AK-CC 550A Case Room Controller
“
Specifications:
- Model: AK-CC 550A
- Supply Voltage: 230 V a.c., 50/60 Hz
- Connections: See detailed instructions below
Product Usage Instructions:
Overview of Outputs and Applications:
The AK-CC 550A controller has various outputs and applications
as listed below:
- DO1: Connection of expansion valve type AKV or AKVA with a 230
V a.c. coil - DO2: Alarm handling and connections for different
scenarios - DI1 to AI6: Digital input signals and analog input signals for
specific functions
Detailed Connections:
Make the following connections based on the requirements:
- Connect Pressure Transmitter AKS 32R to terminals 30, 31, and
32 using cable 060G1034 (Black=30, Blue=31, Brown=32) - Connect Pt 1000 ohm sensors to designated terminals based on
application needs - RS485 for data communication (terminal 51, 52, 53) and RJ45 for
TCP/IP module
Specific Sensors Connection:
Connect the sensors as follows:
- S3: Air sensor placed before the evaporator
- S4: Air sensor placed after the evaporator
- S5: Defrost sensor placed on the evaporator
Data Communication:
For data communication, use RS485 or MODBUS terminals as per
requirements. Ensure correct connections for effective
communication.
FAQ:
Q: What should I do if I encounter alarm situations with the
AK-CC 550A?
A: In alarm situations, ensure proper connections between
terminal 7 and 8. For power loss scenarios, maintain connections
for uninterrupted functionality.
Q: How do I handle different scenarios like rail heat, night
blind, and suction line valve with the AK-CC 550A?
A: Connect terminal 7 accordingly; for rail heat and heating
element in drip tray, connect terminal 7 and 9. For night blind and
suction line valve operations, also connect terminal 7 and 9 as
needed.
“`
Identification
Instructions
AK-CC 550A
Dimensions
Principle
084B8030
S2: Insulate sensor Fühler isolieren Capteur isolés Isolér føleren Sensores aislados
AKV info !!
230 V a.c. spole 230 V a.c. coil 230 V a.c. Spule 230 V c.a. Bobine 230 V c.a. Bobina 230 V c.a. Bobine
AK-CC 550A Additional information: Weitere Information: Renseignements supplémentarires: Yderligere information: Información adicional: Informazioni aggiuntive! Ytterligare information: Aanvullende informatie:
English Manual Deutsches Manual Manuel en français Dansk Manual Manual español Manuale in italiano Svenska Handbok Dutch Handleiding
RS8FS…
www.danfoss.com
RI8NP702 2018-09
1 – 8
The controller is provided with signs from the factory indicating application 1. If you employ another use, signs are provided so that you can mount the relevant one. Werkseitig wird der Regler mit Schildern geliefert, die Anwendung 1 angeben. Wenn Sie eine andere Anwendung verwenden, so montieren Sie bitte das entsprechende der mitgelieferten Schilder. Les régulateurs sortis d’usine sont livrés avec une étiquette indiquant l’utilisation 1. Si vous optez pour une autre utilisation, des plaques sont jointes pour vous permettre de monter la plaque adéquate. Fra fabrikken er regulatoren leveret med skilte, der angiver anvendelse 1. Hvis du benytter en anden anvendelse, er der medleveret skilte, så du kan montere det aktuelle.
1
2
3
4
2
Instructions RI8NP702 © Danfoss 2018-09
AK-CC 550A
5
6
7
8
9
9 10
10
AK-CC 550A
Instructions RI8NP702 © Danfoss 2018-09
3
Data communication Datenkommunikation Transmission de données Datakommunikation
Important All connections to the data communication MODBUS and RS 485 must comply with the requirements for data communication cables. See literature: RC8AC.
Wichtig Alle Anschlüsse an die Datenkommunikation MODBUS und RS 485 müssen die Anforderungen erfüllen, die an Datenkommunikationskabel gestellt werden. Siehe Literatur: RC8AC
Important Tout raccordement au système de données MODBUS et à RS 485 doit satisfaire à la norme applicable pour les câbles de transmission de données. Voir documentation : RC8AC
Vigtigt Alle tilslutninger til datakommunikationen MODBUS og RS 485, skal overholde de krav, der stilles til datakommunikationskabler. Se litteratur: RC8AC
System manager / Gateway
AK-SM….
Display EKA 163 / 164 L < 15 m
AKA 245 version 6.20+ / AK-SM…
OEM
L > 15 m
! Address: o03 > 0
4
Instructions RI8NP702 © Danfoss 2018-09
AK-CC 550A
Connections
English
Overview of outputs and applications.
