • Use of a refrigerant or lubricant not approved by Danfoss.
  • Any deviation from recommended instructions about installation, application, or maintenance.
  • Use in mobile applications.
  • Use in an explosive atmospheric environment.
  • No model number or serial number was transmitted with the warranty claim.

Disposal

  • Danfoss-Scroll-Compressor-FIG-6Danfoss recommends that compressors and compressor oil should be recycled by a suitable company at its site.
  • Danfoss can accept no responsibility for possible errors in catalogues, brochures, and other printed material. Danfoss reserves the right to alter its products without notice.
  • This also applies to products already on order, provided that such alterations can be made without subsequent changes being necessary in specifications already agreed.
  • All trademarks in this material are the property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

FAQ

Can I operate the compressor under nitrogen gas pressure?

No, the compressor should never be operated under nitrogen gas pressure. Follow all safety regulations and guidelines.

What should I do if there is a refrigerant leak?

In case of a refrigerant leak, repair the leak and repeat the leak detection process. Maintain proper refrigerant charge limits.

Documents / Resources

Danfoss Danfoss Scroll Compressor [pdf] Instruction Manual
LLZ034T4LQ9 Danfoss Scroll Compressor, LLZ034T4LQ9, Danfoss Scroll Compressor, Scroll Compressor, Compressor

References

Leave a comment

Your email address will not be published. Required fields are marked *