AK-CC 250A Electronic Controller
Product Information
Specifications:
- Model: AK-CC 250A
- Power: 2.5 VA
- Input Voltage: 10 V < U < 256 V
- Certifications: CE (250 V a.c.), UL (240 V a.c.)
- Relay Ratings:
- DO1. Refrigeration: 8 (6) A, 10 A Resistive 5FLA, 30LRA
- DO2. Defrost: 8 (6) A, 10 A Resistive 5FLA, 30LRA
- DO3. Fan or refrigeration: 6 (3) A, 6 A Resistive 3FLA, 18LRA
131 VA Pilot duty - DO4. Alarm, light, rail heat or hot gas defrost: 4 (1) A, 4 A
Resistive Min. 100 mA 131 VA Pilot duty
Product Usage Instructions
Setting Up:
- Open parameter r12 and stop the regulation.
- Open parameter o06 and set the used sensor type.
- Select electric connection based on the drawings on page
2. - Open parameter o61 and set the electric connection number in
it. - Select one of the preset settings from the table on the
right-hand side. - Open parameter o62 and set the number for the array of
presettings. - Open parameter r12 and start the regulation.
- Review factory settings and make necessary changes in
respective parameters. - If using a network:
- Set the address in o03.
- Start scan function in the system unit.
Auxiliary Table for Settings (Quick-setup):
Preset settings (o62) | Defrost stop on time | Case |
---|---|---|
1 | 100% | Defrost stop on S5 |
Parameters Function Codes:
- r01: Normal operation Temperature (set point)
- r02: Max. limitation of set point setting
- r03: Min. limitation of set point setting
Frequently Asked Questions (FAQ)
Q: What are the relay ratings for DO1 and DO2?
A: DO1 and DO2 are 16 A relays with ratings of 8 (6) A and 10 A
Resistive 5FLA, 30LRA.
Q: How to set up data communication using MOD-BUS?
A: To set up data communication using MOD-BUS, refer to the
instructions provided in the manual under section “Data
communication MOD-BUS: 06-2015 RI8PG302.”
INSTRUCTIONS
AK-CC 250A
tamb = 0 – +55°C 230 V a.c. 50/60 Hz
2.5 VA
10 V < U < 256 V
CE (250 V a.c.)
UL *** (240 V a.c.)
DO1. Refrigeration *
8 (6) A
10 A Resistive 5FLA, 30LRA
DO2. Defrost *
8 (6) A
10 A Resistive 5FLA, 30LRA
DO3. Fan or refrigeration 2 *
6 (3) A
6 A Resistive 3FLA, 18LRA 131 VA Pilot duty
DO4. Alarm, light, rail heat 4 (1) A
4 A Resistive
or hotgas defrost *
Min. 100 mA**
131 VA Pilot duty
* DO1 and DO2 are 16 A relays. DO3 and DO4 are 8 A relays. Max. load must be keept.
** Gold plating ensures make function with small contact loads
*** UL-approval based on 30000 couplings
Coordinated defrost
Pt /PTC sensors See page 6.
Data communication MOD-BUS:
06-2015
RI8PG302
No Function
o61 — Electrical connections
1
*)
2
*)
Danfoss 84B2429.13
Danfoss 84B2428.12
Danfoss 84B2430.13
3
*)
4
*)
5
*)
6
*)
7
*)
8
*)
9
*)
10
*)
! ! !
2
*) DI1, DI2:
AU: Guld, Gold, Or, Oro l = max. 15 m
Instructions RI8PG302 © Danfoss 06/2015
AK-CC 250A
English
Setting:
1 Open parameter r12 and stop the regulation
2 Open parameter o06 and set the used sensor type
3 Select electric connection based on the drawings on page 2
4 Open parameter o61 and set the electric connection number in it
5 Now select one of the preset settings from the table on the right-hand side
6 Open parameter o62 and set the number for the array of presettings
7 Open parameter r12 and start the regulation
8 Go through the survey of factory settings. Make any necessary changes in the respective parameters.
9 For network. a. Set the address in o03 b. Start scan function in the system unit.
Auxiliary table for settings (quick-setup)
Defrost stop on
time
Case
Defrost stop on S5
Preset settings (o62)
1
2
3
Temperature (SP) Max. temp. setting (r02) Min. temp. setting (r03) Sensor signal for thermostat. S4% (r15) Alarm limit high (A13) Alarm limit low (A14) Sensor signal for alarm funct.S4% (A36) Interval between defrost (d03) Defrost sensor: 0=time, 1=S5, 2=S4 (d10) DI1 config. (o02) Sensor signal for display view S4% (017)
4°C
2°C
-24°C
6°C
4°C
-22°C
2°C
0°C
-26°C
100%
10°C
8°C
-15°C
-5°C
-5°C
-30°C
100%
6 h
6h
12h
0
1
1
Case cleaning =10
100%
Room
Defrost stop on
time
4
Defrost stop on S5
5
6
6°C
3°C
-22°C
8°C
5°C
-20°C
4°C
1°C
-24°C
0%
10°C
8°C
-15°C
0°C
0°C
-30°C
0%
8h
8h
12h
0
1
1
Door function =3
0%
Array 1-6: The settings in the grey fields will be changed
Parameters
Function
Codes 1
Normal operation
Temperature (set point)
—
Thermostat
Differential
*** r01
Max. limitation of stepson setting
*** r02
Min. limitation of set point setting
*** r03
Adjustment of temperature indication
r04
Temperature unit (°C/°F)
r05
Correction of the signal from S4
r09
Correction of the signal from S3
r10
Manual service, stop regulation, start regulation (-1, 0, 1)
r12
Displacement of reference during night operation
r13
Definition and weighting, if applicable, of thermostat sensors
r15
– S4% (100%=S4, 0%=S3)
The heating function is started a number of degrees below the
r36
thermostats cutout temperature
Activation of reference displacement r40
r39
Value of reference displacement (activate via r39 or DI)
r40
Alarm
Delay for temperature alarm
A03
Delay for door alarm
*** A04
Delay for temperature alarm after defrost
A12
High alarm limit
*** A13
Low alarm limit
*** A14
Alarm delay DI1
A27
Alarm delay DI2
A28
Signal for alarm thermostat. S4% (100%=S4, 0%=S3)
A36
Compressor
Min. ON-time
c01
Min. OFF-time
c02
Time delay for cutin of comp.2
c05
Compressor relay 1 must cutin and out inversely
c30
(NC-function)
Defrost
Defrost method (none/EL/GAS/BRINE)
d01
Defrost stop temperature
d02
Interval between defrost starts
d03
Max. defrost duration
d04
Displacement of time on cutin of defrost at start-up
d05
Drip off time
d06
Delay for fan start after defrost
d07
Fan start temperature
d08
Fan cutin during defrost
d09
0: Stopped
1: Running
2: Running during pump down and defrost
Defrost sensor (0=time, 1=S5, 2=S4)
d10
Pump down delay
d16
Drain delay
d17
Max. aggregate refrigeration time between two defrosts
d18
Defrost on demand – S5 temperature’s permitted variation dur-
d19
ing frost build-up. On central plant choose 20 K (=off )
Delay of hot gas injection
d23
EL-diagram number (page 2)
Min.-
2 3 4 5 6 7 8 9 10 value
Max.- Factory Actual value setting setting
-50.0°C 50.0°C 2.0°C
0.0 K -49.0°C -50.0°C -20.0 K
°C -10.0 K -10.0 K
-1 -10.0 K
0%
20.0K 50°C 49.0°C 20.0 K
°F +10.0 K +10.0 K
1 10.0 K 100%
2.0 K 50.0°C -50.0°C 0.0 K
°C 0.0 K 0.0 K
0 0.0 K 100%
-15.0 K -3.0 K -15.0 K
OFF
ON
-50.0 K 50.0 K
OFF 0.0 K
0 min 0 min 0 min -50.0°C -50.0°C 0 min 0 min
0%
240 min 240 min 240 min 50.0°C 50.0°C 240 min 240 min
100%
30 min 60 min 90 min 8.0°C -30.0°C 30 min 30 min 100%
0 min 0 min 0 sec
0 OFF
30 min 30 min 999 sec
1 ON
0 min 0 min 0 sec
0 OFF
no 0.0°C 0 hours 0 min 0 min 0 min 0 min -15.0°C
0
bri 25.0°C 48 hours 180 min 240 min 60 min 60 min 0.0°C
2
EL 6.0°C 8 hours 45 min 0 min 0 min 0 min -5.0°C
1
0 0 min 0 min 0 hours 0.0 K
2 60 min 60 min 48 hours 20.0 k
0 0 min 0 min 0 hours 20.0 K
0 min 60 min 0 min
AK-CC 250A
Instructions RI8PG302 © Danfoss 06/2015
3
1 2 3 4 5 6 7 8 9 10
Fan
Fan stop at cutout compressor
F01
no
yes
no
Delay of fan stop
F02
0 min 30 min 0 min
Fan stop temperature (S5)
F04
-50.0°C 50.0°C 50.0°C
HACCP
Actual temperature measurement for the HACCP function
h01
Last registered peak temperature
h10
Selection of function and sensor for the HACCP function. 0 = no
h11
0
2
0
HACCP function. 1 = S4 used (maybe also S3). 2 = S5 used
Alarm limit for the HACCP function
h12
-50.0°C 50.0°C 8.0°C
Time delay for the HACCP alarm
h13
0 min. 240 min. 30 min.