See also electrical diagrams earlier in the instruction
Application 1 2 3 4 5 6 7 8 9 10
DO1 DO2 DO3 DO4 DO5 DO6 DI1 DI2 DI3 AI1 AI2 AI3 AI4 AI5 AI6
· · · P0 S2 S3 S4 S5 S6
· · · P0 S2 S3 S4 S5 S6
· · · P0 S2 S3 S4 S5 S6
· · · P0 S2 S3 S4 S5 S6
· · · P0 S2 S3 S4 S5 S6
suction Blinds
hotgas
heat
21
· · · P0 S2 S3 S4 S5 S6 · · · P0 S2 S3 S4 S5 S6 · · · P0 S2 S3 S4 S5 S6 · · · P0 S2 S3 S4 S5 S5B · · · P0 S2 S3 S4 S5 S3B
DI1 Digital input signal. The defined function is active when the input is short-circuited/ opened. The function is defined in o02.
EKA Display If there is be external reading/operation of the controller, display type EKA 163B or EKA 164B can be connected.
DI2 Digital input signal. The defined function is active when the input is short-circuited/ opened. The function is defined in o37.
Pressure transmitter AKS 32R
Connect to terminal 30, 31 and 32. (Used cable 060G1034: Black=30, Blue=31, Brown=32) The signal from one pressure transmitter can be received by up to 10 controllers. But only if there are no significant pressure decreases between the evaporators to be controlled.
S2, S6 Pt 1000 ohm sensor
S6 / S5B / S3B, product sensor or defrost sensor B or air sensor B. The application determines which.
S3, S4, S5 Pt 1000 ohm sensor or PTC 1000 ohm sensor. All have to be of the same type.
S3, air sensor, placed in the warm air before the evaporator S4, air sensor, placed in the cold air after the evaporator
(the need for either S3 or S4 can be deselected in the configuration) S5, defrost sensor, placed on the evaporator
RS485 (terminal 51, 52, 53) For data communication, but only if a data communication module is inserted in the controller. The module can be a LON RS485, DANBUSS or a MODBUS. Terminal 51 = screen Terminal 52 = A (A+) Terminal 53 = B (B-) (For LON RS485 and gateway type AKA 245 the gateway must be version 6.20 or higher.)
RJ45 For data communication, but only if a TCP/IP module is inserted in the controller. (OEM)
MODBUS For data communication. Terminal 56 = screen Terminal 57 = A+ Terminal 58 = B(Alternatively the terminals can be connected to an external display type EKA 163A or 164A, but then they cannot be used for data communication. Any data communication must then be carried out by one of the other methods.)
Supply voltage 230 V a.c., 50/60 Hz
AK-CC 550A
Instructions RI8NP702 © Danfoss 2018-09
5
DO1 Connection of expansion valve type AKV or AKVA. The coil must be a 230 V a.c. coil.
DO2 Alarm
There is a connection between terminal 7 and 8 in alarm situations and when the controller is without power. Rail heat and heating element in drip tray There is connection between terminal 7 and 9 when heating takes place. Night blind There is connection between terminal 7 and 9 when the night blind is up. Suction line valve There is connection between terminal 7 and 9 when the suction line must be open.
DO6 Light relay
There is connection between terminal 17 and 18 when the light must be on. Rail heat, Compressor 2 There is connection between terminal 17 and 19 when the function must be active.
DI3 Digital input signal. The signal must have a voltage of 0 / 230 V AC. The function is defined in o84.
Data communication If data communication is used, it is important that the installation of the data communication cable is performed correctly. See separate literature No. RC8AC…
DO3 Refrigeration, Rail heat, Heat function, Defrost 2
There is connection between terminal 10 and 11 when the function must be active. Heating element in drip tray There is connection between terminal 10 and 11 when heating takes place.
DO4 Defrost
There is connection between terminal 12 and 14 when defrosting takes place. Hot gas / drain valve There is connection between terminal 13 and 14 during normal operation. There is connection between terminal 12 and 14 when the hot gas valves must open.
DO5 Fan
There is connection between terminal 15 and 16 when the fan is on.
Coordinated defrost via cable connections
Electric noise Cables for sensors, DI inputs and data communication must be kept separate from other electric cables: – Use separate cable trays – Keep a distance between cables of at least 10 cm – Long cables at the DI input should be avoided
Installation considerations Accidental damage, poor installation, or site conditions, can give rise to malfunctions of the control system, and ultimately lead to a plant breakdown. Every possible safeguard is incorporated into our products to prevent this. However, a wrong installation, for example, could still present problems. Electronic controls are no substitute for normal, good engineering practice. Danfoss will not be responsible for any goods, or plant components, damaged as a result of the above defects. It is the installer’s responsibility to check the installation thoroughly, and to fit the necessary safety devices. Special reference is made to the necessity of signals to the controller when the compressor is stopped and to the need of liquid receivers before the compressors. Your local Danfoss agent will be pleased to assist with further advice, etc.
Max. 10
The following controllers can be connected up in this way: EKC 204A, AK-CC 210, AK-CC 250, AK-CC 450, AK-CC 550_,
Refrigeration is resumed when all controllers have “released” the signal for defrost.
