Danfoss logoDanfoss AVPQ Differential Pressure and Flow ControllerInstructions
AVPQ, AVPQ-F, AVPQ 4, AVPQT 
PN 16,25 / DN 15 – 50

AVPQ Differential Pressure and Flow Controller

Danfoss AVPQ Differential Pressure and Flow Controller - partsDanfoss AVPQ Differential Pressure and Flow Controller - parts 1

Differential pressure and flow controller
AVPQ, AVPQ-F, AVPQ 4, AVPQT
www.danfoss.com

Safety Notes

Warning Prior to assembly and commisioning to avoid injury of persons and damages of the devices, it is absolutely necessary to carefully read and observe these instructions. Necessary assembly, startup, and maintenance work must be performed only by qualified, trained and authorized personnel.
Prior to assembly and maintenance work on the controller, the system must be:
– depressurized,
– cooled down,
– emptied and
– cleaned.
Please comply with the instructions of the system manufacturer or system operator.

Definition of Application

The controller is used for differential pressure and flow (and temperature at AVPQT) control of water and water glycol mixtures for heating, district heating and cooling systems.
The technical parameters on the product labels determine the use.

Assembly

Admissible Installation Positions
Medium temperatures up to 100 °C:
– Can be installed in any position.
Medium temperatures > 100 °C:
– Installation permitted only in horizontal pipelines with the actuator oriented downwards.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 1

Installation Location and Installation Scheme

  1. AVPQ(-F)
    return mountingDanfoss AVPQ Differential Pressure and Flow Controller - Assembly 2
  2. AVPQ 4
    flow mountingDanfoss AVPQ Differential Pressure and Flow Controller - Assembly 3
  3. AVPQT
    return mountingDanfoss AVPQ Differential Pressure and Flow Controller - Assembly 4

Valve Installation

  1. Clean pipeline system prior to assembly.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 5
  2. The installation of a strainer in front of the controller is strongly recommended 1.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 6
  3. Install pressure indicators in front of and behind the system part to be controlled.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 7
  4. Install valve
    • The flow direction indicated on the product label 2 or on the valve must be observed 3.
    • The valve with mounted weld-on taipieces may only be spotwelded to the pipeline 5.
    The weld-on taipieces may be welded only without the valve and seals! 5 6Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 8 If these instructions are not observed, high welding temperatures may destroy the seals.
    • Flanges 7 in the pipeline must be in parallel position and sealing surfaces must be clean and without any damage. Tighten screws in flanges crosswise in 3 steps up to the maximum torque (50 Nm).
  5. Caution:
    Mechanical loads of the valve body by the pipelines are not permitted.

Mounting of temperature actuator
(relevant only at AVPQT controllers)
Place temperature actuator AVT at the combination piece and tighten union nut with wrench SW 50.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 9Torque 35Nm.
Other details:
See instructions for temperature actuator AVT.

Impulse tube mounting

  • Which impulse tubes to use?
    Use Impulse tube set AV 1 or use followinge pipe:
    Copper Ø 6×1 mm
    EN 12449Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 10
  • Connection of impulse tube 1 in the system
    Return mounting 2Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 11
    Flow mounting 3Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 12
  • Connection to the  pipeline
    It is strongly recommended to install the impulse tube to the pipeline horizontally 2 or upwards 1.
    This prevents dirt accumulation in the impulse tube and possible  malfunction of thecontroller.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 13Connection downwards is not recommendable 3.

Impulse Tube Mounting

  1. Cut pipe perpendicularly to the pipe axis and smooth edges out 1.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 14
  2. Press impulse tube 2 into the threaded joint up to its stop.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 15
  3. Tighten union nut 3 Torque 14 Nm

Insulation

For medium temperatures up to 100 °C the pressure actuator 1 may also be insulated.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 16Dimensions, Weights
1) Conical ext. thread acc. to EN 10226-1
2) Flanges PN 25, acc. to EN 1092-2Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 17

DN 15 20 25 32 40 50
SW mm 32 (G 3/4A) 41 (G 1A) 50 (G 11/4A) 63 (G 13/4A) 70 (G 2A) 82 (G 21/2A)
d 21 26 33 42 47 60
R1) 1/2 3A 1 1 1/4
L12) 130 150 160
L2 131 144 160 177
L3 139 154 159 184 204 234
k 65 75 85 100 110 125
d2 14 14 14 18 18 18
n 4 4 4 4 4 4

Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 18Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 19Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 20AVPQ PN 25

DN 15 20 25 32 40 50
L mm 65 70 75 100 110 130
Ll 180 200 230
H (Ap = 0.2 – 1.0) 175 175 175 217 217 217
H (Ap = 0.3 – 2.0) 219 219 219 260 260 260
H1 (Ap = 0.2 – 1.0) 217 217 217
H1 (Ap = 0.3 – 2.0) 260 260 260
H2 73 73 76 103 103 103
H3 103 103 103