Select signal for the HACCP function. S4% (100% = S4, 0% = S3)
h14
0%
100% 100%
Real time clock
Six start times for defrost.
t01-t06
0 hours 23 hours 0 hours
Setting of hours.
0=OFF
Six start times for defrost.
t11-t16
0 min 59 min 0 min
Setting of minutes.
0=OFF
Clock – Setting of hours
*** t07
0 hours 23 hours 0 hours
Clock – Setting of minute
*** t08
0 min 59 min 0 min
Clock – Setting of date
*** t45
1
31
1
Clock – Setting of month
*** t46
1
12
1
Clock – Setting of year
*** t47
0
99
0
Miscellaneous
Delay of output signals after start-up
o01
0 s
600 s
5 s
Input signal on DI1. Function:
o02
1
11
0
0=not used. 1=status on DI1. 2=door function with alarm when
open. 3=door alarm when open. 4=defrost start (pulse-pres-
sure). 5=ext.main switch. 6=night operation 7=change refer-
ence (activate r40). 8=alarm function when closed. 9=alarm
function when open. 10=case cleaning (pulse pressure).
11=forced cooling at hot gas defrost.
Network address (0=off )
o03
0
240
0
Access code 1 (all settings)
o05
0
100
0
Used sensor type. See page 6.
o06
Pt
P02
Pt
Pt: Pt 1000 @ 0°C
P01: PTC 1000 (nominal 990 ) = EKS 111
P02: PTC 1000 @ 25°C (nominal 1000 )
Display step = 0.5 (normal 0.1 at Pt sensor)
o15
no
yes
no
Max hold time after coordinated defrost
o16
0 min 60 min 20
Select signal for display view. S4% (100%=S4, 0%=S3)
o17
0%
100% 100%
Input signal on DI2. Function:
o37
0
12
0
(0=not used. 1=status on DI2. 2=door function with alarm when
open. 3=door alarm when open. 4=defrost start (pulse-pres-
sure). 5=ext. main switch 6=night operation 7=change refer-
ence (activate r40). 8=alarm function when closed. 9=alarm
function when open. 10=case cleaning (pulse pressure).
11=forced cooling at hot gas defrost.). 12=coordinated defrost)
Configuration of light function (relay 4)
o38
1
3
1
1=ON during day operation. 2=ON / OFF via data communica-
tion. 3=ON follows the DI-function, when DI is selected to door
function or to door alarm
Activation of light relay (only if o38=2)
o39
OFF
ON
OFF
Rail heat On time during day operations
o41
0%
100%
0
Rail heat On time during night operations
o42
0%
100%
0
Rail heat period time (On time + Off time)
o43
6 min 60 min 10 min
Case cleaning. 0=no case cleaning. 1=Fans only. 2=All output *** o46
0
2
0
Off.
Selection of EL diagram. See overview page 2
* o61*
1
10
1
Download a set of predetermined settings. See overview
* o62*
0
6
0
previous page.
Access code 2 (partly access)
*** o64
0
100
0
Save the controllers present settings to the programming key.
o65
0
25
0
Select your own number.
Load a set of settings from the programming key (previously
o66*
0
25
0
saved via o65 function)
Replace the controllers factory settings with the present set-
o67
OFF
On
OFF
tings
Service
Status codes are shown on page 5
S0-S33
Temperature measured with S5 sensor
*** u09
Status on DI1 input. on/1=closed
u10
Temperature measured with S3 sensor
*** u12
Status on night operation (on or off ) 1=closed
*** u13
Temperature measured with S4 sensor
*** u16
Thermostat temperature
u17
Read the present regulation reference
u28
Status on DI2 output. on/1=closed
u37
Temperature shown on display
u56
Measured temperature for alarm thermostat
u57
Status on relay for cooling
** u58
Status on relay for fan
** u59
4
Instructions RI8PG302 © Danfoss 06/2015
AK-CC 250A
Status on relay for defrost Status on relay for rail heat Status on relay for alarm Status on relay for light Status on relay for valve in suction line Status on relay for compressor 2
** u60 ** u61 ** u62 ** u63 ** u64 ** u67
*) Can only be set when regulation is stopped (r12=0) **) Can be controlled manually, but only when r12=-1 ***) With access code 2 the access to these menus will be limited
Factory settings are indicated for standard units. Other code numbers have customized settings.