Coordinated defrost via data communication
The setting of controllers to coordinate their defrosting takes place in the gateway/system manager.
Refrigeration is resumed when all controllers have “released” the signal for defrost.
6
Instructions RI8NP702 © Danfoss 2018-09
AK-CC 550A
Operation
Display The values will be shown with three digits, and with a setting you can determine whether the temperature is to be shown in °C or in °F.
Get a good start
With the following procedure you can start regulation very quickly:
1 Open parameter r12 and stop the regulation (in a new and not previously set unit, r12 will already be set to 0 which means stopped regulation.)
Light-emitting diodes (LED) on front panel The LED’s on the front panel will light up when the relevant relay is activated.
= Refrigeration = Defrost = Fan running
The light-emitting diodes will flash when there is an alarm. In this situation you can download the error code to the display and cancel/sign for the alarm by giving the top button a brief push.
The buttons When you want to change a setting, the upper and the lower buttons will give you a higher or lower value depending on the button you are pushing. But before you change the value, you must have access to the menu. You obtain this by pushing the upper button for a couple of seconds – you will then enter the column with parameter codes. Find the parameter code you want to change and push the middle buttons until value for the parameter is shown. When you have changed the value, save the new value by once more pushing the middle button.
Examples
Set menu 1. Push the upper button until a parameter r01 is shown 2. Push the upper or the lower button and find that parameter you
want to change 3. Push the middle button until the parameter value is shown 4. Push the upper or the lower button and select the new value 5. Push the middle button again to freeze the value.
Cutout alarm relay / receipt alarm/see alarm code · A short press of the upper button
If there are several alarm codes they are found in a rolling stack. Push the uppermost or lowermost button to scan the rolling stack.
Set temperature 1. Push the middle button until the temperature value is shown 2. Push the upper or the lower button and select the new value 3. Push the middle button again to conclude the setting.
Reading the temperature at defrost sensor (Or product sensor, if selected in o92.) · A short press of the lower button
2 Select electrical connection based on the drawings on page 2 and 3
3 Open parameter o61 and set the electric connection number in it
4 Now select one of the preset settings from the table
Auxiliary schedule for settings (quick-setup)
Case Defrost stop on
Room Defrost stop on
time
S5
time
S5
Preset settings (o62)
1
2
3
4
5
6
Temperature (SP)
2°C -2°C -28°C 4°C 0°C -22°C
Max. temp. setting (r02)
6°C
4°C -22°C 8°C
5°C -20°C
Min. temp. setting (r03)
0°C -4°C -30°C 0°C -2°C -24°C
Sensor signal for thermo-
100%
0%
stat. S4% (r15)
Alarm limit high (A13)
8°C 6°C -15°C 10°C 8°C -15°C
Alarm limit low (A14)
-5°C -5°C -30°C 0°C 0°C -30°C
Sensor signal for alarm funct.S4% (A36) Interval between defrost (d03) Defrost sensor: 0=time, 1=S5, 2=S4 (d10) DI1 config. (o02)
0%
100%
6 h
6h 12h
0
1
1
Case cleaning (=10)
0%
8h
8h
6h
0
1
1
Door function (=2)
Sensor signal for display
0%
view S4% (017)
Note: For applications 9 and 10 the sensor weighting for the S3/S4 sensors is not used for the
thermostat, alarm thermostat and display readings as the sensor uses are predefined.
5 Open parameter o62 and set the number for the array of presettings. The few selected settings will now be transferred to the menu.
6 Select refrigerant via parameter o30
7 Open parameter r12 and start the regulation
8 Go through the survey of factory settings. The values in the grey cells are changed according to your choice of settings. Make any necessary changes in the respective parameters.