Note: other flange dimensions – see table for tailpieces
AVPQ 4 PN 25

DN 15 20 25 32 40 50
L mm 65 70 75 100 110 130
L1 180 200 230
H 298 298 298 340 340 340
H1 340 340 340
H2 73 73 76 103 103 103
H3 103 103 103

Note: other flange dimensions – see table for tailpieces
AVPQ PN 16

DN 15 20 25 32
L 65 70 75 100
H mm 301 301 301 301
H2 73 73 76 77

AVPQ-F PN 16

DN 15 20 25 32
L 65 70 75 100
H mm 165 165 165 165
H2 73 73 76 77

Start-up

Filling the system, first start-up

  1. Slowly open shut-off valves 1 that are possibly available in the impulse tubes.
  2. Open valves 2 in the system.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 21
  3. Slowly open shut-off devices 3 in the flow pipeline.
  4. Slowly open shut-off devices 4 in the return pipeline.

Leak and Pressure Tests
Before pressure test, open the adjustable flow restrictor 2 by turning it to the left (counter clockwise).
Warning icon Pressure must be gradually increased at the +/- connection 1.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 22Non-compliance may cause damages at the actuator or the valve.
A pressure test of the entire system must be carried out in accordance with manufacturer’s instructions.
The maximum test pressure is:
1.5 x PN
PN – see product label

Putting out of operation

  1. Slowly close shut-off devices 1 in the flow  pipeline.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 23
  2. Slowly close shut-off devices 2 in the return pipeline.

Settings
First set the differential pressure.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 24Differential Pressure Setting
(not relevant at fixed setting version AVPQ-F)
The diff. pressure setting range is indicated on the product label 1.
Procedure:

  1. Unscrew cover 2.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 25
  2. Loosen counter nut 3.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 26
  3. Unscrew (counter-clockwise) adjustable flow restrictor 4 up to its stop.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 27
  4. Start system, see section “Filling the system, first start-up“ Completely open all shutoff  devicesin the system.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 28
  5. Set flow rate on a motorised valve 1, on which differential pressure is controlled, to about 50 % .
  6. Adjustment
    Observe pressure indicators 4 or/and alternatively see handle scale indication.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 29Turning to the right 2 (clockwise) increases the set-point (stressing the spring).Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 30Turning to the left 3 (counter-clockwise) reduces the set-point (releasing the spring).

Note: 
If the required differential pressure is not attained, a cause may be a too small pressure loss in the system

Seal
The set-point adjuster can be sealed by a seal wire 1, if neccessary.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 31Flow Rate Setting
The flow rate is adjusted by means the setting of adjustable flow restrictor 1.
There are two possibilities:

  1. Adjustment with the flow adjusting curves,Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 32
  2. Adjustment with heat meter, see page 19.

Pre-condition
(min. diff. pressure over the valve)
At the maximum flow rate, the pressure difference ∆pv across the control valve musbe at least:
∆p min = 0.5 barDanfoss AVPQ Differential Pressure and Flow Controller - Assembly 33Adjustment with flow adjusting curves
The system don’t need to be active for being adjusted.

  1. Unscrew cover 1, loosen counter nut 2.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 34
  2. Screw (clockwise) adjustable flow restrictor 3 in up to its stop.
    Valve is closed, no flow.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 36
  3. Select flow adjusting curve in the diagram (see next page).Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 37
  4. Unscrew (counterclockwise) the adjustable flow restrictor by determined number of revolutions 4.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 38
  5. Adjustment is completed,continue with step 3,page 19.

Note:
The setting may be verified with help of a heat meter if the system is in operation, see next section.
Flow Adjusting CurvesDanfoss AVPQ Differential Pressure and Flow Controller - Assembly 39

Adjustment with Heat Meter
Pre-condition:
The system must be in operation. All units in the system 1 or a bypass must be completely open.

  1. Unscrew cover 2, loosen counter nut 3.
  2. Observe heat meter indicator.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 40 Turning to the left (counter-clockwise) 4 increases the flow rate.
    Turning to the right (clockwise) 5 reduces the flow rate.Danfoss AVPQ Differential Pressure and Flow Controller - Assembly 42After the adjustment has been completed:
  3. Tighten counter nut 6.
  4. Screw the cover 7 in and tighten.
  5. Cover may be sealed.

Temperature setting
(relevant only at AVPQT controllers)
See instructions for temperature actuator AVT.Danfoss logo

Documents / Resources

Danfoss AVPQ Differential Pressure and Flow Controller [pdf] Instructions
AVPQ, AVPQ-F, AVPQ4, AVPQT, AVPQ Differential Pressure and Flow Controller, AVPQ, Differential Pressure and Flow Controller, Pressure and Flow Controller, Flow Controller

References

Leave a comment

Your email address will not be published. Required fields are marked *