Danfoss-LOGO

Danfoss BD50F Electronic Unit for Compressors

Danfoss-BD50F-Electronic-Unit-for-Compressors-product

Specifications

  • Product: Electronic Unit for BD50F Compressors
  • Model: 101N0230

Product Usage Instructions

  • Connect the terminal plug from the electronic unit to the compressor terminal.
  • Mount the electronic unit on the compressor by snapping the cover over the screw head (1).
  • The compressor stops and restarts according to the designated voltage limits measured on the + and – terminals of the electronic unit. Standard settings for 12V and 24V power supply systems are shown in Fig. 3. Optional settings (Fig. 4) can be implemented by establishing a connection with a resistor (9) between terminals C and P.
  • Connect the thermostat (7) between terminals C and T.
  • Without a resistor in the control circuit, the compressor runs at a fixed speed of 2,000 rpm when the thermostat is switched on.
  • Different fixed compressor speeds between 2,000 and 3,500 rpm can be achieved by installing a resistor (8) to adjust the current (mA) of the control circuit. Refer to Fig. 5 for resistor values.
  • A fan (5) can be connected between the terminals + and F.
  • Connect the plus to + and the minus to F.
  • Use a 12V fan for both 12V and 24V power supply systems, as the output voltage is regulated to 12V.
  • The fan output can supply a continuous current of 0.5Aavg, with a higher current draw allowed for 2 seconds during start.

Introduction

  • The electronic unit is a dual-voltage device.
  • This means that the same unit can be used in both 12V and 24V power supply systems.
  • Maximum voltage is 17V for a 12V system and 31.5V for a 24V power supply system.
  • Max.. ambient temperature is 55°C.
  • The electronic unit has a built-in thermal protection that is actuated and stops compressor operation if the electronic unit temperature gets too high.

Installation

  • Connect the terminal plug from the electronic unit to the compressor terminal.
  • Mount the elec tro nic unit on the compressor by snapping the cover over the screw head (1).

Danfoss-BD50F-Electronic-Unit-for-Compressors-fig-1

Power supply

  • The electronic unit must always be connected directly to the battery poles (2).
  • Connect the plus to + and the minus to -, otherwise, the electronic unit will not work.
  • The electronic unit is protected against reverse battery connection.
  • For protection during installation, a fuse (3) must be mounted in the + cable as close to the battery as possible. 15A fuse for 12V and 7.5A fuse for 24V circuits are recommended.
  • If a main switch (4) is used, it should be rated to a minimum current of min. 20A.
  • The wire dimensions in Fig. 2 must be observed.
  • Avoid extra junctions in the power supply system to prevent voltage drop from affecting the battery protection setting.

Danfoss-BD50F-Electronic-Unit-for-Compressors-fig-2

Battery protection

  • The compressor stops and restarts again according to the designated voltage limits meas- ured on the + and – terminals of the electronic unit.
  • The standard settings for 12V and 24V power supply systems appear in Fig. 3.Danfoss-BD50F-Electronic-Unit-for-Compressors-fig-3
  • Other settings (Fig. 4) are optional if a connection that includes a resistor (9) is established between terminals C and P.

Danfoss-BD50F-Electronic-Unit-for-Compressors-fig-4

Thermostat

  • The thermostat (7) is connected between the terminals C and T. Without any resistor in the control circuit, the compressor will run with a fixed speed of 2,000 rpm when the thermostat is switched on.
  • Other fixed compressor speeds in the range between 2,000 and 3,500 rpm can be obtained when a resistor (8) is installed to adjust the current (mA) of the control circuit. Resistor values for various motor speeds appear in Fig. 5.Danfoss-BD50F-Electronic-Unit-for-Compressors-fig-5

Fan optional

  • A fan (5) can be connected between the terminals + and F.
  • Connect the plus to + and the minus to F.
  • Since the output voltage between the terminals + and F is always regulated to 12V, a 12V fan must be used for both 12V and 24V power supply systems.
  • The fan output can supply a continous current of 0.5Aavg. A higher current draw is allowed for 2 seconds during start.

LED optional

  • A 10mA light-emitting diode (LED) (6) can be connected between the terminals + and D.
  • In case the electronic unit records an operational error, the diode will flash a number of times.
  • The number of flashes depends on what kind of operational error was recorded. Each flash will last ¼ second.
  • After the actual number of flashes, there will be a delay with no flashes, so that the sequence for each error recording is repeated every 4 seconds.
Number of fashes Error type
5 Thermal cut-out of electronic unit (If the refrigeration system has been too heavily loaded, or if the ambient temperature is high, the electronic unit will run too hot).
4 Minimum motor speed error

(If the refrigeration system is too heavily loaded, the motor cannot maintain a minimum speed of 1,850 rpm.)

3 Motor start error

(The rotor is blocked or the differential pressure in the refrigeration system is too high (>5 bar)).

2 Fan over-current cut-out

(The fan loads the electronic unit with more than 1Apeak).

1 Battery protection cut-out

(The voltage is outside the cut-out setting.)

VDE/UL Approvals for BD Compressors

Approved Compressor – Electronic Unit Combinations

Danfoss-BD50F-Electronic-Unit-for-Compressors-fig-6

  • Danfoss-BD50F-Electronic-Unit-for-Compressors-fig-7= Combination possible, VDE or UL approval
  • Danfoss-BD50F-Electronic-Unit-for-Compressors-fig-8= Combination possible, but no approval
  • Danfoss-BD50F-Electronic-Unit-for-Compressors-fig-9= Combination not possible

Danfoss can accept no responsibility for possible errors in catalogues, brochures, and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order, provided that such alterations can be made without subsequent changes being necessary in specifications already agreed upon.
All trademarks in this material are the property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Designed and manufactured by Secop for DANFOSS – DEHC.EI.100.J6.02 / 520N0276 compressors.danfoss.com – DEHC.EI.100.J6.02 / 520N0276

FAQ

  • Q: What are the error types indicated by the number of flashes on the electronic unit?
    • Thermal cut-out of electronic unit –  Indicates overheating due to heavy load or high ambient temperature.
    • Minimum motor speed error – Indicates heavy load causing motor speed to drop below minimum required (1,850 rpm).
    • Motor start error – Indicates rotor blockage or high differential pressure (>5 bar) in the refrigeration system.
    • Fan over-current cut-out – Indicates excessive current draw by the fan.

Documents / Resources

Danfoss BD50F Electronic Unit for Compressors [pdf] Instructions
BD50F Electronic Unit for Compressors, BD50F, Electronic Unit for Compressors, Unit for Compressors, for Compressors

References

Leave a comment

Your email address will not be published. Required fields are marked *