9 For network. Set the address in o03
10 Send address to system unit: · MODBUS: Activate scan function in system unit · If another data communication card is used in the controller: – LON RS485: Activate the function o04
Manuel start or stop of a defrost · Push the lower button for four seconds. (However, not at Application 6)
AK-CC 550A
Instructions RI8NP702 © Danfoss 2018-09
7
Menu survey
Function
Parameter
Normal operation
Temperature (setpoint) Thermostat Differential Max. limitation of setpoint setting Min. limitation of setpoint setting Adjustment of temperature indication
Temperature unit (°C/°F) Correction of the signal from S4
Correction of the signal from S3
Manual service, stop regulation, start regulation (-1, 0, 1) Displacement of reference during night operation Define thermostat function 1=ON/OFF, 2=Modulating Definition and weighting, if applicable, of thermostat sensors – S4% (100%=S4, 0%=S3) Time between melt periods Duration of melt periods Temperature setting for thermostat band 2 . As differential use r01
Correction of the signal from S6 Definition and weighting, if applicable, of thermostat sensors when night cover is on. (100%=S4, 0%=S3) Heat function Neutral zone between refrigeration and heat function
Time delay at switch between refrigeration and heat function Alarms Delay for temperature alarm
Delay for door alarm Delay for temperature alarm after defrost High alarm limit for thermostat 1 Low alarm limit for thermostat 1 High alarm limit for thermostat 2 Low alarm limit for thermostat 2 High alarm limit for sensor S6 at thermostat 1 Low alarm limit for sensor S6 at thermostat 1 High alarm limit for sensor S6 at thermostat 2 Low alarm limit for sensor S6 at thermostat 2 S6 alarm time delay With setting = 240 the S6 alarm will be omitted Alarm time delay or signal on the DI1 input Alarm time delay or signal on the DI2 input Signal for alarm thermostat. S4% (100%=S4, 0%=S3) Delay for S6 (product sensor alarm) after defrost Compressor Min. ON-time Min. OFF-time Time delay for cutin of comp.2 Defrost Defrost method: 0=off, 1= EL, 2= gAs Defrost stop temperature Interval between defrost starts
Max. defrost duration Displacement of time on cutin of defrost at start-up
Drip off time
Delay for fan start after defrost
Fan start temperature
Fan cutin during defrost 0: Stopped 1: Running 2: Running during pump down and defrost 3: Running but stops at the temperature set in d41 Defrost sensor: 0 =Stop on time, 1=S5, 2=S4, 3=Sx (Application 1-8 and 10: both S5 and S6. Application 9: S5 and S5B) Pump down delay
Drain delay (used at hot gas defrost only) Max. aggregate refrigeration time between two defrosts
Heat in drip tray. Time from defrosting stops to heating in the drip tray is switched off
SW = 2.0x
Code
1
2
EL-diagram page 2 or 3 3 4 5 67 8 9
10 Min.-value Max.-value
Factory setting
Actual setting
– – – 1 1 1 1 1 1 1 1 1 1 -50°C
r01 1 1 1 1 1 1 1 1 1 1 0.1 K r02 1 1 1 1 1 1 1 1 1 1 -49°C r03 1 1 1 1 1 1 1 1 1 1 -50°C r04 1 1 1 1 1 1 1 1 1 1 -10
r05 1 1 1 1 1 1 1 1 1 1 0/°C r09 1 1 1 1 1 1 1 1 1 1 -10 K
r10 1 1 1 1 1 1 1 1 1 1 -10 K
r12 1 1 1 1 1 1 1 1 1 1 -1 r13 1 1 1 1 1 1 1 1 1 1 -50 K r14 1 1 1 1 1 1 1 1 1 1 1
r15 1 1 1 1 1 1 1 1
0 %
r16 1 1 1 1 1 1 1 1 1 1 0 hrs r17 1 1 1 1 1 1 1 1 1 1 0 min. r21 1 1 1 1 1 1 1 1 1 1 -50°C
r59 1 1 1 1 1 1 1 1 r61 1 1 1 1 1 1 1 1
r62
1
r63
1
-10 K 0 %
0 K
0 min.
50°C
2
20 K
2
50°C
50
49°C
-50
10
0
1/F
0/°C
10 K
0
10 K
0
1
0
50 K
0
2
1
100 % 100
10 hrs
1
30 min. 5
50°C
2
10 K
0
100 % 100
50 K
2
240 min. 0
A03 1 1 1 1 1 1 1 1 1 1 0 min.
A04 1 1 1 1 1 1 1 1 1 1 0 min.
A12 1 1 1 1 1 1 1 1 1 1 0 min.
A13 1 1 1 1 1 1 1 1 1 1 -50°C
A14 1 1 1 1 1 1 1 1 1 1 -50°C
A20 1 1 1 1 1 1 1 1 1 1 -50°C
A21 1 1 1 1 1 1 1 1 1 1 -50°C
A22 1 1 1 1 1 1 1 1
-50°C
A23 1 1 1 1 1 1 1 1
-50°C
A24 1 1 1 1 1 1 1 1
-50°C
A25 1 1 1 1 1 1 1 1
-50°C
A26 1 1 1 1 1 1 1 1
0 min.
240 min. 30
240 min. 60
240 min. 90
50°C
8
50°C
-30
50°C
8
50°C
-30
50°C
8
50°C
-30
50°C
8
50°C
-30
240 min. 240
A27 1 1 1 1 1 1 1 1 1 1 0 min.
A28 1 1 1 1 1 1 1 1 1 1 0 min.
A36 1 1 1 1 1 1 1 1
0 %
A52 1 1 1 1 1 1 1 1
0 min.
