Danfoss Scroll Compressor

Specifications
- Model: LLZ compressors
- Refrigerants: r404A / r507
- Operating Limits: Standard and Economizer Cycle
- Electrical Connections: Three Phase
Product Usage Instructions
Installation and Servicing
- Installation and servicing should be performed by qualified personnel following sound refrigeration engineering practices.
Operating Limits
- The operating limits for LLZ compressors with R404A/R507 refrigerants are provided in the manual. Ensure to operate within the specified temperature and superheat ranges.
Electrical Connections
- Refer to the wiring diagram for electrical connections. Ensure proper connection of terminals and follow the instructions for the control circuit.
Usage Guidelines
- Do not operate the compressor under nitrogen gas pressure. Use the compressor only for its designed purpose. Follow all safety regulations and guidelines during operation.
Maintenance
- Ensure regular maintenance of the compressor. Use rubber grommets provided for sealing. Check for leaks and maintain proper refrigerant charge limits.
Safety Precautions
- Wear protective goggles and work gloves when handling the compressor. Avoid low-pressure operation and follow all safety standards.
PRODUCT OVERVIEW
- A: Model number
- B: Serial Number
- C: Technical number
- D: Manufacturing year
- E: Internal protection
- F: Supply voltage range
- G: Locked rotor current
- Maximum operating current
- H: Lubricant type and nominal charge
- I: Approved Refrigerant

- Installation and servicing of the compressor by qualified personnel only. Follow these instructions and sound refrigeration engineering practice relating to installation, commissioning, maintenance, and service.

Operating limits

- The compressor must only be used for its designed purpose(s) and within its scope of applica-tion (refer to «operating limits»). Consult the Application guidelines and datasheet available from cc.danfoss.com
- Never operate a compressor without the terminal box cover in place and secured.
- The compressor is delivered under nitrogen gas pressure (between 0.3 and 0.4 bar / 4 and 6 psi). Do not disassemble bolts, plugs, fittings, etc, unless all pressure has been relieved from the compressor.
- Under all circumstances, the EN378 (or other appli-cable local safety regulation) requirements must be fulfilled.
- Wear protective goggles and work gloves.
- The compressor must be handled with caution in the vertical position (maximum offset from the vertical: 15°).
Electrical connections