Fault code display
E 1
Fault in controller
E 6
Change battery + check clock
E 25 S3 sensor error
E 26 S4 sensor error
E 27 S5 sensor error
Alarm code display A 1 High temperature alarm A 2 Low temperature alarm A 4 Door alarm A 5 Max. Hold time A 15 DI 1 alarm A 16 DI 2 alarm A 45 Standby mode A 59 Case cleaning A 60 HACCP alarm
SW = 2.3x
Status code display
S0
Regulating
S 1
Waiting for end of the coordinated defrost
S 2
ON-time Compressor
S 3
OFF-time Compressor
S 4
Drip-off time
S 10 Refrigeration stopped by main switch
S 11 Refrigeration stopped by thermostat
S 14 Defrost sequence. Defrosting
S 15 Defrost sequence. Fan delay
S 17 Door open (open DI input)
S 20 Emergency cooling
S 25 Manual control of outputs
S 29 Case cleaning
S 30 Forced cooling
S 32 Delay of output at start-up
S33 Heat function r36 is active
non The defrost temperature cannot be dis-
played. There is stop based on time
-d-
Defrost in progress
PS
Password required
The buttons
Set menu 1. Push the upper button until a parameter
r01 is shown 2. Push the upper or the lower button and
find that parameter you want to change 3. Push the middle button until the
parameter value is shown 4. Push the upper or the lower button and
select the new value 5. Push the middle button again to enter
the value.
Cutout alarm relay / receipt alarm/see alarm code · Push short the upper button
Set temperature 1. Push the middle button until the
temperature value is shown 2. Push the upper or the lower button and
select the new value 3. Push the middle button to select the
setting.
Reading the temperature at defrost sensor · Push briefly the lower button
Manuel start or stop of a defrost · Push the lower button for four seconds.
(Though not for application 4).
See HACCP registration 1. Give the middle button a long push until
h01 appears 2. Select required h01-h10 3. See value by giving the middle button a
short push
AK-CC 250A
Instructions RI8PG302 © Danfoss 06/2015
LED Light emitting diode = refrigeration = defrost = fan running Flashes fast at alarm
HACCP HACCP function is active
5
Sensor overview
o06 Pt: Pt 1000 @ 0°C (AKS 11, AKS 12, AKS 21) P01: PTC 1000 (nominal 990 ) = EKS 111 P02: PTC 1000 @ 25°C (nominal 1000 )
Pt 1000 @ 0°C
PTC 1000 PTC 1000 @ 25°C
AKS 11, AKS 12, AKS 21
KTY81-121 KTY81-110 EKS 111
°C
30
1167.7
1029
1040
25
1097.3
990
1000
20
1077.9
951
961
15
1058.5
914
923
10
1039.0
877
886
5
1019.5
841
850
0
1000.0
807
815
-5
980.4
773
781
-10
960.9
740
747
-15
941.2
708
715
-20
921.6
677
684
-25
901.9
647
653
-30
882.2
617
624
-35
862.5
589
595
-40
842.7
562
567
Carel:
TSH/TST/TSM/ TSQ/PT1
Dixell:
PMG/PMP/PMT
Carel:
03/06/015
Dixell:
S6
Elliwell:
SN6/SN7
Lae:
ST1K.CP
Frigo:
VX6
o06
Pt
P01
P02
AK-CC 250A Additional information: Weitere Information: Renseignements supplémentaires: Yderligere information: Información adicional: Ytterligare information: Aanvullende informatie:
English Manual Deutsches Manual Manuel en français Dansk Manual Manual español Svenska Handbok Dutch Handleiding
RS8GC…
www.danfoss.com
ADAP-KOOL®
The Product contains electrical components And may not be disposed together with domestic waste. Equipment must be separate collected with Electrical and Electronic waste. According to Local and currently valid legislation.
6
Instructions RI8PG302 © Danfoss 06/2015
AK-CC 250A
Documents / Resources
![]() |
Danfoss AK-CC 250A Electronic Controller [pdf] Installation Guide 84B2429.13, 84B2428.12, 84B2430.13, AK-CC 250A Electronic Controller, AK-CC 250A, Electronic Controller, Controller |