240 min. 30 240 min. 30 100 % 100 240 min. 90
c01 1 1 1
1
c02 1 1 1
1
c05
1
0 min. 0 min. 0 sec
30 min. 0 30 min. 0 999 sec 5
d01 1 1 1 1 1 1 1 1 1 1 0/off
2/gAs
1/EL
d02 1 1 1 1 1 1 1 1 1 1 0°C
50°C
6
d03 1 1 1 1 1 1 1 1 1 1 0 hrs/Off 240 hrs 8
d04 1 1 1 1 1 1 1 1 1 1 0 min. 360 min. 45
d05 1 1 1 1 1 1 1 1 1 1 0 min. 240 min. 0
d06 1 1 1 1 1 1 1 1 1 1 0 min. 60 min. 0
d07 1 1 1 1 1 1 1 1 1 1 0 min. 60 min. 0
d08 1 1 1 1 1 1 1 1 1 1 -50 °C 0 °C
-5
d09 1 1 1 1 1 1 1 1 1 1 0
3
1
d10 1 1 1 1 1 1 1 1 1 1 0
3
0
d16 1 1 1 1 1 1 1 1 1 1 0 min.
d17
1
0 min.
d18 1 1 1 1 1 1 1 1 1 1 0 hrs
d20
1
0 min.
60 min. 60 min. 48 hrs 240 min.
0 0 0/OFF 30
8
Instructions RI8NP702 © Danfoss 2018-09
AK-CC 550A
Continued
Adaptive defrost: 0=not active, 1=monitoring only, 2=skip allowed day, 3=skip allowed both day and night, 4=own assessment + all schedules
Time delay before opening of hot gas valve Rail heat during defrost 0=off. 1=on. 2=Pulsating Max. duration of -d- in display
Temperature limit for fan stop during defrost when d09 is set to 3 Injection control function
Max. value of superheat reference Min. value of superheat reference MOP temperature. Off if MOP temp. = 15.0 °C Period time of AKV pulsation Only for trained personnel Max. limitation for the superheat reference when regulating with adaptiv liquid control Min. limitation for the superheat reference when regulating with adaptiv liquid control Fan Fan stop temperature (S5) Pulse operation on fans: 0=No pulse operation, 1=At thermostat cuts out only, 2= Only at thermostat cut outs during night operation Period time for fan pulsation (on-time + off-time) On-time in % of period time Real time clock
Six start times for defrost. Setting of hours. 0=OFF Six start times for defrost. Setting of minutes. 0=OFF
Clock – Setting of hours Clock – Setting of minute
Clock – Setting of date Clock – Setting of month Clock – Setting of year Miscellaneous
Delay of output signals after power failure Input signal on DI1. Function: 0=not used. 1=status on DI1. 2=door function with alarm when open. 3=door alarm when open. 4=defrost start (pulse-signal). 5=ext.main switch. 6=night operation 7=thermostat band changeover (activate r21). 8=alarm function when closed. 9=alarm function when open. 10=Appliance cleaning (pulse signal). 11=forced cooling at hot gas defrost, 12=night cover. 15=case shut down. 20=Refrigerant alarm. 21= adaptiv liquid control at short circuited Network address On/Off switch (Service Pin message) IMPORTANT! o61 must be set prior to o04 (used at LON 485 and DANBUSS only) Access code 1 (all settings) Used sensor type : 0=Pt1000, 1=Ptc1000, Readout of software version Max hold time after coordinated defrost Select signal for display view. S4% (100%=S4, 0%=S3)
Pressure transmitter working range min. value Pressure transmitter working range max. value Refrigerant setting: 1=R12. 2=R22. 3=R134a. 4=R502. 5=R717. 6=R13. 7=R13b1. 8=R23. 9=R500. 10=R503. 11=R114. 12=R142b. 13=User defined. 14=R32. 15=R227. 16=R401A. 17=R507. 18=R402A. 19=R404A. 20=R407C. 21=R407A. 22=R407B. 23=R410A. 24=R170. 25=R290. 26=R600. 27=R600a. 28=R744. 29=R1270. 30=R417A. 31=R422A. 32=R413A. 33=R422D. 34=R427A. 35=R438A. 36=R513A. 37=R407F. 38=R1234ze. 39=R1234yf. 40=R448A. 41=R449A. 42=R452A
Code 1 2 3 4 5 6 7 8 9 10 Min. d21 1 1 1 1 1 1 1 1 1 1 0
Max. 4
Fac. 0
Actual
d23
1
0 min
d27
1111
1
11 0
d40 1 1 1 1 1 1 1 1 1 1 5 min. d41 1 1 1 1 1 1 1 1 1 1 -20°C
60 min 0
2
2
240 min. 30 min.