Wiring diagram
Three-phase (Wiring diagram with pump-down cycle)
Introduction
- These instructions pertain to the LLZ scroll compressors used for refrigeration systems. They provide necessary information regarding safety and proper usage of this product.
Handling and storage
- Handle the compressor with care. Use the dedicated handles in the packaging. Use the compressor lifting lug and use appropriate and safe lifting equipment.
- Store and transport the compressor in an upright position.
- Store the compressor between -35°C and 70°C / – 31°F and 158°F.
- Don’t expose the compressor and the packaging to rain or corrosive atmosphere.
Safety measures before assembly
- Never use the compressor in a flammable atmosphere.
- Mount the compressor on a horizontal flat surface with less than a 7° slope.
- Verify that the power supply corresponds to the compressor motor characteristics (see nameplate).
- When installing a compressor for R404A, R507or R407A, use equipment specifically reserved for HFC refrigerants that was never used for CFC or HCFC refrigerants.
- Use clean and dehydrated refrigeration-grade copper tubes and silver alloy brazing material.
- Use clean and dehydrated system components.
- The piping connected to the compressor must be flexible in 3 dimensions to dampen vibrations.
- The compressor must always be mounted with the rubber grommets supplied with the compressor.
Assembly
- Slowly release the nitrogen holding charge through discharge and suction ports.
- Connect the compressor to the system as soon as possible to avoid oil contamination from ambient moisture.
- Avoid material entering the system while cutting tubes. Never drill holes where burrs cannot be removed.
- Do not exceed the maximum tightening torque for rotolock connections
| Rotolock connections | Tightening torque |
| 1” Rotolock | 80 Nm |
| 1” 1/4 Rotolock | 90 Nm |
| 1” 3/4 Rotolock | 110 Nm |
Instructions
- Connect the required safety and control devices. When the schrader port, if any, is used for this, remove the internal valve.
- For parallel assemblies of the compressors in version C8, contact Danfoss.
Leak detection
- Never pressurize the circuit with oxygen or dry air. This could cause fire or explosion.
- Do not use leak detection dye.
- Perform a leak detection test on the complete system.
- The low side test pressure must not exceed 31 bar /450 psi.
- When a leak is discovered, repair the leak and repeat the leak detection.
Vacuum dehydration
- Never use the compressor to evacuate the system.
- Connect a vacuum pump to both the LP & HP sides.
- Pull down the system under a vacuum of 500 µm Hg (0.67 mbar) / 0.02 inch Hg absolute.
- Do not use a megohmmeter or apply power to the compressor while it is under vacuum, as this may cause internal damage.
Electrical connections
- Switch off and isolate the main power supply.
- All electrical components must be selected as per local standards and compressor requirements.
- Refer to page 1 for electrical connections details. For three-phase applications, the terminals are labeled T1, T2, and T3.
- Danfoss scroll compressors will only compress gas while rotating counter-clockwise (when viewed from the compressor top).
- Three-phase motors, however, will start and run in either direction, depending on the phase angles of the supplied power.
- Care must be taken during installation to ensure that the compressor operates in the correct direction.
- Use ø 4.8 mm / #10 – 32 screws and ¼” ring terminals for the power connection with ring connect screw terminal (C type). Fasten with 3 Nm torque.
- Use a self-tapping screw to connect the compressor to the earth.
Filling the system
- Keep the compressor switched off.
- Keep the refrigerant charge below the indicated charge limits if possible. Above this limit, protect the compressor against liquid flood-back with a pump-down cycle or suction line accumulator.
- Never leave the filling cylinder connected to the circuit.
| Compressor models | Refrigerant charge limit |
| LLZ013-015-018 | 4.5 kg / 10 lb |
| LLZ024-033 | 7.2 kg / 16 lb |
Verification before commissioning
- Use safety devices such as a safety pressure switch and a mechanical relief valve in compliance with both generally and locally applicable regulations and safety standards. Ensure that they are operational and properly set.
- Check that the settings of high-pressure switches don’t exceed the maximum service pressure of any system component.
- A low-pressure switch is recommended to avoid low-pressure operation.
- Minimum setting for R404A / R507 1.3 bar (absolute) / 19 psia
- Verify that all electrical connections are properly fastened and in compliance with local regulations.
- When a crankcase heater is required, it must be energized at least 24 hours before initial start-up and after prolonged shutdown.
Start-up
- Never start the compressor when no refrigerant is charged.
- Do not provide any power to the compressor unless the suction and discharge service valves are open, if installed.
- Energize the compressor. It must start promptly. If the compressor does not start, check wiring conformity and voltage on terminals.
- Eventual reverse rotation can be detected by following phenomena: excessive noise, no pressure differential between suction and discharge, and line warming rather than immediate cooling.
- A service technician should be present at initial start-up to verify that supply power is properly phased and that the compressor is rotating in the correct direction. For LLZ compressors, phase monitors are required for all applications.
- If the internal overload protector trips out, it must cool down to 60°C / 140°F to reset. Depending on ambient temperature, this may take up to several hours.
Check with the running compressor
- Check the current draw and voltage. Measurement of amps and volts during running conditions must be taken at other points in the power supply, not in the compressor electrical box.
- Check suction superheat to reduce the risk of slugging.
- Observe the oil level in the sight glass (if provided) for about 60 minutes to ensure proper oil return to the compressor.
- Respect the operating limits.
- Check all tubes for abnormal vibration. Movements in excess of 1.5 mm / 0.06 in require corrective measures such as tube brackets.
- When needed, additional refrigerant in liquid phase may be added in the low-pressure side as far as possible from the compressor. The compressor must be operating during this process.
- Do not overcharge the system.
- Never release refrigerant to the atmosphere.
- Before leaving the installation site, carry out a general installation inspection regarding cleanliness, noise, and leak detection.
- Record type and amount of refrigerant charge, as well as operating conditions, as a reference for future inspections.
Maintenance
- Internal pressure and surface temperature are dangerous and may cause permanent injury. Maintenance operators and installers require appropriate skills and tools.
- Tubing temperature may exceed 100°C / 212°F and can cause severe burns.
- Ensure that periodic service inspections to ensure system reliability and as required by local regulations, are performed.
- To prevent system-related compressor problems, the following periodic maintenance is recommended.
- Verify that safety devices are operational and properly set.
- Ensure that the system is leak-tight.
- Check the compressor current draw.
- Confirm that the system is operating in a way consistent with previous maintenance records and ambient conditions.
- Check that all electrical connections are still adequately fastened.
- Keep the compressor clean and verify the absence of rust and oxidation on the compressor shell, tubes, and electrical connections.
- Acid/moisture content in the system and oil should be checked regularly.
Warranty
- Always transmit the model number and serial number with any claim filed regarding this product.
The product warranty may be void in the following cases:
- Absence of nameplate.
- External modifications, in particular, drilling, welding, broken feet, and shock marks.
- Compressor opened or returned unsealed.
- Rust, water, or leak detection dye inside the compressor.
- Use of a refrigerant or lubricant not approved by Danfoss.
- Any deviation from recommended instructions about installation, application, or maintenance.
- Use in mobile applications.
- Use in an explosive atmospheric environment.
- No model number or serial number was transmitted with the warranty claim.
Disposal
Danfoss recommends that compressors and compressor oil should be recycled by a suitable company at its site.- Danfoss can accept no responsibility for possible errors in catalogues, brochures, and other printed material. Danfoss reserves the right to alter its products without notice.
- This also applies to products already on order, provided that such alterations can be made without subsequent changes being necessary in specifications already agreed.
- All trademarks in this material are the property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
FAQ
Can I operate the compressor under nitrogen gas pressure?
No, the compressor should never be operated under nitrogen gas pressure. Follow all safety regulations and guidelines.
What should I do if there is a refrigerant leak?
In case of a refrigerant leak, repair the leak and repeat the leak detection process. Maintain proper refrigerant charge limits.
Documents / Resources
![]() |
Danfoss Danfoss Scroll Compressor [pdf] Instruction Manual LLZ034T4LQ9 Danfoss Scroll Compressor, LLZ034T4LQ9, Danfoss Scroll Compressor, Scroll Compressor, Compressor |