20°C
0
n09 1 1 1 1 1 1 1 1 1 1 2°C
20°C
12
n10 1 1 1 1 1 1 1 1 1 1 2°C
20°C
3
n11 1 1 1 1 1 1 1 1 1 1 -50°C
15°C
15
n13 1 1 1 1 1 1 1 1 1 1 3 sec
6 sec
6
P86 1 1 1 1 1 1 1 1 1 1 1°C
20°C
3
P87 1 1 1 1 1 1 1 1 1 1 0°C
20°C
1
F04 1 1 1 1 1 1 1 1 1 1 -50°C
50°C
50
F05 1 1 1 1 1 1 1 1 1 1 0
2
0
F06 1 1 1 1 1 1 1 1 1 1 1 min. F07 1 1 1 1 1 1 1 1 1 1 0 %
30 min. 5
100 %
100
t01 – 1 1 1 1 1 1 1 1 1 1 0 hrs t06
t11 – 1 1 1 1 1 1 1 1 1 1 0 min. t16
t07 1 1 1 1 1 1 1 1 1 1 0 hrs t08 1 1 1 1 1 1 1 1 1 1 0 min. t45 1 1 1 1 1 1 1 1 1 1 1 day t46 1 1 1 1 1 1 1 1 1 1 1 mon. t47 1 1 1 1 1 1 1 1 1 1 0 year
23 hrs
0
59 min. 0
23 hrs
0
59 min. 0
31 day 1
12 mon. 1
99 year 0
o01 1 1 1 1 1 1 1 1 1 1 0 sec o02 1 1 1 1 1 1 1 1 1 1 0
600 sec 5
21
0
o03 1 1 1 1 1 1 1 1 1 1 0 o04 1 1 1 1 1 1 1 1 1 1 0/Off
240 1/On
0 0/Off
o05 1 1 1 1 1 1 1 1 1 1 0
o06 1 1 1 1 1 1 1 1 1 1 0/Pt
o08 1 1 1 1 1 1 1 1 1 1
o16 1 1 1 1 1 1 1 1 1 1 0 min.
o17 1 1 1 1 1 1 1 1
0 %
o20 1 1 1 1 1 1 1 1 1 1 -1 bar
o21 1 1 1 1 1 1 1 1 1 1 6 bar
o30 1 1 1 1 1 1 1 1 1 1 0
100
0
1/Ptc
0/Pt
360 min. 20
100 %
100
5 bar
-1
200 bar 12
42
0
AK-CC 550A
Instructions RI8NP702 © Danfoss 2018-09
9
Continued
Code 1 2 3 4 5 6 7 8 9 10 Min.
Input signal on DI2. Function:
o37
(0=not used. 1=status on DI2. 2=door function with alarm
when open. 3=door alarm when open. 4=defrost start
(pulse-signal). 5=ext. main switch 6=night operation
7=thermostat band changeover (activate r21). 8=alarm
function when closed. 9=alarm function when open.
10=Appliance cleaning (pulse signal). 11=forced cooling at
hot gas defrost.). 12=night cover, 13=coordinated defrost).
15=case shut down. 20=Refrigerant alarm. 21= adaptiv
liquid control at short circuited
Configuration of light function: 1=Light follows day /night
o38
operation, 2=Light control via data communication via `o39′, 3=Light control with a DI-input, 4=As “2”, but
light switch on and night cover will open if the network
cut out for more than 15 minutes.
Activation of light relay (only if o38=2) On=light
o39
Rail heat On time during day operations
o41
Rail heat On time during night operations
o42
Rail heat period time (On time + Off time)
o43
Appliance cleaning. 0=no Appliance cleaning. 1=Fans only. *** o46 2=All output Off.
Selection of EL diagram. See overview page 2 and 3
* o61
Download a set of predetermined settings. See overview * o62 page 7.
Access code 2 (partial access)
*** o64
Replace the controllers factory settings with the present
o67
settings
Input signal on DI3. Function: (high voltage input)
o84
(0=not used. 1=status on DI2. 2=door function with alarm
when open. 3=door alarm when open. 4=defrost start
(pulse-signal). 5=ext. main switch 6=night operation,
7=thermostat band changeover (activate r21). 8=Not
used. 9=Not used. 10=Appliance cleaning (pulse signal). 11=forced cooling at hot gas defrost, 12=night cover. 13=Not used. 14=Refrigeration stopped (forced
closing)). 15=case shut down. 21= adaptiv liquid control at short circuited
Rail heat control
o85
0=not used, 1=pulse control with timer function (o41
and o42), 2=pulse control with dew point function
Dew point value where the rail heat is minimum
o86
Dew point value where the rail heat is 100% on
o87
Lowest permitted rail heat effect in %
o88
Time delay from “open door” refrigeration is started
o89
Fan operation at stopped cooling (forced closing):
o90
0= Stopped (defrost allowed)
1= Running (defrost allowed)
2= Stopped (defrost not allowed)
3= Running (defrost not allowed)
1=defrost stop temperature, 2=S6 temperature,
o92
3=S5_B temperature (application 9), 4=S3B (application
10)
Display of temperature
o97
1= u56 Air temperature
2= u36 product temperature
Light and night blinds defined
o98
0: Light is switch off and night blind is open when the
main switch is off
1: Light and night blind is independent of main switch
Configuration of alarm relay
P41
The alarm relay will be activated upon an alarm signal
from the following groups:
1 – High temperature alarms
2 – Low temperature alarms 4 – Sensor error
8 – Digital input enabled for alarm
16 – Defrosting alarms 32 – Miscellaneous 64 – Injection alarms
The groups that are to activate the alarm relay must be
set by using a numerical value which is the sum of the groups that must be activated.
(E.g.: a value of 5 will activate all high temperature
alarms and all sensor error and 0 will cancel the relay function).
11111111110
11
1
111111
11
1
1 1 1 1 1 0/Off
1111
1
1 1 0%
1111
1
1 1 0%
1111
1
1 1 6 min.
11111111110
11111111111 11111111110
11111111110 1 1 1 1 1 1 1 1 1 1 0/Off
11111111110
1111
1
110
1111
1
1 1 -10°C
1111
1
1 1 -9°C
1111
1
1 1 0%
1 1 1 1 1 1 1 1 1 1 0 min.
11111111110
11111111111 11111111111 11111111110
1
11
1
10
Max. 21
Fac. 0
4
1
1/On 100 % 100 % 60 min. 2
10 6
100 1/On
21
0/Off 100 100 10 0
1 0
0 0/Off
0
2
0
50°C
8
50°C
17
100 %
30
240 min. 30
3
1
4
1
2
1
1
0
127
111
Actual
10
Instructions RI8NP702 © Danfoss 2018-09
AK-CC 550A
Continued
Service Temperature measured with S5 sensor Status on DI1 input. on/1=closed Actual defrost time (minutes) Temperature measured with S3 sensor Status on night operation (on or off ) 1=on Temperature measured with S4 sensor
Thermostat temperature Run time of thermostat (cooling time) in minutes Temperature of evaporator outlet temp. Superheat across evaporator Reference of superheat control Opening degree of AKV valve Evaporating pressure Po (relative) Evaporator temperature To (Calculated) Temperature measured with S6 sensor (product temperature) Status on DI2 output. on/1=closed Air temperature . Weighted S3 and S4 Measured temperature for alarm thermostat Status on relay for cooling Status on relay for fan Status on relay for defrost Status on relay for railheat Status on relay for alarm Status on relay for light Status on relay for valve in suction line Status on relay for compressor 2 Temperature measured with S5B sensor Temperature measured with S3B sensor Status on relay for hot gas- / drain valve Status on relay for heating element in drip tray Status on relay for night blinds Status on relay for defrost B Status on relay for heat function Readout of the actual rail heat effect 1: Thermostat 1 operating, 2: Thermostat 2 operating Status on high voltage input DI3 Readout of thermostats actual cut in value Readout of thermostats actual cut out value Readout of status on the adaptive defrost 0: Off. Function is not activated and are zero set 1: Sensor error or S3/S4 are reversed. 2: Tuning is in progress 3: Normal 4: Light build-up of ice 5: Medium build-up of ice 6: Heavy build-up of ice Number of defrosts carried out since the initial power up or since the resetting of the function Number of defrosts skipped since the initial power up or since the resetting of the function
Code 1 2 3 4 5 6 7 8 9 10
u09 u10 u11 u12 u13 u16 u17 u18 u20 u21 u22 ** u23 u25 u26 u36
1111111111 1111111111 1111111111 1111111111 1111111111 1111111111 11111111 1111111111 1111111111 1111111111 1111111111 1111111111 1111111111 1111111111 11111111
u37 u56 u57 ** u58 ** u59 ** u60 ** u61 ** u62 ** u63 ** u64 ** u67 u75 u76 ** u80 ** u81 ** u82 ** u83 ** u84 u85 u86 u87 u90 u91 U01
1111111111
1111111111
11111111
111
1
1111111111
11111
1111
1111
1
11
1
11
1
1
11
1
11111
1
1
1
1
1
1
1
1
1
1111
1
11
1111111111
1111111111
1111111111
1111111111
1111111111
U10 1 1 1 1 1 1 1 1 1 1 U11 1 1 1 1 1 1 1 1 1 1
Min.
*) Can only be set when regulation is stopped (r12=0) **) Can be controlled manually, but only when r12=-1 ***) With access code 2 the access to these menus will be limited
Factory setting If you need to return to the factory-set values, it can be done in this way: – Cut out the supply voltage to the controller – Keep upper and lower button depressed at the same time as you reconnect the supply voltage
Factory settings are indicated for standard units. Other code numbers have customized settings.
Max.
Fac. Actual
AK-CC 550A
Instructions RI8NP702 © Danfoss 2018-09
11
Fault message
In an error situation the LED’s on the front will flash and the alarm relay will be activated. If you push the top button in this situation you can see the alarm report in the display. There are two kinds of error reports – it can either be an alarm occurring during the daily operation, or there may be a defect in the installation.
A-alarms will not become visible until the set time delay has expired. E-alarms, on the other hand, will become visible the moment the error occurs. (An A alarm will not be visible as long as there is an active E alarm). Here are the messages that may appear:
Code / Alarm text via data communication
Description
Alarm relay groups (P41)
A1/— High t.alarm High temperature alarm
1
A2/— Low t. alarm Low temperature alarm
2
A4/— Door alarm Door alarm
8
A5/— Max hold time The “o16” function is activated during
16
a coordinated defrost
A10/— Inject prob. Control problem
64
A11/— No Rfg. sel. No refrigerant selected
64
A13/— High temp Temperature alarm. High S6
1
S6
A14/— Low temp S6 Temperature alarm. Low S6
2
A15/— DI1 alarm DI1 alarm
8
A16/— DI2 alarm DI2 alarm
8
A45/— Standby
Standby position (stopped refrigera-
–
mode
tion via r12 or DI input)
A59/— Case clean Case cleaning. Signal from DI input
–
AA2/ —Refrig Leak A refrigerant leak detection signal is
8
received
AA3/— CO2 alarm A refrigerant leak detection signal is
8
received and the selected refrigerant
is CO2
— AD fault
Error in the adaptive defrost function
16
— AD Iced
Evaporator is iced up. Reduction of
16
air flow
— AD not defr.
Defrost of evaporator is not
16
satisfactory
— AD flashgas.
Flash gas is formed at the valve
16
E1/— Ctrl. error
Faults in the controller
32
E6/— RTC error
Check clock
32
E20/— Pe error
Error on pressure transmitter Pe
64
E24/— S2 error
Error on S2 sensor
4
E25/— S3 error
Error on S3 sensor
4
E26/— S4 error
Error on S4 sensor
4
E27/— S5 error
Error on S5 sensor
4
E28/— S6 error
Error on S6 sensor
4
E34/ — S3 error B Error on S3B sensor
4
E37/— S5 error B Error on S5B sensor
4
—/— Max Def.Time Defrost stopped based on time in-
16
stead of, as wanted, on temperature
Operating status
(Measurement)
The controller goes through some regulating situations where it is just waiting for the next point of the regulation. To make these “why is nothing happening” situations visible, you can see an operating status on the display. Push briefly (1s) the upper button. If there is a status code, it will be shown on the display. The individual status codes have the following meanings:
Normal regulation
S0
Waiting for end of the coordinated defrost
S1
When the compressor is operating it must run for at least S2 x minutes. When the compressor is stopped, it must remain stopped S3 for at least x minutes. The evaporator drips off and waits for the time to run out S4
Refrigeration stopped by main switch. Either with r12 or S10
a DI-input
Refrigeration stopped by thermostat
S11
Defrost sequence. Defrost in progress
S14
Defrost sequence. Fan delay — water attaches to the
S15
evaporator
Refrigeration stopped due to open ON input or stopped S16 regulation
Door is open. DI input is open
S17
Melt function in progress. Refrigeration is interrupted S18
Modulating thermostat control
S19
Emergency cooling due to sensor error
S20
Regulation problem in the injections function
S21
Start-up phase 2. Evaporator being charged
S22
Adaptive control
S23
Start-up phase 1. Signal reliability from sensors is
S24
controlled
Manual control of outputs
S25
No refrigerant selected
S26
Case cleaning
S29
Forced cooling
S30
Delay on outputs during start-up
S32
Heat function r36 is active
S33
Case shutdown
S45
Operation with adaptiv liquid control
S48
Other displays:
The defrost temperature cannot be displayed. There is non stop based on time
Defrost in progress / First cooling after defrost
-d-
Password required. Set password
PS
Regulation is stopped via main switch
OFF
Ctrl. state: (Shown in all menu displays)
0 1 2
3
4 10
11 14 15
16
17 18 19 20 21 22 23 24
25 26 29 30 32 33 45 48
*) Emergency cooling will take effect when there is lack of signal from a defined S3 or S4 sensor or signal from the pressure transmitter is outside signal range. The regulation will continue with a registered average cutin frequency. There are two registered values one for day operation and one for night operation.
Data communication The importance of individual alarms can be defined with a setting. The setting must be carried out in the group “Alarm destinations”
Settings from
System manager High Middle Low Log only Disabled
Settings from
Log
AKM (AKM destination)
1
X
2
X
3
X
X
Alarm relay
Send via
Non
High
Low-High
Network
X
X
X
X
X
X
X
ADAP-KOOL®
12
Instructions RI8NP702 © Danfoss 2018-09
AK-CC 550A
Documents / Resources
![]() |
Danfoss AK-CC 550A Case Room Controller [pdf] Instructions AK-CC 550A Case Room Controller, AK-CC 550A, Case Room Controller, Room Controller |